Scanned/Finished Bin | Original | / | 4/20/2016 | | RITA | Location = Scanned/Finished Bin by RITA | | Scanned/Finished Bin | 864559 |
To Be Scanned Bin | Original | / | 4/19/2016 | | KENYATTA | Location = To Be Scanned Bin by KENYATTA | | To Be Scanned Bin | 864494 |
Plan Coordinator | Original | / | 4/19/2016 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 864490 |
Enumeration | Original | A | 4/19/2016 | AMY | AMY | CODE STUDY FORM UP DATED. | | Enumeration | 864488 |
Plumbing | Original | A | 4/19/2016 | TCRIPPEN | TCRIPPEN | Small plumbing job allowed on M-pages this job only Inspector see M.00 and MA.102 | | Plumbing | 864360 |
Enumeration | Original | / | 4/18/2016 | | KENYATTA | Location = Enumeration by KENYATTA | | Enumeration | 864220 |
Plan Coordinator | Original | / | 4/18/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 864151 |
Plumbing | Original | D | 4/18/2016 | TCRIPPEN | TCRIPPEN | plumbing comments not addressed.per phone call plumbing on M-pages okay for this job only tcc 4-19-16 | | Plumbing | 864148 |
Plumbing | Original | / | 4/18/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 864126 |
Plumbing | Original | / | 4/18/2016 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 864028 |
Plan Coordinator | Original | / | 4/18/2016 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 864019 |
Electrical | Original | A | 4/18/2016 | BERTHA | BERTHA | | | Electrical | 864018 |
Electrical | Original | / | 4/15/2016 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 863652 |
Electrical | Original | / | 4/12/2016 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 862525 |
Plan Coordinator | Original | / | 4/12/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 862449 |
Mechanical | Original | A | 4/12/2016 | JUSTINC | JUSTINC | | | Mechanical | 862447 |
Mechanical | Original | / | 4/11/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 862202 |
Mechanical | Original | / | 4/7/2016 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 861505 |
Plan Coordinator | Original | / | 4/7/2016 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 861494 |
Construction | Original | A | 4/7/2016 | SHELLEY | SHELLEY | revised floor plan | | Construction | 861492 |
Construction | Original | / | 4/7/2016 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 861485 |
Construction | Original | / | 4/7/2016 | | NELIDA | Location = Construction by NELIDA | | Construction | 861450 |
Resubmittal 1 | Original | / | 4/7/2016 | NELIDA | NELIDA | Resubmittal #1 4/7/16 | | Resubmittal 1 | 861449 |
Out to Review | Original | / | 4/7/2016 | NELIDA | NELIDA | James 303-3096947 | | Out to Review | 861431 |
Finished Bin | Original | / | 4/6/2016 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 861215 |
Hazmat | Original | N | 4/1/2016 | CSFIRE | CSFIRE | | dwithee | Hazmat | 859951 |
CO Springs Fire | Original | A | 4/1/2016 | CSFIRE | CSFIRE | | csfdit | CO Springs Fire | 859950 |
Fire | Original | / | 3/29/2016 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 858923 |
CO Springs DRE | Original | N | 3/29/2016 | RDCUSER | RDCUSER | INTERIOR REMODEL ONLY, NO CHANGE OF USE (see full review) | | CO Springs DRE | 858922 |
Zoning/Planning | Original | / | 3/29/2016 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 858854 |
Plan Coordinator | Original | / | 3/29/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 858768 |
Electrical | Original | D | 3/29/2016 | SHELBY | SHELBY | 1. Label all new and relocated electrical devices/equipment with panel and circuit number. 2. Comply 422.51 NEC for vending . 3. Clearly identify all relocated lights. 4. GFCI devices may not be located above or behind appliances. 5. Alternates are not allowed ( see panel WPR1 notes). 6. Include panel schedules for all panels in this scope ( ECMRS etc). | | Electrical | 858767 |
Electrical | Original | / | 3/29/2016 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 858750 |
Electrical | Original | / | 3/24/2016 | | RITA | Location = Electrical by RITA | | Electrical | 857782 |
Plan Coordinator | Original | / | 3/24/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 857712 |
Plumbing | Original | D | 3/24/2016 | TCRIPPEN | TCRIPPEN | Per page AA.102 need to clarify sink and pump is the sink relocated or new is the pump used to remove the waste? sounds like a plumbing stamped page is required. | | Plumbing | 857711 |
Plumbing | Original | / | 3/24/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 857690 |
Plumbing | Original | / | 3/24/2016 | | RITA | Location = Plumbing by RITA | | Plumbing | 857689 |
Electrical | Original | / | 3/22/2016 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 856927 |
Plan Coordinator | Original | / | 3/22/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 856897 |
Mechanical | Original | D | 3/22/2016 | JUSTINC | JUSTINC | Provide ventilation schedule. Sheet MA.102 has plumbing iso inserted? Remove from (M) sheet and relocate to (P) sheet? Add note: Provide copy of test and balance report to mechanical inspector at time of heating final REST OK WALK OK | | Mechanical | 856896 |
Mechanical | Original | / | 3/21/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 856785 |
Mechanical | Original | / | 3/21/2016 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 856784 |
Plan Coordinator | Original | / | 3/21/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 856714 |
Plumbing | Original | N | 3/21/2016 | TCRIPPEN | TCRIPPEN | No plumbing work issue no permit, water and waste water removed not required. | | Plumbing | 856713 |
Plumbing | Original | / | 3/21/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 856696 |
Plumbing | Original | / | 3/18/2016 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 856498 |
Plan Coordinator | Original | / | 3/18/2016 | | JIMA | Location = Plan Coordinator by JIMA | | Plan Coordinator | 856490 |
Construction | Original | A | 3/18/2016 | JIMA | JIMA | | | Construction | 856489 |
Construction | Original | / | 3/18/2016 | JIMA | JIMA | In Current Review by JIMA | | Construction | 856372 |
Construction | Original | / | 3/18/2016 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 856342 |
Plan Coordinator | Original | / | 3/18/2016 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 856315 |
Enumeration | Original | D | 3/18/2016 | AMY | AMY | Legal Description & Tax Schedule number are required on the Code Study form.
See Key plan for area of work. | | Enumeration | 856314 |
Enumeration | Original | / | 3/18/2016 | AMY | AMY | In Current Review by AMY | | Enumeration | 856311 |
Floodplain | Original | N | 3/16/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 855207 |