Plan Coordinator | Splice 3-31-16 | / | 4/1/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 859910 |
Plumbing | Splice 3-31-16 | A | 4/1/2016 | TCRIPPEN | TCRIPPEN | Add note to show wrap on PVC installed in plenum | | Plumbing | 859908 |
Plumbing | Splice 3-31-16 | / | 4/1/2016 | | DALEH | Location = Plumbing by DALEH | | Plumbing | 859707 |
Mechanical | Splice 3-31-16 | A | 4/1/2016 | DALEH | DALEH | revised drawing to plenum return system, revised to show wrap on PVC installed in plenum | | Mechanical | 859705 |
Mechanical | Splice 3-31-16 | / | 3/31/2016 | | REBECCA | Location = Mechanical by REBECCA | | Mechanical | 859606 |
Scanned/Finished Bin | Original | / | 1/21/2016 | | RITA | Location = Scanned/Finished Bin by RITA | | Scanned/Finished Bin | 842425 |
Waste Water Div | Original | A | 1/20/2016 | NELIDA | NELIDA | see label | | Waste Water Div | 842312 |
Electrical | Original | A | 1/20/2016 | SHELBY | SHELBY | | | Electrical | 842306 |
Plumbing | Original | A | 1/20/2016 | TCRIPPEN | TCRIPPEN | will work with engineers water pipe size analysis data | | Plumbing | 842243 |
Plumbing | Original | D | 1/20/2016 | TCRIPPEN | TCRIPPEN | Need water pipe size analysis data on plans. | | Plumbing | 842185 |
Mechanical | Original | A | 1/20/2016 | JUSTINC | JUSTINC | | | Mechanical | 842144 |
CO Springs Fire | Original | A | 1/15/2016 | CSFIRE | CSFIRE | | wtaylor | CO Springs Fire | 841680 |
Out to Review | Original | / | 1/15/2016 | REBECCA | REBECCA | kyle 316-209-5296 | | Out to Review | 841653 |
Finished Bin | Original | / | 1/15/2016 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 841578 |
Hazmat | Original | A | 1/14/2016 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 841400 |
Enumeration | Original | A | 12/29/2015 | BRENT | BRENT | tenant wants to keep 721 N Academy as it is already posted on the door and the lease is at that address. our suggestion was to change to 719 N. Academy. | | Enumeration | 838490 |
Out to Review | Original | / | 12/22/2015 | NELIDA | NELIDA | Kyle 316-209-5296 | | Out to Review | 837503 |
Finished Bin | Original | / | 12/16/2015 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 836276 |
Water Division | Original | A | 12/16/2015 | CSUREVIEW | CSUREVIEW | All comments addressed. Taken plan set to RBD counter AJ 12/16/15 | ajuvera | Water Division | 836268 |
Out to Review | Original | / | 12/16/2015 | JANE | JANE | Al at CSU | | Out to Review | 836267 |
Finished Bin | Original | / | 12/11/2015 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 835620 |
Waste Water Div | Original | D | 12/11/2015 | CSUREVIEW | CSUREVIEW | Approved utility construction plans are still missing. (mt_12/11/2015) | mtroche | Waste Water Div | 835507 |
Waste Water Div | Original | D | 12/11/2015 | CSUREVIEW | CSUREVIEW | Provide copy of variance to have an inside grease trap instead of an outside grease interceptor and address it. By example, the trap must have a capacity of 250 pounds of grease sludge, at least. (mt_12/11/2015) | mtroche | Waste Water Div | 835505 |
CSU Utilities | Original | / | 12/10/2015 | | CSFIRE | Location = CSU Utilities by CSFIRE | dwithee | CSU Utilities | 835331 |
Hazmat | Original | D | 12/10/2015 | CSFIRE | CSFIRE | | dwithee | Hazmat | 835330 |
CO Springs Fire | Original | D | 12/10/2015 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 835329 |
Fire | Original | / | 12/7/2015 | | KENYATTA | Location = Fire by KENYATTA | | Fire | 834513 |
Plan Coordinator | Original | / | 12/7/2015 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 834507 |
Mechanical | Original | D | 12/7/2015 | JUSTINC | JUSTINC | #1 - Per Fs-2 CO2 tank shown with alarm, also need to provide sensor, installation instructions for Fire and Mechanical inspectors. Also need size of tank provided and all details shown on plans not 8 1/2" x 11". #2 - Cannot locate any information on walk-in cooler on plans. Need refrig. type and quantity shown on plan. 8 1/2" x 11" sheet only indicates type. #3 - Verify note 13 on plan page MEP1.0 #4 - RTU's # 1 & 2 cannot run continuous. Need to be interlocked with EF-3 to be within 10% negative in kitchen. RTU #3 allowable to run continuous during occupied hours. #5 - Need to provide FULL installation instructions for plan review and field inspection, Verify and provide letter from TURBOCHEF engineering to PPRBD showing installing oven inside enclosure will not void UL710B listing. Show all options used to achieve UL710B as required. Units UL listing from info provided is as stand-alone equip. not tested in enclosure.
