Out to Review | Splice 4/11/17 | / | 4/13/2017 | GITA | GITA | michael took it | | Out to Review | 952003 |
Scanned/Finished Bin | Splice 4/11/17 | / | 4/13/2017 | | JLANE | Location = Scanned/Finished Bin by JLANE | | Scanned/Finished Bin | 951935 |
To Be Scanned Bin | Splice 4/11/17 | / | 4/12/2017 | | JLANE | Location = To Be Scanned Bin by JLANE | | To Be Scanned Bin | 951560 |
Plan Coordinator | Splice 4/11/17 | / | 4/12/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 951513 |
Mechanical | Splice 4/11/17 | A | 4/12/2017 | JUSTINC | JUSTINC | Revised layouts, Gas, snowmelt | | Mechanical | 951511 |
Mechanical | Splice 4/11/17 | / | 4/12/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 951456 |
Mechanical | Splice 4/11/17 | / | 4/11/2017 | | JESSICAM | Location = Mechanical by JESSICAM | | Mechanical | 951390 |
Plan Coordinator | Splice 4/11/17 | / | 4/11/2017 | | GITA | Location = Plan Coordinator by GITA | | Plan Coordinator | 951355 |
Electrical | Splice 4/11/17 | A | 4/11/2017 | BERTHA | BERTHA | | | Electrical | 951324 |
Plumbing | Splice 4/11/17 | A | 4/11/2017 | TCRIPPEN | TCRIPPEN | new splice pages | | Plumbing | 951251 |
Out to Review | Splice 4/11/17 | / | 4/11/2017 | GITA | GITA | | | Out to Review | 951195 |
Scanned/Finished Bin | Original | / | 9/6/2016 | | KENYATTA | Location = Scanned/Finished Bin by KENYATTA | | Scanned/Finished Bin | 901228 |
Health Dept. | Original | A | 9/2/2016 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Ankit Parikh 578-3278 | Aparikh | Health Dept. | 900802 |
CSU Contract Admin. | Original | A | 8/19/2016 | CSUAPPSPRM | CSUAPPSPRM | Utility charges/fees paid 8/19/16. BTE | Benglish | CSU Contract Admin. | 896805 |
Out to Review | Original | / | 8/10/2016 | RDCUSER | RDCUSER | out to applicant | | Out to Review | 894516 |
CO Springs DRE | Original | A | 8/10/2016 | RDCUSER | RDCUSER | DP amendment now approved. Okay to permit. RTL per MPF (see full review) | | CO Springs DRE | 894515 |
Elevators | Original | A | 8/10/2016 | ERIC | ERIC | Synergy 85S x 2 | | Elevators | 894454 |
Plumbing | Original | A | 8/5/2016 | DALEH | DALEH | | | Plumbing | 893564 |
Mechanical | Original | A | 8/5/2016 | JUSTINC | JUSTINC | Revised discharge height of EF grilles | | Mechanical | 893529 |
Construction | Original | A | 8/5/2016 | SHELLEY | SHELLEY | revised elevator details | | Construction | 893518 |
Out to Review | Original | / | 8/3/2016 | REBECCA | REBECCA | mike 719-216-7332 | | Out to Review | 892743 |
Finished Bin | Original | / | 8/2/2016 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 892280 |
Health Dept. | Original | D | 8/2/2016 | HEALTHDEPT | HEALTHDEPT | Health Department RFE plan review may be required. Please contact MYM 578-3140 for more information. | Michelle Martinez | Health Dept. | 892263 |
Health Dept. | Original | / | 7/29/2016 | | KENYATTA | Location = Health Dept. by KENYATTA | | Health Dept. | 891488 |
CO Springs DRE | Original | D | 7/29/2016 | RTEFERTILLER | RTEFERTILLER | delivered to Plan Coordinator (see full review) | | CO Springs DRE | 891478 |
CSU Contract Admin. | Original | / | 7/29/2016 | | RTEFERTILLER | Location = CSU Contract Admin. by RTEFERTILLER | | CSU Contract Admin. | 891474 |
CO Springs DRE | Original | D | 7/29/2016 | RTEFERTILLER | RTEFERTILLER | plans appear consistent with recently submitted development plan amendment. However, DP amendment is not yet approved. Please resubmit construction documents with approved development plan amendment. (see full review) | | CO Springs DRE | 891473 |
Zoning/Planning | Original | / | 7/27/2016 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 890675 |
Plan Coordinator | Original | / | 7/27/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 890637 |
Plumbing | Original | D | 7/27/2016 | TCRIPPEN | TCRIPPEN | See variance letter on P 502 you need 325 pound grease trap, and the 2- compartment sink , dishwasher and hand sink are to drain to the grease trap plan to reflect this, | | Plumbing | 890636 |
Plumbing | Original | / | 7/27/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 890577 |
Plumbing | Original | / | 7/26/2016 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 890396 |
Plan Coordinator | Original | / | 7/26/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 890392 |
Electrical | Original | A | 7/26/2016 | SHELBY | SHELBY | | | Electrical | 890391 |
