Mechanical | 8/8/17 | D | 8/15/2017 | DALEH | DALEH | after conversation with field inspector Jon B. it appears this splice is incomplete ..please converse with Jon and resubmit proper splice with complete changes to scope of work. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 986832 |
Mechanical | 8/8/17 | / | 8/10/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 985469 |
Mechanical | 8/8/17 | / | 8/10/2017 | | JANE | Location = Mechanical by JANE | | Mechanical | 985374 |
Construction | 1/3/17 | A | 1/3/2017 | SHELLEY | SHELLEY | AMM application to State for daylighting. | | Construction | 927655 |
Scanned/Finished Bin | Original | / | 8/18/2016 | | RITA | Location = Scanned/Finished Bin by RITA. LARGE PLAN BIN. | | Scanned/Finished Bin | 896504 |
To Be Scanned Bin | Original | / | 8/18/2016 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 896259 |
County Fire | Original | A | 8/18/2016 | RITA | RITA | PER RTP 08/08/16 | | County Fire | 896258 |
Hazmat | Original | A | 8/17/2016 | CSFIRE | CSFIRE | Read attached comments and ensure items addressed prior to inspection. Placed in finished bin. | smitty91 | Hazmat | 896142 |
Hazmat | Original | D | 8/12/2016 | CSFIRE | CSFIRE | Read attached comments, address and resubmit. Placed in finished bin. | smitty91 | Hazmat | 895085 |
Hazmat | Original | / | 8/12/2016 | | CSFIRE | Location = Hazmat by CSFIRE | smitty91 | Hazmat | 895076 |
Health Dept. | Original | A | 8/11/2016 | HEALTHDEPT | HEALTHDEPT | Pre-operational inspection will be required before final approval for opening is granted. Gustavo 578-3295 | galvarez | Health Dept. | 894720 |
Enumeration | Original | A | 7/27/2016 | BRENT | BRENT | | | Enumeration | 890851 |
Out to Review | Original | / | 7/27/2016 | MINDY | MINDY | Todd 473 8446 | | Out to Review | 890829 |
Finished Bin | Original | / | 7/26/2016 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 890192 |
Health Dept. | Original | D | 7/25/2016 | HEALTHDEPT | HEALTHDEPT | 1. Plan review required. 2. Air quality construction activity permit required. 3. Contact Health Department for septic system and well water requirements. Please contact the health department at (719) 578-3199 option 3 for more information. AParikh (719) 578-3278 | Aparikh | Health Dept. | 890091 |
Health Dept. | Original | / | 7/22/2016 | | KENYATTA | Location = Health Dept. by KENYATTA | | Health Dept. | 889524 |
Mechanical | Original | A | 7/15/2016 | DALEH | DALEH | | | Mechanical | 887807 |
Out to Review | Original | / | 7/14/2016 | JANE | JANE | Todd 473 8446 | | Out to Review | 887377 |
Health Dept. | Original | / | 7/14/2016 | | KENYATTA | Location = Health Dept. by KENYATTA | | Health Dept. | 887262 |
Plan Coordinator | Original | / | 7/14/2016 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 887246 |
Mechanical | Original | D | 7/14/2016 | DALEH | DALEH | all refrigerant calc's must be on drawings not just response letter exhaust fans in prep and science labs must be interlocked with VAV'S or show other means of how balance will be maintained smoke damper required in storage 279 return all green lines walk ok | | Mechanical | 887239 |
Image Server | Original | / | 7/14/2016 | | KENYATTA | Location = Image Server by KENYATTA | | Image Server | 887151 |
Plan Coordinator | Original | / | 7/14/2016 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 887148 |
Elevators | Original | A | 7/14/2016 | ERIC | ERIC | Machine room less hydraulic elevator. Must be registered with the State prior to final | | Elevators | 887147 |
Elevators | Original | / | 7/13/2016 | | KENYATTA | Location = Elevators by KENYATTA | | Elevators | 887038 |
Mechanical | Original | / | 7/13/2016 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 887037 |
Plan Coordinator | Original | / | 7/13/2016 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 887008 |
Resubmittal 1 | Original | / | 7/13/2016 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 887007 |
Construction | Original | A | 7/13/2016 | SHELLEY | SHELLEY | | | Construction | 887003 |
Out to Review | Original | / | 6/29/2016 | REBECCA | REBECCA | todd 473-8446 | | Out to Review | 883758 |
Finished Bin | Original | / | 6/28/2016 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 883422 |
Mechanical | Original | D | 6/28/2016 | DALEH | DALEH | provide kitchen balance schedule is dishwasher above counter ? type 2 hood ? provide refrigerant calcs elevator equipment room ? see plans for complete red lines return red lines NO walk | | Mechanical | 883409 |
Mechanical | Original | / | 6/23/2016 | | RITA | Location = Mechanical by RITA | | Mechanical | 882149 |
Plan Coordinator | Original | / | 6/23/2016 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 882115 |
Construction | Original | D | 6/23/2016 | SHELLEY | SHELLEY | Provide wall type and listed assembly for fire walls; FRT plywood is required in IIB construction; Legend reference for 1-hour on TS2.1 incorrect; note separate permit and submittal required for pump house; clarify where elevator equipment room is; Verify 1-hour at existing walls and provide equivalent assembly for new corridor and at infill in Area D (1922 bldg) see A2.4; provide proof of compliance with IECC C402.4.2 at gym; clarify fall protection for all roof equipment and hatches that are <10' from edge of roof; Clearance at restrooms 240, 239, 224, and 223 not compliant for 180 degree turn; see plans. Walk ok WITH SHELLEY ONLY. | | Construction | 882114 |
Construction | Original | / | 6/22/2016 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 881754 |
Construction | Original | / | 6/15/2016 | | RITA | Location = Construction by RITA | | Construction | 880213 |
Plan Coordinator | Original | / | 6/15/2016 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 880178 |
Floodplain | Original | N | 6/15/2016 | BRENT | BRENT | | | Floodplain | 880177 |