Return redline comments for re-review | | Mechanical | 834506 |
Mechanical | Original | / | 12/4/2015 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 834148 |
Mechanical | Original | / | 12/4/2015 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 834134 |
Enumeration | Original | D | 12/4/2015 | JEANNINE | JEANNINE | The Code Study Form has not been corrected per the Tax ID Number for the property and the legal description. Verify that the Pizza company that is going in knows that 719 N. Academy is to be the address; not the 721 as shown on the plan. The plan will need to be corrected to reflect the address that is assigned prior to approval. | | Enumeration | 834125 |
Plan Coordinator | Original | / | 12/4/2015 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 834119 |
Elevators | Original | / | 12/3/2015 | | JANE | Location = Elevators by JANE | | Elevators | 834008 |
Enumeration | Original | / | 12/3/2015 | | JANE | Location = Enumeration by JANE | | Enumeration | 833949 |
Resubmittal 1 | Original | / | 12/3/2015 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 833948 |
Out to Review | Original | / | 11/20/2015 | | JANE | Location = Out to Review by JANE | | Out to Review | 831668 |
Finished Bin | Original | / | 11/18/2015 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 831077 |
CSU Contract Admin. | Original | N | 11/18/2015 | CSUAPPSPRM | CSUAPPSPRM | Water service to be fed from existing 1.5" building housemeter. Plan returned to RBD counter. BTE | Benglish | CSU Contract Admin. | 831046 |
CSU Contract Admin. | Original | / | 11/18/2015 | | RITA | Location = CSU Contract Admin. by RITA | | CSU Contract Admin. | 830871 |
Waste Water Div | Original | D | 11/18/2015 | CSUREVIEW | CSUREVIEW | Need to show existing or proposed grease interceptor as well as calculation sheets for this project. Taken plan set to RBD counter down stairs. | ajuvera | Waste Water Div | 830758 |
Water Division | Original | N | 11/18/2015 | CSUREVIEW | CSUREVIEW | No new water services being proposed. Taken plan set to RBD counter down stairs. | ajuvera | Water Division | 830753 |
Gas/Elec. Utils | Original | N | 11/18/2015 | CSUREVIEW | CSUREVIEW | Call electric/gas Field Engineering at 719-668-5564 for any questions you might have on this project. Taken plan set to RBD counter down stairs. | ajuvera | Gas/Elec. Utils | 830751 |
Hazmat | Original | D | 11/16/2015 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 830638 |
CSU Utilities | Original | / | 11/16/2015 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 830637 |
CO Springs Fire | Original | D | 11/16/2015 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 830636 |
Fire | Original | / | 11/5/2015 | | MMCCONNELL | Location = Fire by MMCCONNELL | | Fire | 828335 |
CO Springs DRE | Original | A | 11/5/2015 | MMCCONNELL | MMCCONNELL | interior remodel. new restaurant. Parked at commercial center. (see full review) | | CO Springs DRE | 828334 |
Health Dept. | Original | A | 11/4/2015 | HEALTHDEPT | HEALTHDEPT | Plans are approved per comment sheet. A Preopening inspection is required for final approval of the facility. MGirard (719) 575-8688 | MGirard | Health Dept. | 827881 |
Zoning/Planning | Original | / | 10/30/2015 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 827099 |
Plan Coordinator | Original | / | 10/30/2015 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 827090 |
Electrical | Original | A | 10/30/2015 | DOUG | DOUG | | | Electrical | 827089 |
Electrical | Original | / | 10/29/2015 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 826622 |
