Electrical | 12/6/16 | A | 12/6/2016 | BERTHA | BERTHA | Added 100A/3P disconnect. | | Electrical | 922237 |
Out to Review | 12/6/16 | / | 12/6/2016 | | GITA | Location = Out to Review by GITA | | Out to Review | 922213 |
Mechanical | 11/16/16 | A | 11/16/2016 | JUSTINC | JUSTINC | Revised to show radiation dampers in bathroom 305 | | Mechanical | 918173 |
Out to Review | 11/16/16 | / | 11/16/2016 | GITA | GITA | | | Out to Review | 918172 |
Construction | 11/9/16 | A | 11/9/2016 | DANM | DANM | Revise note regarding gyp in corridors | | Construction | 916749 |
Out to Review | 11/9/16 | / | 11/9/2016 | GITA | GITA | | | Out to Review | 916735 |
Electrical | 8/24/16 | A | 8/31/2016 | SHELBY | SHELBY | | | Electrical | 900126 |
Mechanical | 8/24/16 | A | 8/31/2016 | JUSTINC | JUSTINC | | | Mechanical | 900109 |
Plumbing | 8/24/16 | A | 8/31/2016 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 900092 |
Plumbing | 8/24/16 | D | 8/31/2016 | TCRIPPEN | TCRIPPEN | missing sizes | | Plumbing | 899976 |
Plumbing | 8/24/16 | A | 8/29/2016 | TCRIPPEN | TCRIPPEN | new splice page relocated sink in same room. | | Plumbing | 899085 |
Construction | 8/24/16 | A | 8/29/2016 | MICHAELA | MICHAELA | Revise floor plan | | Construction | 899068 |
Out to Review | 8/24/16 | / | 8/24/2016 | GITA | GITA | | | Out to Review | 897828 |
Scanned/Finished Bin | Original | / | 5/26/2016 | | RITA | Location = Scanned/Finished Bin by RITA | | Scanned/Finished Bin | 875391 |
To Be Scanned Bin | Original | / | 5/26/2016 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 875315 |
CO Springs Fire | Original | A | 5/25/2016 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland T (see full review) | csfdit | CO Springs Fire | 874839 |
CO Springs Fire | Original | D | 5/24/2016 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland T (see full review) | csfdit | CO Springs Fire | 874645 |
Mechanical | Original | A | 5/19/2016 | JUSTINC | JUSTINC | | | Mechanical | 873634 |
Electrical | Original | A | 5/19/2016 | BERTHA | BERTHA | | | Electrical | 873620 |
Construction | Original | A | 5/19/2016 | MICHAELA | MICHAELA | | | Construction | 873597 |
Enumeration | Original | A | 5/19/2016 | AMY | AMY | Everything corrected.. There is a door running from suite 300 to 352 they are 2 different business. They are associated with one another but are separate tenants. | | Enumeration | 873590 |
Plumbing | Original | A | 5/19/2016 | TCRIPPEN | TCRIPPEN | okay, | | Plumbing | 873571 |
Out to Review | Original | / | 4/27/2016 | REBECCA | REBECCA | GENT-denver/boulder courier 303-938-6887 | | Out to Review | 866487 |
Finished Bin | Original | / | 4/27/2016 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 866369 |
Hazmat | Original | N | 4/25/2016 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 866006 |
CO Springs Fire | Original | D | 4/25/2016 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 866004 |
Fire | Original | / | 4/13/2016 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 863119 |
CO Springs DRE | Original | N | 4/13/2016 | RDCUSER | RDCUSER | Interior Finish (see full review) | | CO Springs DRE | 863118 |
Zoning/Planning | Original | / | 4/13/2016 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 863064 |
Plan Coordinator | Original | / | 4/13/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 862957 |
Electrical | Original | D | 4/13/2016 | SHELBY | SHELBY | 1 Provide panel schedule for p[panel EM. 2. Provide HP 3 panel schedule. 3. Provide load calculation for the building service. 4. Supply side bonding jumper for transformer secondary is sized incorrectly. 5. Label panel L3D correctly on floor plan. 6. Provide emergency lighting in treatment rooms. 7. Clearly identify new VS existing on one line. 8. Comply 517.18 NEC for post op bed locations ( use EM for critical). 9. Comply 517.19(C) NEC for operating room ( use EM for critical). | | Electrical | 862956 |
Electrical | Original | / | 4/13/2016 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 862851 |
Electrical | Original | / | 4/4/2016 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 860050 |
Plan Coordinator | Original | / | 4/4/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 860038 |
Plumbing | Original | D | 4/4/2016 | TCRIPPEN | TCRIPPEN | All hand washing sinks to be 110 degrees max with mixing valve(s), Water hammer devices to be used when required, see construction notes for bath room accessibly. water and waste water removed not required | | Plumbing | 860037 |
Plumbing | Original | / | 4/4/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 860017 |
Plumbing | Original | / | 3/31/2016 | | RITA | Location = Plumbing by RITA | | Plumbing | 859607 |
Plan Coordinator | Original | / | 3/31/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 859604 |
Mechanical | Original | D | 3/31/2016 | JUSTINC | JUSTINC | Toilet room #305 does not indicate any exhaust? Indicate how providing ventilation per 09' IMC 403.3 (Public Spaces) - (Toilet Rooms-Public). See plan for additional notes RETURN REDLINE COMMENTS WITH NEXT REVIEW WALK OK | | Mechanical | 859603 |
Mechanical | Original | / | 3/31/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 859538 |
Mechanical | Original | / | 3/30/2016 | | RITA | Location = Mechanical by RITA | | Mechanical | 859283 |
Plan Coordinator | Original | / | 3/30/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 859209 |
Construction | Original | D | 3/30/2016 | MICHAELA | MICHAELA | New toilet room not ANSI compliant Bench required in locker room Walk-through OK | | Construction | 859010 |
Construction | Original | / | 3/29/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 858913 |
Construction | Original | / | 3/25/2016 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 857933 |
Plan Coordinator | Original | / | 3/24/2016 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 857879 |
Floodplain | Original | N | 3/24/2016 | AMY | AMY | | | Floodplain | 857878 |
Enumeration | Original | D | 3/24/2016 | AMY | AMY | Plan was checked in under 2 different addresses. Contacted Brian Long-Architect to clarify the correct address-6071 E Woodmen Road. correct all page to reflect the correct address. The location map is incorrect for the location of the 6071 E Woodmen Road-please replace. The Code Study form is incomplete-Tax Schedule number & Legal Description are required on this form. A plan for the 3rd floor has not been submitted since 2011, please show the entire floor to include separation of space per tenants with all suite numbers to date. Permit history for Pikes Peak Urology is currently under suite 300. Have they moved? | | Enumeration | 857868 |