Scanned/Finished Bin | Original | / | 4/19/2017 | | JLANE | Location = Scanned/Finished Bin by JLANE | | Scanned/Finished Bin | 953620 |
To Be Scanned Bin | Original | / | 4/19/2017 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 953467 |
Hazmat | Original | A | 4/19/2017 | RITA | RITA | per MAS 04/19/17 | | Hazmat | 953465 |
Fountain Fire | Original | A | 4/19/2017 | FNTNFIRE | FNTNFIRE | HAZ-MAT OK Fountain FD MAS | mstanwood | Fountain Fire | 953396 |
Fountain Water | Original | A | 4/18/2017 | NELIDA | NELIDA | see label | | Fountain Water | 953252 |
Fountain Waste Water | Original | A | 4/18/2017 | NELIDA | NELIDA | see label | | Fountain Waste Water | 953250 |
Fountain Zoning | Original | A | 4/18/2017 | NELIDA | NELIDA | see label | | Fountain Zoning | 953249 |
Health Dept. | Original | A | 2/1/2017 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Rebecca Nielsen 575-8965 | rnielsen | Health Dept. | 933642 |
Fountain Fire | Original | A | 1/25/2017 | FNTNFIRE | FNTNFIRE | Fountain Fire department OK MAS 2 horn strobes and one pull station required to be added to the existing fire alarm system | mstanwood | Fountain Fire | 932184 |
Out to Review | Original | / | 1/23/2017 | NELIDA | NELIDA | Alex 303-886-6219 | | Out to Review | 931731 |
Finished Bin | Original | / | 1/10/2017 | | JESSICAM | Location = Finished Bin by JESSICAM | | Finished Bin | 929093 |
Plan Coordinator | Original | / | 1/10/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 929070 |
Plumbing | Original | A | 1/10/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 929069 |
Plumbing | Original | / | 1/10/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 929060 |
Plumbing | Original | / | 1/9/2017 | | JESSICAM | Location = Plumbing by JESSICAM | | Plumbing | 928934 |
Plan Coordinator | Original | / | 1/9/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 928918 |
Mechanical | Original | A | 1/9/2017 | JUSTINC | JUSTINC | | | Mechanical | 928917 |
Mechanical | Original | / | 1/9/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 928864 |
Mechanical | Original | / | 1/9/2017 | | JESSICAM | Location = Mechanical by JESSICAM | | Mechanical | 928826 |
Plan Coordinator | Original | / | 1/9/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 928798 |
Electrical | Original | A | 1/9/2017 | SHELBY | SHELBY | | | Electrical | 928797 |
Electrical | Original | / | 1/9/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 928756 |
Electrical | Original | / | 1/6/2017 | | NELIDA | Location = Electrical by NELIDA | | Electrical | 928577 |
Resubmittal 3 | Original | / | 1/6/2017 | NELIDA | NELIDA | Resubmittal #3 1/6/17 | | Resubmittal 3 | 928576 |
Enumeration | Original | A | 1/6/2017 | AMY | AMY | 130 | | Enumeration | 928568 |
Out to Review | Original | / | 1/6/2017 | MINDY | MINDY | Alex 303 886 6219 | | Out to Review | 928558 |
Finished Bin | Original | / | 12/28/2016 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 926752 |
Plan Coordinator | Original | / | 12/28/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 926739 |
Plumbing | Original | D | 12/28/2016 | TCRIPPEN | TCRIPPEN | Still need water pipe size analysis data on plans, see chapter 4 of the 2012 IPC table 403.1 note D The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required. So your occupant load of 185 will require 2-men`s and 2 women`s toilets, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 926736 |
Plumbing | Original | / | 12/28/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 926698 |
Plumbing | Original | / | 12/23/2016 | | JESSICAM | Location = Plumbing by JESSICAM | | Plumbing | 926308 |
Plan Coordinator | Original | / | 12/23/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 926298 |
Electrical | Original | D | 12/23/2016 | SHELBY | SHELBY | See comments BA 12/20/16 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 926297 |
Electrical | Original | / | 12/23/2016 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 926276 |
Electrical | Original | / | 12/20/2016 | | JESSICAM | Location = Electrical by JESSICAM | | Electrical | 925330 |
Plan Coordinator | Original | / | 12/20/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 925297 |
Mechanical | Original | D | 12/20/2016 | JUSTINC | JUSTINC | See plan for example of air balance schedule and interlock schedule as discussed with mech. engineer on 12/20/2016
WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 925296 |
Mechanical | Original | / | 12/20/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 925238 |
Resubmittal 2 | Original | / | 12/20/2016 | MINDY | MINDY | Resubmittal #2 | | Resubmittal 2 | 925216 |
Mechanical | Original | / | 12/20/2016 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 925215 |
Plan Coordinator | Original | / | 12/20/2016 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 925173 |
Electrical | Original | D | 12/20/2016 | BERTHA | BERTHA | 1. Provide complete one-line to include conduit/wire size, type and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work.
