Electrical | Original | A | 11/4/2016 | BERTHA | BERTHA | | | Electrical | 915797 |
Mechanical | Original | A | 11/4/2016 | DALEH | DALEH | | | Mechanical | 915794 |
Mechanical | Original | D | 9/20/2016 | DALEH | DALEH | all ok pending structural engineers letter | | Mechanical | 904513 |
Plumbing | Original | A | 9/20/2016 | TCRIPPEN | TCRIPPEN | okay, | | Plumbing | 904511 |
Out to Review | Original | / | 9/7/2016 | MINDY | MINDY | Jesse 719 502 1431 | | Out to Review | 901658 |
Finished Bin | Original | / | 8/18/2016 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 896271 |
Hazmat | Original | N | 8/11/2016 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 894672 |
CO Springs Fire | Original | A | 8/11/2016 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 894669 |
CO Springs DRE | Original | N | 8/9/2016 | CFAHEY | CFAHEY | Interior remodel only, no significant change of use. (see full review) | | CO Springs DRE | 894089 |
Fire | Original | / | 8/9/2016 | | CFAHEY | Location = Fire by CFAHEY | | Fire | 894088 |
Zoning/Planning | Original | / | 8/5/2016 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 893347 |
Plan Coordinator | Original | / | 8/4/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 893328 |
Electrical | Original | D | 8/4/2016 | SHELBY | SHELBY | 1. Corroborate verification of note on one line stipulating that all existing work has been permitted. 2. Switchboard feeding HV1 is overloaded. 3. GEC for transformer is incorrect. 4. Transformer is incorrect on floor plan. | | Electrical | 893327 |
Electrical | Original | / | 8/4/2016 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 893190 |
Electrical | Original | / | 8/2/2016 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 892338 |
Plan Coordinator | Original | / | 8/2/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 892325 |
Plumbing | Original | D | 8/2/2016 | TCRIPPEN | TCRIPPEN | Hot water source to be within 50` without a pump. water and waste water removed not required, | | Plumbing | 892324 |
Plumbing | Original | / | 8/2/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 892318 |
Plumbing | Original | / | 8/1/2016 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 891875 |
Plan Coordinator | Original | / | 8/1/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 891833 |
Mechanical | Original | D | 8/1/2016 | JUSTINC | JUSTINC | Provide stamped letter or sheet from structural engineer for rooftop equip. over 300#'s Provide typ. detail or show on gas floor plan (gas shutoff valves, regulators, dirt leg, ect..) (2) sheets shown as M1?
SEE PLAN FOR ANY ADDITIONAL COMMENTS RETURN RED LINE COMMENT SHEETS WITH NEXT REVIEW WALK OK | | Mechanical | 891832 |
Mechanical | Original | / | 8/1/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 891805 |
Mechanical | Original | / | 8/1/2016 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 891795 |
Plan Coordinator | Original | / | 8/1/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 891759 |
Construction | Original | A | 8/1/2016 | MICHAELA | MICHAELA | | | Construction | 891758 |
Construction | Original | / | 7/29/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 891527 |
Construction | Original | / | 7/27/2016 | | RITA | Location = Construction by RITA | | Construction | 890666 |
Plan Coordinator | Original | / | 7/27/2016 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 890620 |
Enumeration | Original | A | 7/27/2016 | AMY | AMY | PERMIT I76402 WAS NEVER COMPLETED FOR AN INTERIOR REMODEL IN 2013 | | Enumeration | 890619 |
Enumeration | Original | / | 7/27/2016 | AMY | AMY | In Current Review by AMY | | Enumeration | 890617 |
Enumeration | Original | / | 7/26/2016 | | BPHILLIPS | Location = Enumeration by BPHILLIPS | | Enumeration | 890457 |
Out to Review | Original | / | 7/26/2016 | REBECCA | REBECCA | walking | | Out to Review | 890441 |
Floodplain | Original | N | 7/26/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 890439 |