Electrical | Original | / | 10/28/2015 | | RITA | Location = Electrical by RITA | | Electrical | 826400 |
Plan Coordinator | Original | / | 10/28/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 826347 |
Plumbing | Original | A | 10/28/2015 | TCRIPPEN | TCRIPPEN | All fixtures except the bath rooms shall go to the grease trap, the grease trap shall not be indirect waste provide variance letter for inside grease trap this show what fixtures must be on the grease trap.Provide cut sheets for lavatory's, all gas pipe and gas related items to be on the M-pages per our web site. Correct all red lines. No walk through | | Plumbing | 826346 |
Plumbing | Original | / | 10/28/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 826272 |
Plumbing | Original | / | 10/26/2015 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 825611 |
Plan Coordinator | Original | / | 10/26/2015 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 825583 |
Mechanical | Original | / | 10/26/2015 | | JUSTINC | Location = Mechanical by JUSTINC | | Mechanical | 825582 |
Mechanical | Original | D | 10/26/2015 | JUSTINC | JUSTINC | MEP 1.0 - Need gas piping length from meter to most remote appliance provided to verify gas pipe sizing. NO GAS REVIEW DONE. (2) New RTU's over 300lbs. Need structural letter or plan sheet to verify structure is adequate.
M1.0 - Grease duct shall be 16 ga. steel off type I hood. Label exhaust fans as EF-1, EF-2. Type I hood info, shall be provided on full size sheet, see plan for additional hood req. Need communication open between kitchen and dining for makeup air. Need CO2 tank size provided, with alarm, sensor, and detector. per CSFD with installation instructions. Need refg. type and quality provided for walk-in freezer/ cooler.
M2.0 - Test and balance report to inspector at time of heating final. Adjust O.S.A schedule per comments.
M3.0 - Fix up-blast E.F detail as noted. Provide detail of how supporting/ hanging fabric duct sock. | | Mechanical | 825581 |
Electrical | Original | / | 10/22/2015 | | RITA | Location = Electrical by RITA | | Electrical | 825063 |
Plan Coordinator | Original | / | 10/22/2015 | | JIMA | Location = Plan Coordinator by JIMA | | Plan Coordinator | 825061 |
Construction | Original | A | 10/22/2015 | JIMA | JIMA | | | Construction | 825060 |
Construction | Original | / | 10/22/2015 | JIMA | JIMA | In Current Review by JIMA | | Construction | 824940 |
Construction | Original | / | 10/22/2015 | | RITA | Location = Construction by RITA | | Construction | 824846 |
Plan Coordinator | Original | / | 10/22/2015 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 824824 |
Enumeration | Original | D | 10/22/2015 | BRENT | BRENT | I have included a diagram of the tenant spaces and addresses for this building from 2013. Please verify whether or not this is the current configuration of this building. Based on the addresses on this diagram, the address for this space is 719 N. Academy Blvd. Please show on the site plan the addresses the current tenants are using so that this space can be addressed consistently. Additionally, the tax schedule number and legal description are missing from the code study form and need to be included there. | | Enumeration | 824823 |
Enumeration | Original | / | 10/21/2015 | | NELIDA | Location = Enumeration by NELIDA | | Enumeration | 824691 |
Finished Bin | Original | / | 10/13/2015 | NELIDA | NELIDA | Pending plan review payment. Point of contact, Peter Brown has been notified via email. | | Finished Bin | 822535 |
Floodplain | Original | N | 10/13/2015 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 822534 |