Out to Review | Original | / | 7/26/2016 | NELIDA | NELIDA | Steven Peake 719-635-0900 | | Out to Review | 890370 |
Plumbing | Original | / | 7/26/2016 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 890217 |
Plan Coordinator | Original | / | 7/26/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 890214 |
Electrical | Original | D | 7/26/2016 | SHELBY | SHELBY | Please comply with previous review comments 8 and 9. | | Electrical | 890213 |
Electrical | Original | / | 7/26/2016 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 890188 |
Electrical | Original | / | 7/18/2016 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 888077 |
Elevators | Original | D | 7/18/2016 | ERIC | ERIC | Elevator submittals do not match plans Hoistway ventilation does not meet code requirements 2009 IBC 3004.3 Heat detectors required at top of hoistways 2013 ASME A17.1 2.27.3.2.1 | | Elevators | 888067 |
Plan Coordinator | Original | / | 7/18/2016 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 887952 |
Construction | Original | A | 7/18/2016 | DANM | DANM | | | Construction | 887951 |
Construction | Original | / | 7/14/2016 | DANM | DANM | In Current Review by DANM | | Construction | 887427 |
Construction | Original | / | 7/14/2016 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 887209 |
Plan Coordinator | Original | / | 7/14/2016 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 887192 |
Enumeration | Original | A | 7/14/2016 | AMY | AMY | | | Enumeration | 887191 |
Enumeration | Original | / | 7/14/2016 | AMY | AMY | In Current Review by AMY | | Enumeration | 887138 |
Enumeration | Original | / | 7/13/2016 | | JANE | Location = Enumeration by JANE | | Enumeration | 886889 |
Resubmittal 1 | Original | / | 7/13/2016 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 886888 |
Construction | 7/6/16- Foundation Only | A | 7/8/2016 | DANM | DANM | Minor foundation revisions | | Construction | 885795 |
Out to Review | 7/6/16- Foundation Only | / | 7/6/2016 | GITA | GITA | | | Out to Review | 885091 |
Out to Review | Original | / | 6/28/2016 | NELIDA | NELIDA | Michael Pattee 719-216-7332 | | Out to Review | 883272 |
Finished Bin | Original | / | 6/24/2016 | | RITA | Location = Finished Bin by RITA - LARGE BIN | | Finished Bin | 882399 |
Hazmat | Original | N | 6/23/2016 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 882138 |
CO Springs Fire | Original | A | 6/23/2016 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland T (see full review) | csfdit | CO Springs Fire | 882134 |
City Engr | Original | / | 6/22/2016 | | MINDY | Location = City Engr by MINDY | | City Engr | 881792 |
City Engr | Original | A | 6/21/2016 | CSENGINEER | CSENGINEER | Plan routed to RBD. pvm | csengineer | City Engr | 881626 |
CSU Contract Admin. | Original | D | 6/21/2016 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved for requested 3" water meter. Requires payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for information and assistance. Plans taken to City Engr. BTE | Benglish | CSU Contract Admin. | 881387 |
CSU Contract Admin. | Original | D | 6/20/2016 | CSUAPPSPRM | CSUAPPSPRM | Requires Paid Utility Reciept, Water meter sizing form submitted for review CQ | cquinn | CSU Contract Admin. | 881075 |
Gas/Elec. Utils | Original | A | 6/20/2016 | CSUREVIEW | CSUREVIEW | CQ | cquinn_ds | Gas/Elec. Utils | 881074 |
Waste Water Div | Original | A | 6/20/2016 | CSUREVIEW | CSUREVIEW | CQ | cquinn_ds | Waste Water Div | 881073 |
Water Division | Original | A | 6/20/2016 | CSUREVIEW | CSUREVIEW | CQ | cquinn_ds | Water Division | 881072 |
Fire | Original | / | 6/13/2016 | | RTEFERTILLER | Location = Fire by RTEFERTILLER | | Fire | 879129 |
CO Springs DRE | Original | D | 6/13/2016 | RTEFERTILLER | RTEFERTILLER | As discussed previously with applicant representatives, a minor amendment to the approved development plan and an approved final landscape plan are necessary before approving building permits for vertical construction. (see full review) | | CO Springs DRE | 879128 |
Zoning/Planning | Original | / | 6/8/2016 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 878457 |
Scanned/Finished Bin | Original | / | 6/8/2016 | | ERIC | Location = Scanned/Finished Bin by ERIC | | Scanned/Finished Bin | 878322 |
Plan Coordinator | Original | / | 6/8/2016 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 878317 |
