Plumbing | Splice 4/4/17 | A | 4/4/2017 | TCRIPPEN | TCRIPPEN | new plumbing splice | | Plumbing | 949438 |
Out to Review | Splice 4/4/17 | / | 4/4/2017 | GITA | GITA | | | Out to Review | 949435 |
Electrical | Splice 3/14/17 | A | 3/14/2017 | BERTHA | BERTHA | | | Electrical | 943476 |
Out to Review | Splice 3/14/17 | / | 3/14/2017 | GITA | GITA | | | Out to Review | 943466 |
CO Springs Fire | Original | A | 1/4/2017 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 928064 |
Hazmat | Original | N | 1/4/2017 | CSFIRE | CSFIRE | | dwithee | Hazmat | 928073 |
Water Division | Original | A | 1/4/2017 | CSUREVIEW | CSUREVIEW | Existing water service adequate CQ | cquinn_ds | Water Division | 927951 |
Electrical | Original | A | 12/29/2016 | SHELBY | SHELBY | | | Electrical | 927293 |
Plumbing | Original | A | 12/29/2016 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 927258 |
Out to Review | Original | / | 12/27/2016 | MINDY | MINDY | Rowell 719 659 4100 | | Out to Review | 926469 |
Finished Bin | Original | / | 12/23/2016 | | JESSICAM | Location = Finished Bin by JESSICAM | | Finished Bin | 926351 |
Water Division | Original | D | 12/23/2016 | CSUREVIEW | CSUREVIEW | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate. mjg | mgackle | Water Division | 926325 |
CSU Utilities | Original | / | 12/20/2016 | | CSFIRE | Location = CSU Utilities by CSFIRE | dwithee | CSU Utilities | 925472 |
Hazmat | Original | D | 12/20/2016 | CSFIRE | CSFIRE | | dwithee | Hazmat | 925471 |
CO Springs Fire | Original | D | 12/20/2016 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 925469 |
Fire | Original | / | 12/19/2016 | | JESSICAM | Location = Fire by JESSICAM | | Fire | 924951 |
Plan Coordinator | Original | / | 12/19/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 924934 |
Plumbing | Original | D | 12/19/2016 | TCRIPPEN | TCRIPPEN | Provide fixture to occupant load for combined floors short on drinking fountains, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 924933 |
Plumbing | Original | / | 12/19/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 924899 |
Plumbing | Original | / | 12/16/2016 | | JESSICAM | Location = Plumbing by JESSICAM | | Plumbing | 924667 |
Plan Coordinator | Original | / | 12/16/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 924647 |
Mechanical | Original | A | 12/16/2016 | JUSTINC | JUSTINC | | | Mechanical | 924646 |
Mechanical | Original | / | 12/16/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 924601 |
Mechanical | Original | / | 12/16/2016 | | JESSICAM | Location = Mechanical by JESSICAM | | Mechanical | 924527 |
Plan Coordinator | Original | / | 12/15/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 924503 |
Electrical | Original | A | 12/15/2016 | SHELBY | SHELBY | | | Electrical | 924502 |
Electrical | Original | / | 12/15/2016 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 924382 |
Electrical | Original | / | 12/15/2016 | | RITA | Location = Electrical by RITA | | Electrical | 924329 |
Plan Coordinator | Original | / | 12/15/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 924300 |
Construction | Original | A | 12/15/2016 | MICHAELA | MICHAELA | | | Construction | 924299 |
Construction | Original | / | 12/15/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 924275 |
Construction | Original | / | 12/15/2016 | | NELIDA | Location = Construction by NELIDA | | Construction | 924179 |
Resubmittal 1 | Original | / | 12/15/2016 | NELIDA | NELIDA | Resubmittal #1 12/15/16 | | Resubmittal 1 | 924178 |
Out to Review | Original | / | 12/2/2016 | REBECCA | REBECCA | 719-659-4100 rowell | | Out to Review | 921731 |
Water Division | Original | D | 12/2/2016 | CSUREVIEW | CSUREVIEW | Requires an updated Commercial Water Meter Sizing Form (CWMSF) and development charges/fees may apply subject to review of CWMSF. Please contact our office at 719-668-8111. mjg | mgackle | Water Division | 921515 |
Waste Water Div | Original | A | 12/2/2016 | CSUREVIEW | CSUREVIEW | mjg | mgackle | Waste Water Div | 921516 |
CSU Utilities | Original | / | 12/1/2016 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 921476 |
Hazmat | Original | D | 12/1/2016 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 921445 |
CO Springs Fire | Original | D | 12/1/2016 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 921443 |
Fire | Original | / | 11/18/2016 | | MMCCONNELL | Location = Fire by MMCCONNELL | | Fire | 919006 |
CO Springs DRE | Original | A | 11/18/2016 | MMCCONNELL | MMCCONNELL | interior finish med office (see full review) | | CO Springs DRE | 919005 |
Zoning/Planning | Original | / | 11/18/2016 | MMCCONNELL | MMCCONNELL | In Current Review by MMCCONNELL | | Zoning/Planning | 918842 |
Zoning/Planning | Original | / | 11/17/2016 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 918656 |
Plumbing | Original | D | 11/17/2016 | JUSTINC | JUSTINC | Review incomplete pending approved floor plan
NO WALK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 918627 |
Mechanical | Original | D | 11/17/2016 | JUSTINC | JUSTINC | Review incomplete pending approved floor plan
NO WALK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 918626 |
Mechanical | Original | / | 11/17/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 918428 |
Mechanical | Original | / | 11/14/2016 | | JESSICAM | Location = Mechanical by JESSICAM | | Mechanical | 917476 |
Plan Coordinator | Original | / | 11/14/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 917390 |
Electrical | Original | D | 11/14/2016 | SHELBY | SHELBY | Show SCA at new panel on one line. Review incomplete pending approved floor plan (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 917389 |
Electrical | Original | / | 11/14/2016 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 917383 |
Electrical | Original | / | 11/8/2016 | | JESSICAM | Location = Electrical by JESSICAM | | Electrical | 916640 |
Plan Coordinator | Original | / | 11/8/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 916616 |
Construction | Original | D | 11/8/2016 | MICHAELA | MICHAELA | Provide code compliant separation of exits for occupant load greater than 50 in a non-sprinklered building No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 916609 |
Construction | Original | / | 11/8/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 916526 |
Construction | Original | / | 11/8/2016 | | JESSICAM | Location = Construction by JESSICAM | | Construction | 916488 |
Plan Coordinator | Original | / | 11/8/2016 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 916467 |
Enumeration | Original | A | 11/8/2016 | BRENT | BRENT | single tenant taking up two spaces. Using Suite 200 as the business address. | | Enumeration | 916466 |
Floodplain | Original | N | 11/7/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 916360 |
Floodplain | Original | N | 11/7/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 916361 |