Construction | Splice 3-2-16 | A | 3/2/2016 | JIMA | JIMA | changed wall types at shaft | | Construction | 851694 |
Out to Review | Splice 3-2-16 | / | 3/2/2016 | REBECCA | REBECCA | walking | | Out to Review | 851672 |
To Be Scanned Bin | Original | / | 11/20/2015 | | KENYATTA | Location = To Be Scanned Bin by KENYATTA | | To Be Scanned Bin | 831747 |
Plan Coordinator | Original | / | 11/20/2015 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 831731 |
Electrical | Original | A | 11/20/2015 | DOUG | DOUG | | | Electrical | 831730 |
Electrical | Original | / | 11/20/2015 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 831697 |
Electrical | Original | / | 11/20/2015 | | NELIDA | Location = Electrical by NELIDA | | Electrical | 831659 |
Resubmittal 2 | Original | / | 11/20/2015 | NELIDA | NELIDA | Resubmittal #2 11/20/15 | | Resubmittal 2 | 831658 |
Out to Review | Original | / | 11/20/2015 | NELIDA | NELIDA | Ryan 720-271-2884 | | Out to Review | 831594 |
Finished Bin | Original | / | 11/13/2015 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 830137 |
Electrical | Original | D | 11/13/2015 | DOUG | DOUG | | | Electrical | 830136 |
Plan Coordinator | Original | / | 11/13/2015 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 830109 |
Mechanical | Original | A | 11/13/2015 | JUSTINC | JUSTINC | | | Mechanical | 830108 |
Mechanical | Original | / | 11/13/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 830095 |
Mechanical | Original | / | 11/13/2015 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 830037 |
Plan Coordinator | Original | / | 11/13/2015 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 830036 |
Construction | Original | A | 11/13/2015 | DANM | DANM | | | Construction | 830034 |
Construction | Original | / | 11/12/2015 | DANM | DANM | In Current Review by DANM | | Construction | 829835 |
Construction | Original | / | 11/12/2015 | | JANE | Location = Construction by JANE | | Construction | 829746 |
Resubmittal 1 | Original | / | 11/12/2015 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 829745 |
Electrical | Original | D | 11/12/2015 | DOUG | DOUG | See comments 3 and 5 prior. Metered load on EL3N3 exceeds capacity. Verify Circuit feeding EL3N3 back to ED10. Meter ED12 or calculate load. | | Electrical | 829738 |
Out to Review | Original | / | 10/27/2015 | NELIDA | NELIDA | Chris 719-491-0247 | | Out to Review | 825885 |
Finished Bin | Original | / | 10/26/2015 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 825690 |
Hazmat | Original | A | 10/22/2015 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 824914 |
CO Springs Fire | Original | A | 10/20/2015 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 824077 |
Fire | Original | / | 10/12/2015 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 822425 |
CO Springs DRE | Original | N | 10/12/2015 | RDCUSER | RDCUSER | INTERIOR REMODEL, NO SIGNIFICANT CHANGE OF USE. (see full review) | | CO Springs DRE | 822424 |
Zoning/Planning | Original | / | 10/9/2015 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 822208 |
Plan Coordinator | Original | / | 10/9/2015 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 822154 |
Electrical | Original | D | 10/9/2015 | DOUG | DOUG | 1. Provide load data for panel ED2 2. Circuit feeding EL5N2, EL6N2, and EL7N2 appears overloaded. Clarify how panels connect and load on EL5N2. 3. Circuit feeding EL3N3 and EL4N3 needs loading indicated. Show size of fuse and switch and how panels connect to/through each other. Show load on panel EL3N3. 4. Provide load for D2N2. 5. Verify panel ED12 has no other loads than shown on one-line. 6. Comply NEC 517.13 Wiring in patient care areas. 7. Comply 517.30(C)(3) Raceways for Patient Care. 8. Two sheets labeled E802 | | Electrical | 822153 |
Electrical | Original | / | 10/8/2015 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 821877 |
Electrical | Original | / | 10/8/2015 | | RITA | Location = Electrical by RITA | | Electrical | 821660 |
Plan Coordinator | Original | / | 10/8/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 821655 |
Plumbing | Original | A | 10/8/2015 | TCRIPPEN | TCRIPPEN | | | Plumbing | 821654 |
Plumbing | Original | / | 10/8/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 821652 |
Plumbing | Original | / | 10/7/2015 | | RITA | Location = Plumbing by RITA | | Plumbing | 821428 |
Plan Coordinator | Original | / | 10/7/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 821423 |
Mechanical | Original | D | 10/7/2015 | RUSSELL | RUSSELL | Cannot locate on plan, FC 6-1, need to provide a F/S damper at new exhaust duct out of shaft | | Mechanical | 821422 |
Mechanical | Original | / | 10/7/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 821337 |
Mechanical | Original | / | 10/6/2015 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 820926 |
Plan Coordinator | Original | / | 10/6/2015 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 820912 |
Construction | Original | D | 10/6/2015 | DANM | DANM | Specify materials on two of three partition details See plans Walk-through review OK | | Construction | 820910 |
Construction | Original | / | 10/5/2015 | DANM | DANM | In Current Review by DANM | | Construction | 820701 |
Construction | Original | / | 10/5/2015 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 820585 |
Plan Coordinator | Original | / | 10/5/2015 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 820568 |
Enumeration | Original | A | 10/5/2015 | BRENT | BRENT | multiple floors, single tenant | | Enumeration | 820567 |
Floodplain | Original | N | 10/2/2015 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 820396 |