Finished Bin | Splice 4/17/17 | / | 4/21/2017 | | MINDY | Location = Finished Bin by MINDY - fin bin per ben P | | Finished Bin | 954363 |
Electrical | Splice 4/17/17 | A | 4/21/2017 | BERTHA | BERTHA | | | Electrical | 954348 |
Out to Review | Splice 4/17/17 | / | 4/20/2017 | JANE | JANE | ben 719 332 2006 | | Out to Review | 954055 |
Finished Bin | Splice 4/17/17 | / | 4/20/2017 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 953903 |
Electrical | Splice 4/17/17 | D | 4/17/2017 | BERTHA | BERTHA | 1. Homogenize Panel A labeling - New or Existing. 2. If individually metered service provide meters and enumerated addresses. 3. Panel B SCA exceeds AIC rating of panel. 4. Panel H SCA exceeds AIC rating of panel. 5. Remove parallel neutral from feeder 2.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 952893 |
Plumbing | Splice 4/17/17 | A | 4/17/2017 | TCRIPPEN | TCRIPPEN | new splice page new mop sink | | Plumbing | 952885 |
Out to Review | Splice 4/17/17 | / | 4/17/2017 | BECKYA | BECKYA | Splice 4/17/17 | | Out to Review | 952861 |
Electrical | Splice 4/17/17 | A | 3/13/2017 | SHELBY | SHELBY | Installation is meter stack | | Electrical | 943196 |
Electrical | Splice 4/17/17 | D | 3/10/2017 | BERTHA | BERTHA | Configure service per CSU standards.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 942952 |
Out to Review | Splice 4/17/17 | / | 3/10/2017 | GITA | GITA | | | Out to Review | 942936 |
Plumbing | 2/21/17 | A | 2/27/2017 | TCRIPPEN | TCRIPPEN | new splice pages adding bath room , mop sink, and trench drain | | Plumbing | 939744 |
Mechanical | 2/21/17 | A | 2/27/2017 | JUSTINC | JUSTINC | Revised for bath addition | | Mechanical | 939734 |
Out to Review | 2/21/17 | / | 2/27/2017 | SHELBY | SHELBY | | | Out to Review | 939722 |
Electrical | 2/21/17 | A | 2/27/2017 | SHELBY | SHELBY | | | Electrical | 939721 |
Electrical | 2/21/17 | D | 2/27/2017 | SHELBY | SHELBY | 1. Remove parallel neutral. 2. Collate panel voltages. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 939615 |
Construction | 2/21/17 | A | 2/27/2017 | BPHILLIPS | BPHILLIPS | added restroom | | Construction | 939597 |
Mechanical | 2/21/17 | D | 2/21/2017 | DALEH | DALEH | provide previous schedules (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 938158 |
Plumbing | 2/21/17 | D | 2/21/2017 | TCRIPPEN | TCRIPPEN | see red lines 4 inch required, vent required, grate type required. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 938151 |
Electrical | 2/21/17 | D | 2/21/2017 | BERTHA | BERTHA | Provide clouded drawings for splice. Cloud changes only.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 938141 |
Construction | Original | A | 1/9/2017 | BPHILLIPS | BPHILLIPS | approve MA 12/30/16 | | Construction | 928903 |
Hazmat | Original | N | 1/9/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 928881 |
CO Springs Fire | Original | N | 1/9/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 928880 |
Electrical | Original | A | 1/5/2017 | BERTHA | BERTHA | | | Electrical | 928305 |
Mechanical | Original | A | 1/5/2017 | JUSTINC | JUSTINC | | | Mechanical | 928259 |
Out to Review | Original | / | 1/3/2017 | RDCUSER | RDCUSER | | | Out to Review | 927757 |
CO Springs DRE | Original | N | 1/3/2017 | RDCUSER | RDCUSER | interior remodel for restoroom. (see full review) | | CO Springs DRE | 927756 |
Mechanical | Original | D | 1/3/2017 | JUSTINC | JUSTINC | How providing ventilation to office cannot use warehouse. Must be from outdoors
RETURN ALL COMMENT SHEETS WITH NEXT REVIEW WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 927752 |
Electrical | Original | D | 12/30/2016 | BERTHA | BERTHA | Clarify new and existing. Verify duplicate conflicting information. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 927484 |
Plumbing | Original | A | 12/30/2016 | TCRIPPEN | TCRIPPEN | okay water and waste water removed not required, | | Plumbing | 927483 |
Enumeration | Original | A | 12/30/2016 | BRENT | BRENT | | | Enumeration | 927476 |
Floodplain | Original | A | 12/30/2016 | BRENT | BRENT | floodplain permit number 16085 | | Floodplain | 927475 |
Out to Review | Original | / | 12/30/2016 | REBECCA | REBECCA | walking | | Out to Review | 927453 |