Plan Coordinator | 8/16/2017 | / | 8/23/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 989281 |
Mechanical | 8/16/2017 | A | 8/16/2017 | TCRIPPEN | TCRIPPEN | Okay, new splice relocate duct work. | | Mechanical | 987076 |
Mechanical | 8/16/2017 | / | 8/16/2017 | | JANE | Location = Mechanical by JANE | | Mechanical | 987010 |
Electrical | Splice 7/13/17 | A | 7/13/2017 | BERTHA | BERTHA | Revised lighting layout. | | Electrical | 977683 |
Out to Review | Splice 7/13/17 | / | 7/13/2017 | BECKYA | BECKYA | | | Out to Review | 977675 |
Construction | Splice 7/13/17 | A | 7/13/2017 | MICHAELA | MICHAELA | Add drop ceiling | | Construction | 977659 |
Scanned/Finished Bin | Original | / | 4/27/2017 | | JLANE | Location = Scanned/Finished Bin by JLANE | | Scanned/Finished Bin | 955729 |
To Be Scanned Bin | Original | / | 4/25/2017 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 955082 |
Out to Review | Original | / | 4/24/2017 | MINDY | MINDY | Terri P | | Out to Review | 954765 |
Health Dept. | Original | A | 4/21/2017 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Jodi Zimmerman 719-433-3685 | abrannon | Health Dept. | 954438 |
Finished Bin | Original | / | 4/17/2017 | | JESSICAM | Location = Finished Bin by JESSICAM | | Finished Bin | 952815 |
Health Dept. | Original | D | 4/17/2017 | HEALTHDEPT | HEALTHDEPT | Plan review required. Please contact the health department at (719) 578-3199 option 3. ABrannon | abrannon | Health Dept. | 952770 |
Health Dept. | Original | / | 4/17/2017 | | JESSICAM | Location = Health Dept. by JESSICAM | | Health Dept. | 952706 |
Plan Coordinator | Original | / | 4/17/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 952699 |
Construction | Original | D | 4/17/2017 | SHELLEY | SHELLEY | New sheets provided with no corresponding redlines. This submittal includes an addition to the shell for the drive-thru window - provide structural plans to include foundation design, soils report, and roof framing; provide IECC and allowable area calcs for addition; neither of the door schedules reference back to doors on the floor plans - provide schedule that references doors - provide hardware on both schedules or remove one. There is a lot of duplicate information in this plan. see plans for all comments; walk ok. RTU support located on M200 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 952698 |
Construction | Original | / | 4/17/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 952645 |
Construction | Original | / | 4/14/2017 | | MINDY | Location = Construction by MINDY | | Construction | 952568 |
Resubmittal 1 | Original | / | 4/14/2017 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 952567 |
Fountain Zoning | Original | A | 4/14/2017 | MINDY | MINDY | 03/13/2017 | | Fountain Zoning | 952566 |
Fountain Water | Original | A | 4/14/2017 | MINDY | MINDY | 02/24/2017 Stratmoor Hills | | Fountain Water | 952565 |
Fountain Waste Water | Original | A | 4/14/2017 | MINDY | MINDY | 02/24/2017 Stratmoor Hills | | Fountain Waste Water | 952564 |
Hazmat | Original | N | 4/14/2017 | MINDY | MINDY | | | Hazmat | 952563 |
Mechanical | Original | A | 3/30/2017 | JUSTINC | JUSTINC | | | Mechanical | 948346 |
Plumbing | Original | A | 3/29/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 948027 |
Electrical | Original | A | 3/29/2017 | SHELBY | SHELBY | | | Electrical | 948010 |
Enumeration | Original | A | 3/29/2017 | AMY | AMY | SEE SITE PLAN PAGE A-1001 FOR ALL ADDRESSING. | | Enumeration | 947962 |
Fountain Fire | Original | A | 3/8/2017 | FNTNFIRE | FNTNFIRE | MAS Fountain Fire Department OK Require 1 horn strobe Area in front of electrical panels not to be used as delivery area or storage Require 2 ABC 5 LB Fire Extinguishers 2A; 10 BC rating | mstanwood | Fountain Fire | 942194 |
Out to Review | Original | / | 2/24/2017 | MINDY | MINDY | Teri P | | Out to Review | 939210 |
Finished Bin | Original | / | 2/23/2017 | | JLANE | Location = Finished Bin by JLANE | | Finished Bin | 938903 |
Health Dept. | Original | D | 2/23/2017 | HEALTHDEPT | HEALTHDEPT | Plan review required. Please contact the health department at (719) 578-3199 option 3. ABrannon (719)352-1842 | abrannon | Health Dept. | 938844 |
Health Dept. | Original | / | 2/22/2017 | | MINDY | Location = Health Dept. by MINDY | | Health Dept. | 938612 |
Plan Coordinator | Original | / | 2/22/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 938596 |
Plumbing | Original | D | 2/22/2017 | TCRIPPEN | TCRIPPEN | P 400 missing sizes and notes for numbers see red lines. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 938595 |
Plumbing | Original | / | 2/15/2017 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 936971 |
Mechanical | Original | D | 2/14/2017 | DALEH | DALEH | back draft damper on exhaust fan co2 tanks for carbonated drinks ? what is distance from regulator to farthest appliance ? see plans for complete red lines return red lines with next review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 936744 |
Mechanical | Original | / | 2/9/2017 | | JLANE | Location = Mechanical by JLANE | | Mechanical | 935790 |
Plan Coordinator | Original | / | 2/9/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 935735 |
Electrical | Original | D | 2/9/2017 | BERTHA | BERTHA | 1. Approval pending Enumerations approval. 2. Enumerated address must be noted for meter on one-line diagram. 3. Remove parallel neutral between CT and disconnect.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 935734 |
Electrical | Original | / | 2/7/2017 | | JESSICAM | Location = Electrical by JESSICAM | | Electrical | 935136 |
Plan Coordinator | Original | / | 2/7/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 935093 |
Construction | Original | D | 2/7/2017 | MICHAELA | MICHAELA | Demising wall labeled as existing does not appear on any permits in our system - who is constructing this wall? Doors are not sized or identified by type - provide door schedule including existing doors with hardware schedule Plan calls out wall type 3 at storefront glazing - drywall over windows? Restroom 1 door encroaches more than 50% into the required egress width of the corridor Main entry door location does not match shell location No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 935092 |
Construction | Original | / | 2/7/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 934994 |
Construction | Original | / | 2/6/2017 | | JESSICAM | Location = Construction by JESSICAM | | Construction | 934816 |
Plan Coordinator | Original | / | 2/6/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 934809 |
Enumeration | Original | D | 2/6/2017 | BRENT | BRENT | This is a multi tenant building. include a site plan showing all tenant spaces with suite numbering and area of work highlighted. update code study form and all plan pages to show the suite number for this tenant. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 934807 |
Floodplain | Original | N | 2/1/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 933844 |
Floodplain | Original | N | 2/1/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 933843 |
Floodplain | Original | N | 2/1/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 933842 |