Mechanical | Splice 7/27/17 | A | 7/27/2017 | TCRIPPEN | TCRIPPEN | adjusted calculations, added after hours ventilation table, adjusted CFM | | Mechanical | 981837 |
Out to Review | Splice 7/27/17 | / | 7/27/2017 | BECKYA | BECKYA | | | Out to Review | 981813 |
Electrical | 5/4/17 | A | 5/23/2017 | SHELBY | SHELBY | | | Electrical | 962612 |
Construction | 5/4/17 | A | 5/23/2017 | DANM | DANM | Revise double door to single and misc details | | Construction | 962594 |
Plumbing | 5/4/17 | A | 5/23/2017 | TCRIPPEN | TCRIPPEN | new splice page adding water heater | | Plumbing | 962593 |
Mechanical | 5/4/17 | A | 5/23/2017 | DALEH | DALEH | | | Mechanical | 962583 |
Out to Review | 5/4/17 | / | 5/23/2017 | BECKYA | BECKYA | Added MEP to splice | | Out to Review | 962561 |
Out to Review | 5/4/17 | / | 5/4/2017 | JANE | JANE | Mark Mahler | | Out to Review | 957503 |
Electrical | Splice 5/3/17 | A | 5/3/2017 | SHELBY | SHELBY | | | Electrical | 957434 |
Plumbing | Splice 5/3/17 | A | 5/3/2017 | JUSTINC | JUSTINC | | | Plumbing | 957399 |
Mechanical | Splice 5/3/17 | A | 5/3/2017 | JUSTINC | JUSTINC | | | Mechanical | 957392 |
Waste Water Div | Original | A | 3/27/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. Garbage disposal deleted. HSF | hfranson | Waste Water Div | 947037 |
Mechanical | Original | A | 3/27/2017 | DALEH | DALEH | | | Mechanical | 947032 |
Out to Review | Original | / | 3/22/2017 | MICHAELA | MICHAELA | | | Out to Review | 945945 |
Construction | Original | A | 3/22/2017 | MICHAELA | MICHAELA | | | Construction | 945944 |
Finished Bin | Original | / | 3/21/2017 | | JESSICAM | Location = Finished Bin by JESSICAM | | Finished Bin | 945331 |
Water Division | Original | A | 3/20/2017 | CSUREVIEW | CSUREVIEW | Water service lines already connected to building. Backflow assembly OK per Tara McGowan. HSF | hfranson | Water Division | 944840 |
Waste Water Div | Original | D | 3/20/2017 | CSUREVIEW | CSUREVIEW | Garbage disposals are not recommended by CSU. Either delete the proposed garbage disposal, or Contact Kim Caltrider (719-668-4506) to discuss a possible variance. If approved, add copy of variance letter to this permit set. HSF Note: per voice mail from Kim on 3/27 variance not approved. | hfranson | Waste Water Div | 944602 |
CSU Utilities | Original | / | 3/17/2017 | | JESSICAM | Location = CSU Utilities by JESSICAM | | CSU Utilities | 944559 |
Hazmat | Original | N | 3/17/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 944537 |
CO Springs Fire | Original | A | 3/17/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 944536 |
Zoning/Planning | Original | / | 3/9/2017 | DWOLF | DWOLF | In Current Review by DWOLF | | Zoning/Planning | 942558 |
Zoning/Planning | Original | / | 3/8/2017 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 942268 |
Plan Coordinator | Original | / | 3/8/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 942191 |
Plumbing | Original | A | 3/8/2017 | TCRIPPEN | TCRIPPEN | okay,water and waste water removed not required. | | Plumbing | 942190 |
Plumbing | Original | / | 3/8/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 942125 |
Plumbing | Original | / | 3/7/2017 | | JESSICAM | Location = Plumbing by JESSICAM | | Plumbing | 942017 |
Plan Coordinator | Original | / | 3/7/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 941965 |
Mechanical | Original | D | 3/7/2017 | JUSTINC | JUSTINC | Verify ventilation schedule? Why using office space for locker room? See 09' IMC 403.3 Locker/dressing room. How exhausting locker room per 09' IMC 403.3? It appears some of the title block has been cut off? Enlarge floor plans to 1/4" scale for clarity. Remove grid background for clarity.
REVIEW INCOMPLETE RETURN ALL COMMENT SHEETS WITH NEXT REVIEW
WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 941964 |
Mechanical | Original | / | 3/7/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 941819 |
Mechanical | Original | / | 3/6/2017 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 941548 |
Plan Coordinator | Original | / | 3/6/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 941529 |
Electrical | Original | A | 3/6/2017 | SHELBY | SHELBY | | | Electrical | 941528 |
Electrical | Original | / | 3/6/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 941502 |
Electrical | Original | / | 3/3/2017 | | MINDY | Location = Electrical by MINDY | | Electrical | 940814 |
Plan Coordinator | Original | / | 3/2/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 940787 |
Construction | Original | D | 3/2/2017 | MICHAELA | MICHAELA | Reconcile two different square footage numbers on plan and code study Provide ANSI compliant clear floor space at all doors Missing 18" vertical grab bar at toilet rooms Walk-through Ok (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 940786 |
Construction | Original | / | 3/2/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 940730 |
Construction | Original | / | 3/2/2017 | | MINDY | Location = Construction by MINDY | | Construction | 940581 |
Plan Coordinator | Original | / | 3/2/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 940539 |
Enumeration | Original | A | 3/2/2017 | BRENT | BRENT | combining suites 135 and 145 and using suite 135 as address. | | Enumeration | 940538 |
Floodplain | Original | N | 2/28/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 939993 |