Scanned/Finished Bin | Original | / | 5/17/2016 | | KENYATTA | Location = Scanned/Finished Bin by KENYATTA | | Scanned/Finished Bin | 873098 |
To Be Scanned Bin | Original | / | 5/16/2016 | | MINDY | Location = To Be Scanned Bin by MINDY | | To Be Scanned Bin | 871625 |
Plan Coordinator | Original | / | 5/16/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 871623 |
Construction | Original | A | 5/16/2016 | MICHAELA | MICHAELA | | | Construction | 871622 |
Construction | Original | / | 5/13/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 871464 |
Construction | Original | / | 5/13/2016 | | NELIDA | Location = Construction by NELIDA | | Construction | 871394 |
Resubmittal 3 | Original | / | 5/13/2016 | NELIDA | NELIDA | Resubmittal #3 5/13/16 | | Resubmittal 3 | 871393 |
CO Springs Fire | Original | A | 5/11/2016 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 870367 |
Fire | Original | / | 5/5/2016 | | RITA | Location = Fire by RITA | | Fire | 868829 |
Mechanical | Original | A | 5/5/2016 | DALEH | DALEH | | | Mechanical | 868815 |
Mechanical | Original | / | 5/4/2016 | | RITA | Location = Mechanical by RITA | | Mechanical | 868465 |
Plan Coordinator | Original | / | 5/4/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 868458 |
Construction | Original | D | 5/4/2016 | MICHAELA | MICHAELA | Show full code compliance at fire wall See plan Walk with Michael only | | Construction | 868457 |
Construction | Original | / | 4/29/2016 | | REBECCA | Location = Construction by REBECCA | | Construction | 867398 |
Resubmittal 2 | Original | / | 4/29/2016 | REBECCA | REBECCA | Resubmittal #2 | | Resubmittal 2 | 867397 |
Out to Review | Original | / | 4/7/2016 | REBECCA | REBECCA | lyonell 633-5901 | | Out to Review | 861555 |
Finished Bin | Original | / | 4/6/2016 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 860876 |
Mechanical | Original | D | 4/6/2016 | DALEH | DALEH | remove general notes that do not apply to the sheet they are on provide refrigerant calcs for crac units provide balance schedules for exhaust in individual rooms see plans for complete red lines return red lines no walk | | Mechanical | 860856 |
Mechanical | Original | / | 3/30/2016 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 859097 |
Mechanical | Original | / | 3/23/2016 | | RITA | Location = Mechanical by RITA | | Mechanical | 857506 |
Plan Coordinator | Original | / | 3/23/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 857461 |
Construction | Original | D | 3/23/2016 | MICHAELA | MICHAELA | Provide IECC certificate for envelope compliance Provide soils report No structural review - need stamped structural pages Show compliance with IBC 706.5.1 at fire wall Fire wall does not match U416 Clarify how vertical continuity is being met at fire wall - detail 28 on 1A8.6 is not compliant at the parapet No walk-through | | Construction | 857460 |
Construction | Original | / | 3/22/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 857202 |
Construction | Original | / | 3/22/2016 | | REBECCA | Location = Construction by REBECCA | | Construction | 856981 |
Resubmittal 1 | Original | / | 3/22/2016 | REBECCA | REBECCA | Resubmittal #1 | | Resubmittal 1 | 856980 |
Out to Review | Original | / | 2/22/2016 | JANE | JANE | holly 6335901 | | Out to Review | 849342 |
Finished Bin | Original | / | 2/17/2016 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 848527 |
Plan Coordinator | Original | / | 2/17/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 848524 |
Construction | Original | D | 2/17/2016 | MICHAELA | MICHAELA | REVIEW STOPPED - too many items umclear Preliminary review only See plan and make clarifications No walk-through | | Construction | 848517 |
Construction | Original | / | 2/17/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 848260 |
Construction | Original | / | 2/12/2016 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 847543 |
Plan Coordinator | Original | / | 2/12/2016 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 847538 |
Floodplain | Original | N | 2/12/2016 | BRENT | BRENT | | | Floodplain | 847537 |