Elevators | Original | D | 6/8/2016 | ERIC | ERIC | Need complete specifications for elevators being installed | | Elevators | 878316 |
Elevators | Original | / | 6/8/2016 | | RITA | Location = Elevators by RITA | | Elevators | 878160 |
Plan Coordinator | Original | / | 6/7/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 878063 |
Electrical | Original | D | 6/7/2016 | SHELBY | SHELBY | 1. Specify method of 240.87 NEC compliance. 2. Provide specification on Heat and Power Micro turbine detailing interaction between the micro turbine, utility power , and the "Micro turbine Dual Mode System controller". 3. Comply 702.4(B)(2) NEC. 4. Designate ATS's as service rated. 5. Remove all solar equipment from scope of work. 6. Show feeder over current device size on one line. 7. Show transformer GEC sizes on one line. 8. Comply 620.23 (A) and 620.24(A) NEC. 9. Supply side bonding jumper for XFMR KT incorrect. | | Electrical | 878061 |
Electrical | Original | / | 6/2/2016 | BRIAN | BRIAN | In Current Review by BRIAN | | Electrical | 876795 |
Electrical | Original | / | 6/1/2016 | | RITA | Location = Electrical by RITA | | Electrical | 876336 |
Plan Coordinator | Original | / | 6/1/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 876329 |
Plumbing | Original | D | 6/1/2016 | TCRIPPEN | TCRIPPEN | Plan 87969 Elevator sump pumps to floor sink or mop sink okay, 3 inch minimum drain required using 55 GPM, Inside Planters shall go to the sanitary waste not to the storm waste. Drinking fountains to be high – low type your occupant load of 2,209 requires 5- high – low types or 10 signal drinking fountains, Need letter from waste water for inside grease trap, Provide water pipe size analysis data on plan, ////// 7-6-16 okay for under cabinet vented,planters are outside not covered no plumbing reviewed required.TCC | | Plumbing | 876327 |
Plumbing | Original | / | 6/1/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 876231 |
Plumbing | Original | / | 5/27/2016 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 875543 |
Plan Coordinator | Original | / | 5/27/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 875535 |
Mechanical | Original | A | 5/27/2016 | JUSTINC | JUSTINC | | | Mechanical | 875533 |
Electrical | Original | / | 5/25/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electrical | 874910 |
Electrical | Original | / | 5/25/2016 | | RITA | Location = Electrical by RITA | | Electrical | 874898 |
Plan Coordinator | Original | / | 5/25/2016 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 874884 |
Construction | Original | D | 5/25/2016 | DANM | DANM | Code Study Form - Clarify why A-2 is considered a separate occupancy when it appears that it qualifies as an accessory use Life Safety Plan - Level 2 - Provide occupant load of terrace with no. of required exits - exit sign may be required for exiting back through the building Level 2 - Floor Plan - Provide Alternative Materials and Methods Application for smoke control in the atrium Sheet A225 - Provide Keynote Legend Sheet A351 - Clarify if Detail 2 should read Egress Stair #3 Sheet A352 - Clarify where the aluminum sunshades are detailed and how they are attached Sheet A411 - Missing, or providing conflicting, rated wall information on several details Sheet A413 - Provide listed assembly for required 1-hr rated exterior wall on detail 10 Sheet A417, A418 - Clarify elevator shaft partition type Sheet A426 - Provide Keynote Legend Sheet A561 - Reprint page with details shifted to the left so everything is on the page Sheet A594 - Provide listed assembly for concrete wall in detail 1 Provide listed assemblies for exterior bearing walls Sheet A653 - Clarify how steel beam in Detail 7 is rated per requirements of Type II-A Construction Provide listed assembly for concrete columns Provide listed assemblies for all flr/clg construction including concrete See Plans No walk-through review allowed | | Construction | 874883 |
Construction | Original | / | 5/17/2016 | DANM | DANM | In Current Review by DANM | | Construction | 872938 |
Construction | Original | / | 5/17/2016 | | AMY | Location = Construction by AMY | | Construction | 872937 |
Floodplain | Original | N | 5/17/2016 | AMY | AMY | | | Floodplain | 872936 |
Floodplain | Original | / | 5/17/2016 | | AMY | Location = Floodplain by AMY | | Floodplain | 872933 |
