Water Division | Original | A | 11/29/2018 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Water Division | 1135739 |
Waste Water Div | Original | A | 11/29/2018 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Waste Water Div | 1135737 |
Electrical | Original | A | 11/29/2018 | BERTHA | BERTHA | Stamp over 1 year old. Re-approved - restamped. | | Electrical | 1135720 |
Enumeration | Original | A | 11/29/2018 | AMY | AMY | | | Enumeration | 1135701 |
Mechanical | Original | A | 11/29/2018 | TCRIPPEN | TCRIPPEN | okay restamp | | Mechanical | 1135691 |
Plumbing | Original | A | 11/29/2018 | TCRIPPEN | TCRIPPEN | okay restamp | | Plumbing | 1135690 |
Construction | Original | A | 10/24/2018 | SHELLEY | SHELLEY | Updated approval, no changes to sheets. | | Construction | 1123255 |
Water Division | Original | A | 11/6/2017 | NELIDA | NELIDA | see label | | Water Division | 1010339 |
Waste Water Div | Original | A | 11/6/2017 | NELIDA | NELIDA | see label | | Waste Water Div | 1010338 |
Hazmat | Original | N | 11/6/2017 | NELIDA | NELIDA | see label | | Hazmat | 1010337 |
Cimarron Hills Fire | Original | A | 11/6/2017 | NELIDA | NELIDA | see label | | Cimarron Hills Fire | 1010336 |
Construction | Original | A | 5/26/2017 | DANM | DANM | | | Construction | 964050 |
Out to Review | Original | / | 5/26/2017 | NELIDA | NELIDA | Jennifer 719-488-2145 | | Out to Review | 963789 |
Finished Bin | Original | / | 5/25/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 963595 |
Plan Coordinator | Original | / | 5/25/2017 | | BECKYA | Location = Plan Coordinator by BECKYA | | Plan Coordinator | 963571 |
Mechanical | Original | A | 5/25/2017 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 963566 |
County Zoning | Original | A | 5/25/2017 | DSDRANGEL | DSDRANGEL | FEE PAID PER SDP | | County Zoning | 963412 |
Mechanical | Original | / | 5/25/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Mechanical | 963259 |
Mechanical | Original | / | 5/24/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 963245 |
Plan Coordinator | Original | / | 5/24/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 963216 |
Construction | Original | D | 5/24/2017 | SHELLEY | SHELLEY | Clarify if non-rated windows above fire wall termination will be replaced with rated windows or wall infill - if wall infill, provide assembly. Walk ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 963214 |
Construction | Original | / | 5/24/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 963195 |
Construction | Original | / | 5/24/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 962825 |
Electrical | Original | A | 5/19/2017 | BERTHA | BERTHA | | | Electrical | 961657 |
Out to Review | Original | / | 5/19/2017 | JANE | JANE | Jennifer | | Out to Review | 961638 |
Electrical | Original | / | 5/18/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 961498 |
Plan Coordinator | Original | / | 5/18/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 961442 |
Construction | Original | D | 5/18/2017 | SHELLEY | SHELLEY | There should only be 1 code study form - revise as noted; fire walls cannot turn horizontally - address continuity at alcove to santuary - fire shudder may be better option; not meeting stepped building provisions throughout plan; provide secondary listing to complete W4 - or would U305 work; ceiling assembly provided is for floor, not roof, and components are missing to comply; several locations where two different walls type intersect at fire wall create a breach in protection; rated materials need to follow through on both sides of wall; 2x top plate cannot span over bearing wall and fire wall; see plans for all comments; no walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 961440 |
Construction | Original | / | 5/18/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 961333 |
Construction | Original | / | 5/18/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 961299 |
Resubmittal 3 | Original | / | 5/18/2017 | JANE | JANE | Resubmittal #3 | | Resubmittal 3 | 961297 |
Out to Review | Original | / | 5/10/2017 | RITA | RITA | Jennifer 434-5630 | | Out to Review | 959135 |
Zoning/Planning | Original | / | 5/8/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 958385 |
Plan Coordinator | Original | / | 5/8/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 958319 |
Mechanical | Original | D | 5/8/2017 | TCRIPPEN | TCRIPPEN | see constructions notes 2 hour wall required between lobby/sanctuary (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 958317 |
Mechanical | Original | / | 5/8/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Mechanical | 958275 |
Mechanical | Original | / | 5/5/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 958133 |
Electrical | Original | D | 5/5/2017 | SHELBY | SHELBY | please comply with previous review comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 958123 |
Plumbing | Original | A | 5/5/2017 | DALEH | DALEH | | | Plumbing | 958113 |
Electrical | Original | / | 5/5/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 958097 |
Electrical | Original | / | 5/3/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 957289 |
Plan Coordinator | Original | / | 5/3/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 957253 |
