Electrical | 2/16/2017 | A | 2/16/2017 | SHELBY | SHELBY | | | Electrical | 937408 |
Out to Review | 2/16/2017 | / | 2/16/2017 | GITA | GITA | | | Out to Review | 937393 |
Finished Bin | Original | / | 11/28/2016 | | JESSICAM | Location = Finished Bin by JESSICAM | | Finished Bin | 920400 |
Health Dept. | Original | A | 11/23/2016 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A Pre-operational inspection will be required before final approval for opening is granted. AB 352-1842 | abrannon | Health Dept. | 920181 |
Fountain Water | Original | A | 11/22/2016 | MINDY | MINDY | 11/07/2016 | | Fountain Water | 919973 |
Fountain Waste Water | Original | A | 11/22/2016 | MINDY | MINDY | 11/08/2016 J | | Fountain Waste Water | 919972 |
Fountain Zoning | Original | A | 11/22/2016 | MINDY | MINDY | 12/09/2016 AGS | | Fountain Zoning | 919971 |
Mechanical | Original | A | 11/22/2016 | JUSTINC | JUSTINC | | | Mechanical | 919964 |
Plumbing | Original | A | 11/22/2016 | TCRIPPEN | TCRIPPEN | okay, | | Plumbing | 919941 |
Enumeration | Original | A | 11/21/2016 | AMY | AMY | see site plan attached with all addressing. | | Enumeration | 919512 |
Fountain Fire | Original | A | 11/7/2016 | FNTNFIRE | FNTNFIRE | 2 fire alarm horn strobes required to be connected to existing system, 1 in Kitchen & 1 in dining room area. One FA Pull Station required. Hood suppression system permit required from Fountain FD required to be connected to the Fire Alarm. Fountain FD requires the size of the CO2 Tank an alarm may be required. | mstanwood | Fountain Fire | 916296 |
Out to Review | Original | / | 11/7/2016 | NELIDA | NELIDA | Jack 719-232-8760 | | Out to Review | 916042 |
Finished Bin | Original | / | 11/4/2016 | | JESSICAM | Location = Finished Bin by JESSICAM | | Finished Bin | 915992 |
Health Dept. | Original | D | 11/4/2016 | HEALTHDEPT | HEALTHDEPT | Health Department plan review required prior to approval. AB 352-1842 | abrannon | Health Dept. | 915960 |
Health Dept. | Original | / | 11/2/2016 | | RITA | Location = Health Dept. by RITA | | Health Dept. | 915036 |
Plan Coordinator | Original | / | 11/2/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 915029 |
Plumbing | Original | D | 11/2/2016 | TCRIPPEN | TCRIPPEN | Your coffee service area is to be on the grease waste line, Bar area okay, see red line for mop sink faucet being use for chemical dispensing. need floor sink for dishwasher need to add hand sink (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 915028 |
Plumbing | Original | / | 11/2/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 914934 |
Plumbing | Original | / | 10/20/2016 | | RITA | Location = Plumbing by RITA | | Plumbing | 912266 |
Plan Coordinator | Original | / | 10/20/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 912187 |
Mechanical | Original | D | 10/20/2016 | JUSTINC | JUSTINC | New MAU-1 indicated with weight over 300#'s. Provide stamped letter or sheet from structural engineer. Coordinate with kitchen supplier to define walk-in cooler/freezer calculations. Indicate volume of refrig. and if within allowable limits per 09' IMC 1103.1 Indicate how protecting if over allowable limit. OR provide sensors and alarms. CO2 tank indicated. Indicate size of tank and within allowable limits per CSFD. If over allowable limits indicate how protecting. Ventilation table not showing kitchen or supply room?
RETURN RED LINE COMMENT SHEETS WITH NEXT REVIEW WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 912184 |
Mechanical | Original | / | 10/20/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 912148 |
Mechanical | Original | / | 10/20/2016 | | RITA | Location = Mechanical by RITA | | Mechanical | 912093 |
Plan Coordinator | Original | / | 10/19/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 912047 |
Electrical | Original | A | 10/19/2016 | SHELBY | SHELBY | | | Electrical | 912046 |
Electrical | Original | / | 10/18/2016 | | JESSICAM | Location = Electrical by JESSICAM | | Electrical | 911646 |
Plan Coordinator | Original | / | 10/18/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 911630 |
Construction | Original | A | 10/18/2016 | MICHAELA | MICHAELA | | | Construction | 911629 |
Construction | Original | / | 10/18/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 911584 |
Construction | Original | / | 10/17/2016 | | JESSICAM | Location = Construction by JESSICAM | | Construction | 911109 |
Plan Coordinator | Original | / | 10/17/2016 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 911101 |
Enumeration | Original | D | 10/17/2016 | AMY | AMY | included a floor plan showing separation of space per tenant with all addressing labeled to date. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 911100 |
Floodplain | Original | N | 10/14/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 910891 |
Floodplain | Original | N | 10/14/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 910890 |
Floodplain | Original | N | 10/14/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 910889 |