Electrical | Original | A | 10/27/2016 | SHELBY | SHELBY | | | Electrical | 913601 |
Resubmittal 2 | Original | / | 10/25/2016 | GITA | GITA | Resubmittal #2 | | Resubmittal 2 | 913126 |
Electrical | Original | D | 10/4/2016 | BERTHA | BERTHA | 1. Provide complete one line to include conduit/wire size, type and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work. 2. Verify panel capacity prior to plan submittal - note 16.470 and 16.471 sheet EMC1. | | Electrical | 907830 |
Resubmittal 1 | Original | / | 10/3/2016 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 907745 |
Hazmat | Original | N | 9/19/2016 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 904071 |
CO Springs Fire | Original | N | 9/19/2016 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L | csfdit | CO Springs Fire | 904070 |
CO Springs DRE | Original | N | 9/15/2016 | MBINGMAN | MBINGMAN | Interior Remodel Only. No change of use. (see full review) | | CO Springs DRE | 903601 |
Plumbing | Original | N | 9/15/2016 | TCRIPPEN | TCRIPPEN | No plumbing work issue no permit, water and waste water removed not required | | Plumbing | 903586 |
Electronic Plan | Original | / | 9/15/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 903579 |
Electrical | Original | D | 9/14/2016 | SHELBY | SHELBY | 1. Provide complete one line. 2. Verify panel capacity prior to plan submittal ( note 16.470 sheet EMC1 ). 3. Include required information on UPS circuits ( see note 16.W06 sheet EMC1). 4. See http://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202015a.pdf for requirements. | | Electrical | 903262 |
Mechanical | Original | A | 9/14/2016 | JUSTINC | JUSTINC | | | Mechanical | 903101 |
Zoning/Planning | Original | / | 9/13/2016 | MBINGMAN | MBINGMAN | In Current Review by MBINGMAN | | Zoning/Planning | 902996 |
Construction | Original | A | 9/13/2016 | MICHAELA | MICHAELA | | | Construction | 902932 |
Electronic Plan | Original | / | 9/13/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 902927 |
Enumeration | Original | A | 9/12/2016 | BRENT | BRENT | | | Enumeration | 902558 |
Floodplain | Original | N | 9/12/2016 | BRENT | BRENT | floodplain on parcel, not near structure | | Floodplain | 902557 |