Construction | Original | D | 5/3/2017 | SHELLEY | SHELLEY | Still missing IECC; revised code study form to match architectural plans; Fire wall required between hall/lobby and sanctuary in order to use VB type of construction; revised allowable areas to show each building (area) as it's own square footage; provisions of 706 have not been shown throughout plans for fire wall continuity and structural stability requirements; no section references on floor plan to A3.03 sheet; clarify a two hour wall being used for supporting construction and corridor wall; stud wall next to U415 fire wall must be 1-hour on it's own to afford proper supporting construction in VA building; W4 does not match listing; ceiling listing not from valid table; show handrails at ramp and stairs that comply with all of 1012; revise structural to match architectural plans; see plans for comments and clarifications; no walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 957252 |
Construction | Original | / | 5/3/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 957167 |
Construction | Original | / | 5/2/2017 | | GITA | Location = Construction by GITA | | Construction | 956897 |
Resubmittal 2 | Original | / | 5/2/2017 | GITA | GITA | Resubmittal #2 | | Resubmittal 2 | 956895 |
Out to Review | Original | / | 4/20/2017 | SHELLEY | SHELLEY | jennifer; 719-434-5630 | | Out to Review | 953793 |
Construction | Original | / | 4/20/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY - for meeting with DP | | Construction | 953705 |
Construction | Original | / | 4/20/2017 | | MINDY | Location = Construction by MINDY | | Construction | 953704 |
Electrical | Original | / | 4/19/2017 | | JLANE | Location = Electrical by JLANE | | Electrical | 953369 |
Plan Coordinator | Original | / | 4/19/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 953345 |
Construction | Original | D | 4/19/2017 | SHELLEY | SHELLEY | STILL PRELIMINARY REVIEW - too many items not addressed from previous cursory review and building has not been proven to be able to be constructed. see plans; no walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 953344 |
Construction | Original | / | 4/19/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 953321 |
Construction | Original | / | 4/18/2017 | | MINDY | Location = Construction by MINDY | | Construction | 953286 |
Resubmittal 1 | Original | / | 4/18/2017 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 953285 |
Out to Review | Original | / | 3/3/2017 | RITA | RITA | Randy Stewart 71-260-9999 | | Out to Review | 941145 |
Finished Bin | Original | / | 3/3/2017 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 941060 |
Zoning/Planning | Original | / | 3/3/2017 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 941045 |
Plan Coordinator | Original | / | 3/3/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 940986 |
Mechanical | Original | D | 3/3/2017 | TCRIPPEN | TCRIPPEN | Construction calling out rated walls and corridor, plans are incomplete plenary review only, No walk through ///// (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 940983 |
Plumbing | Original | D | 3/2/2017 | TCRIPPEN | TCRIPPEN | Need approved occupant load for fixture count, show required mop sink and drinking fountain, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 940502 |
Mechanical | Original | / | 3/2/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Mechanical | 940444 |
Mechanical | Original | / | 2/24/2017 | | JESSICAM | Location = Mechanical by JESSICAM | | Mechanical | 939084 |
Electrical | Original | D | 2/24/2017 | SHELBY | SHELBY | Provide load calculation per NEC. ( see load summary basing load calculation on non updated information 21 years old). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 939036 |
Plan Coordinator | Original | / | 2/24/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Plan Coordinator | 939028 |
Plan Coordinator | Original | / | 2/17/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 937677 |
Construction | Original | D | 2/17/2017 | SHELLEY | SHELLEY | PRELIMINARY REVIEW ONLY Provide IECC for envelope; provide referenced soils report; clarify square footage; clarify additional fire walls and fire barriers; clarify occupant load; clarify sprinklers; clarify rated corridors; provide listed assemblies to meet all requirements of type VA construction and other rated wall requirements; incorrect wall types appear to be referenced; clarify accessible route to platform; provide all clearances in restrooms; revise door schedule to reflect correct rating on doors; see plans for comment clarifications; no walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 937676 |
Construction | Original | / | 2/16/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 937504 |
Construction | Original | / | 2/15/2017 | | MINDY | Location = Construction by MINDY | | Construction | 937019 |
Plan Coordinator | Original | / | 2/15/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 936998 |
Enumeration | Original | A | 2/15/2017 | AMY | AMY | ADDITION TO EXISTING 910 PETERSON ROAD. | | Enumeration | 936997 |
Enumeration | Original | / | 2/15/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 936995 |
Floodplain | Original | N | 2/14/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 936716 |