Enumeration | Original | D | 5/17/2016 | AMY | AMY | If the addressing is not to be replace or written back in on the end tabs-please cross out the 14 E Cache La Poudre Street addressing. | | Enumeration | 872932 |
Enumeration | Original | / | 5/17/2016 | AMY | AMY | In Current Review by AMY | | Enumeration | 872920 |
Enumeration | Original | / | 5/13/2016 | | REBECCA | Location = Enumeration by REBECCA - UPGRADE TO FINISH | | Enumeration | 871478 |
City Engr | Original | A | 5/13/2016 | PMORRIS | PMORRIS | Walk-thru at CAB Suite 401. Plan returned to the contractor. pvm | | City Engr | 871242 |
CO Springs Fire | Original | N | 5/13/2016 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 871214 |
Water Division | Original | A | 5/12/2016 | CSUREVIEW | CSUREVIEW | All comments addressed. | cquinn_ds | Water Division | 870801 |
Waste Water Div | Original | A | 5/12/2016 | CSUREVIEW | CSUREVIEW | All comments addressed. | cquinn_ds | Waste Water Div | 870800 |
Gas/Elec. Utils | Original | A | 5/12/2016 | CSUREVIEW | CSUREVIEW | All comments addressed. | cquinn_ds | Gas/Elec. Utils | 870799 |
Mechanical | Original | A | 5/10/2016 | DALEH | DALEH | Changing foundation only from N/A to an Approval so that a Mechanical contractor can attach for the purposes of this being a Geo Thermal system that requires a pressure test on the loops and manifold system located underground. The remaining system that will be installed and inspected under the upgrade to finish will require a certified test and balance contractor or an Engineers approval per the RBC code section 304.4.25 at time of heat final for the complete operating system. NOTE : No approved set of Mechanical drawings are scanned into the system for this approval due to the Mechanical attachment only being a pressure test. The approved Mechanic drawings will be submitted under the upgrade to finish. | | Mechanical | 870184 |
Out to Review | Original | / | 5/6/2016 | RTEFERTILLER | RTEFERTILLER | | | Out to Review | 869199 |
CO Springs DRE | Original | A | 5/6/2016 | RTEFERTILLER | RTEFERTILLER | Foundation only permit acceptable. Submittal of DP amendment and final landscape plan needed prior to issuing core/shell permits. (see full review) | | CO Springs DRE | 869198 |
Out to Review | Original | / | 5/6/2016 | DANM | DANM | | | Out to Review | 869180 |
Construction | Original | A | 5/6/2016 | DANM | DANM | | | Construction | 869179 |
Health Dept. | Original | A | 5/5/2016 | HEALTHDEPT | HEALTHDEPT | A Construction Activity Permit was pulled. T.O. 719-578-3286 | TaraOlson | Health Dept. | 868952 |
Elevators | Original | N | 5/3/2016 | ERIC | ERIC | Foundation only | | Elevators | 868308 |
Gas/Elec. Utils | Original | D | 5/2/2016 | CSUREVIEW | CSUREVIEW | Need to provide approved development plans per RBD checklist. (mjg, May 02, 2016) | mtroche | Gas/Elec. Utils | 867905 |
Water Division | Original | D | 5/2/2016 | CSUREVIEW | CSUREVIEW | Need to provide approved utility construction plans as per RBD checklist. (mjg, May 02, 2016) | mtroche | Water Division | 867902 |
Waste Water Div | Original | D | 5/2/2016 | CSUREVIEW | CSUREVIEW | Need to provide approved utility construction plans as per RBD checklist. (mjg, May 02, 2016) | mtroche | Waste Water Div | 867901 |
Hazmat | Original | N | 4/29/2016 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 867427 |
CO Springs Fire | Original | D | 4/29/2016 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland T (see full review) | csfdit | CO Springs Fire | 867419 |
Fire | Original | / | 4/27/2016 | | RTEFERTILLER | Location = Fire by RTEFERTILLER | | Fire | 866352 |
CO Springs DRE | Original | D | 4/27/2016 | RTEFERTILLER | RTEFERTILLER | Plans look largely okay and consistent with approved development plan (AR DP 15-00257) but the construction set must include a copy of the approved development plan. Additionally, the construction set appears to include a final landscape plan which hasn't been reviewed/approved by City Planning. Please provide confirmation that the City's landscape architect has reviewed and approved the project's final landscape plan and irrigation plan. (see full review) | | CO Springs DRE | 866351 |
Zoning/Planning | Original | / | 4/19/2016 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 864343 |
Plan Coordinator | Original | / | 4/19/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 864312 |