2. AIC and fault current calculations for all service equipment and sub panels in the scope of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 925172 |
Electrical | Original | / | 12/16/2016 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 924795 |
Electrical | Original | / | 12/13/2016 | | JESSICAM | Location = Electrical by JESSICAM | | Electrical | 923636 |
Plan Coordinator | Original | / | 12/13/2016 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 923626 |
Construction | Original | A | 12/13/2016 | SHELLEY | SHELLEY | | | Construction | 923625 |
Construction | Original | / | 12/13/2016 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 923620 |
Construction | Original | / | 12/12/2016 | | JESSICAM | Location = Construction by JESSICAM | | Construction | 923588 |
Plan Coordinator | Original | / | 12/12/2016 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 923536 |
Enumeration | Original | D | 12/12/2016 | AMY | AMY | SEE NOTES 9-14-16 NOT COMPLETED. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 923535 |
Enumeration | Original | / | 12/12/2016 | | NELIDA | Location = Enumeration by NELIDA | | Enumeration | 923376 |
Resubmittal 1 | Original | / | 12/12/2016 | NELIDA | NELIDA | Resubmittal #1 12/12/16 | | Resubmittal 1 | 923375 |
Out to Review | Original | / | 10/26/2016 | MINDY | MINDY | with contractor | | Out to Review | 913309 |
Finished Bin | Original | / | 10/5/2016 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 908381 |
Plan Coordinator | Original | / | 10/5/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 908319 |
Electrical | Original | D | 10/5/2016 | SHELBY | SHELBY | 1. Provide complete one line. See http://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202015a.pdf 2. Provide SCA and AIR at and of all panels and electrical gear in this scope. | | Electrical | 908318 |
- Not Set - | Original | / | 10/5/2016 | SHELBY | SHELBY | In Current Review by SHELBY | | - Not Set - | 908296 |
- Not Set - | Original | / | 10/4/2016 | | TCRIPPEN | Location = - Not Set - by TCRIPPEN | | - Not Set - | 908049 |
Plumbing | Original | D | 10/4/2016 | TCRIPPEN | TCRIPPEN | Your occupant load of 185 will require 2-men`s and 2-women`s fixtures, all gas pipe and related items to be on the M-pages, provide water pipe size analysis data on plans | | Plumbing | 908048 |
Plumbing | Original | / | 10/4/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 908029 |
Plumbing | Original | / | 10/4/2016 | | REBECCA | Location = Plumbing by REBECCA | | Plumbing | 908028 |
Electrical | Original | / | 10/4/2016 | | REBECCA | Location = Electrical by REBECCA | | Electrical | 908019 |
Plan Coordinator | Original | / | 10/4/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 908011 |
Mechanical | Original | D | 10/4/2016 | JUSTINC | JUSTINC | Provide interlock schedules as called out in plans Provide refrig. calculations per 09 IMC 1103.1 Provide typ. gas connection detail
RETURN RED LINE COMMENT SHEETS SEE PLAN PAGES FOR ALL ADDITIONAL COMMENTS NO WALK REVIEW INCOMPLETE | | Mechanical | 908005 |
Mechanical | Original | / | 10/4/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 907972 |
Mechanical | Original | / | 10/4/2016 | | REBECCA | Location = Mechanical by REBECCA | | Mechanical | 907971 |
Electrical | Original | / | 9/15/2016 | | RITA | Location = Electrical by RITA | | Electrical | 903396 |
Plan Coordinator | Original | / | 9/15/2016 | | JIMA | Location = Plan Coordinator by JIMA | | Plan Coordinator | 903380 |
Construction | Original | D | 9/15/2016 | JIMA | JIMA | see plan / walk ok occupant load under building code information needs to match page A002 / move exit at front door / | | Construction | 903378 |
Construction | Original | / | 9/14/2016 | JIMA | JIMA | In Current Review by JIMA | | Construction | 903247 |
Construction | Original | / | 9/14/2016 | | RITA | Location = Construction by RITA | | Construction | 903204 |
Plan Coordinator | Original | / | 9/14/2016 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 903151 |
Enumeration | Original | D | 9/14/2016 | BRENT | BRENT | Based on the site plan, it appears that this tenant will be occupy suites 130 & 140, NOT suite 120. Verify suite number for this tenant. Correct plan pages to show correct suite numbering and show suite numbering for all tenant spaces in this building. Contact Enumerations for help as needed. The building location shown on the vicinity map is incorrect. | | Enumeration | 903150 |
Floodplain | Original | N | 9/13/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 902892 |