Plumbing | Original | N | 4/19/2016 | TCRIPPEN | TCRIPPEN | No plumbing work issue no permit. | | Plumbing | 864308 |
Plumbing | Original | / | 4/19/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 864302 |
Plumbing | Original | / | 4/18/2016 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 863944 |
Plan Coordinator | Original | / | 4/15/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 863910 |
Electrical | Original | A | 4/15/2016 | SHELBY | SHELBY | UNG only | | Electrical | 863909 |
Electrical | Original | / | 4/15/2016 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 863625 |
Mechanical | Original | N | 4/15/2016 | DALEH | DALEH | | | Mechanical | 863610 |
Mechanical | Original | / | 4/13/2016 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 862723 |
Mechanical | Original | / | 4/13/2016 | | RITA | Location = Mechanical by RITA | | Mechanical | 862722 |
Electrical | Original | / | 4/12/2016 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 862604 |
Plan Coordinator | Original | / | 4/12/2016 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 862585 |
Construction | Original | D | 4/12/2016 | DANM | DANM | Provide IECC Commercial Certificate for envelope compliance in order to indicate if there will be any slab or foundation insulation See plans Walk-through review OK | | Construction | 862584 |
Construction | Original | / | 4/12/2016 | DANM | DANM | In Current Review by DANM | | Construction | 862396 |
Construction | Original | / | 4/11/2016 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 862078 |
Plan Coordinator | Original | / | 4/11/2016 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 862076 |
Enumeration | Original | A | 4/11/2016 | BRENT | BRENT | Site plan on page C100. tax schedule number and address on code study form were incorrect. corrected. | | Enumeration | 862075 |
Enumeration | Original | / | 4/8/2016 | | JANE | Location = Enumeration by JANE | | Enumeration | 861917 |
Out to Review | Original | / | 3/31/2016 | JAY | JAY | to Rick Greene | | Out to Review | 859533 |
Construction | Original | / | 3/31/2016 | JAY | JAY | In Current Review by JAY | | Construction | 859415 |
Construction | Original | / | 3/31/2016 | | JAY | Location = Construction by JAY | | Construction | 859414 |
Electrical | Original | / | 3/29/2016 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 858894 |
Mechanical | Original | D | 3/29/2016 | JUSTINC | JUSTINC | Clarify callouts on plan ie... exhaust, return, supply, outside air. Verify ventilation to all mech rooms. Duct shown penetrating 2 hour shaft? how protecting? See plan for additional comments RETURN REDLINE COMMENTS WITH NEXT REVIEW NO WALK If you have any questions please call Justin C. @ 719-327-2899 | | Mechanical | 858882 |
Mechanical | Original | / | 3/28/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 858308 |
Mechanical | Original | / | 3/24/2016 | | RITA | Location = Mechanical by RITA | | Mechanical | 857773 |
Plan Coordinator | Original | / | 3/24/2016 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 857735 |
Construction | Original | D | 3/24/2016 | DANM | DANM | Missing significant information on fire ratings/listed assemblies for structural framing, floors and roofs - preliminary fire rating review only Occupant load questions Exterior stair and surrounding glass issues Redlines are too numerous to list out in detail See plans No walk-through review allowed | | Construction | 857734 |
Construction | Original | / | 3/17/2016 | DANM | DANM | In Current Review by DANM | | Construction | 855815 |
Construction | Original | / | 3/17/2016 | | RITA | Location = Construction by RITA | | Construction | 855793 |
Plan Coordinator | Original | / | 3/17/2016 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 855772 |
Enumeration | Original | D | 3/17/2016 | AMY | AMY | AFTER FURTHER REVIEW THE ADDRESS TO THE TUTT LIBRARY IS NOT 14 E CACHE LA POUDRE -SHOULD BE 1021 N CASCADE AVE- you can just cross out with a pen to edit each page. I see the trash enclosure is being removed. Is a new one going in? and what is the height? indicate page #. Include Tax Schedule number on the Code Study-incorrect. | | Enumeration | 855771 |
Enumeration | Original | / | 3/17/2016 | AMY | AMY | In Current Review by AMY | | Enumeration | 855710 |
Floodplain | Original | N | 3/15/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 855153 |