Mechanical | 8/18/17 | A | 8/18/2017 | DALEH | DALEH | | | Mechanical | 988089 |
Construction | Splice 7/7/17 | A | 7/7/2017 | MICHAELA | MICHAELA | Replace rated assembly | | Construction | 976078 |
Out to Review | Splice 7/7/17 | / | 7/7/2017 | BECKYA | BECKYA | | | Out to Review | 976074 |
Electrical | Original | A | 6/2/2017 | BERTHA | BERTHA | | | Electrical | 965685 |
Electrical | Original | D | 5/31/2017 | BERTHA | BERTHA | Provide complete one-line diagram including all service gear and conductor size, type and quantity beginning with the utility transformer.
Existing 400A service overloaded.
All new electrical sheets inserted prior to scanning/after permit.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 964589 |
Out to Review | Original | / | 5/31/2017 | | SCANNING | Location = Out to Review by SCANNING See Notes from Plan Coordinator 5/31/17 Plans returned to person who brought them to Permit Counter be scanned by GITA (Note by JLANE) | | Out to Review | 964584 |
Plan Coordinator | Original | / | 5/31/2017 | | SCANNING | Location = Plan Coordinator by SCANNING Set ELECTRICAL to PENDING as New Pages were added needs further Electrical Review for new pages added per Bertha, Did NOT scan plan when it came into scanning as "Live" Plan. JLANE This plan is currently "Out To Review" | | Plan Coordinator | 964583 |
Health Dept. | Original | A | 5/30/2017 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Jodi Zimmerman 719-433-3685 | Jzimmerman | Health Dept. | 964440 |
Plumbing | Original | A | 5/15/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 960297 |
Out to Review | Original | / | 5/15/2017 | JUSTINC | JUSTINC | | | Out to Review | 960285 |
Mechanical | Original | A | 5/15/2017 | JUSTINC | JUSTINC | | | Mechanical | 960284 |
Water Division | Original | N | 5/10/2017 | CSUREVIEW | CSUREVIEW | No new water service line proposed outside the building. Building has master meter with approved backflow. HSF | hfranson | Water Division | 959382 |
Waste Water Div | Original | N | 5/10/2017 | CSUREVIEW | CSUREVIEW | No new wastewater service line proposed outside the building. Existing grease interceptor/grease line. HSF | hfranson | Waste Water Div | 959379 |
Hazmat | Original | N | 5/10/2017 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 959335 |
CO Springs Fire | Original | A | 5/10/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 959334 |
Fire | Original | / | 5/2/2017 | | SDALSING | Location = Fire by SDALSING | | Fire | 957031 |
CO Springs DRE | Original | A | 5/2/2017 | SDALSING | SDALSING | Interior Finish suite170 (see full review) | | CO Springs DRE | 957030 |
Zoning/Planning | Original | / | 4/26/2017 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 955469 |
Plumbing | Original | D | 4/26/2017 | TCRIPPEN | TCRIPPEN | high - low drinking fountain required per code , you didn't sign and date your stamp. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 955447 |
Plumbing | Original | / | 4/26/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 955425 |
Plumbing | Original | / | 4/26/2017 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 955320 |
Plan Coordinator | Original | / | 4/26/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 955294 |
Mechanical | Original | D | 4/26/2017 | JUSTINC | JUSTINC | Seals not signed?
REST OK WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 955293 |
Mechanical | Original | / | 4/26/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 955277 |
Mechanical | Original | / | 4/25/2017 | | JESSICAM | Location = Mechanical by JESSICAM | | Mechanical | 955078 |
Plan Coordinator | Original | / | 4/25/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 955031 |
Construction | Original | A | 4/25/2017 | MICHAELA | MICHAELA | | | Construction | 955030 |
Construction | Original | / | 4/25/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 955020 |
Construction | Original | / | 4/24/2017 | | JESSICAM | Location = Construction by JESSICAM | | Construction | 954641 |
Plan Coordinator | Original | / | 4/24/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 954634 |
Enumeration | Original | A | 4/24/2017 | BRENT | BRENT | | | Enumeration | 954633 |
Enumeration | Original | / | 4/21/2017 | | RITA | Location = Enumeration by RITA | | Enumeration | 954468 |
Resubmittal 1 | Original | / | 4/21/2017 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 954273 |
Out to Review | Original | / | 3/20/2017 | RDCUSER | RDCUSER | Rick Cihak picked up plans 3/20/17 | | Out to Review | 944817 |
Zoning/Planning | Original | / | 3/17/2017 | | JESSICAM | Location = Zoning/Planning by JESSICAM | | Zoning/Planning | 944455 |
Electrical | Original | A | 3/17/2017 | SHELBY | SHELBY | | | Electrical | 944299 |
Electrical | Original | / | 3/17/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 944268 |
Mechanical | Original | D | 3/16/2017 | JUSTINC | JUSTINC | REVIEW INCOMPLETE
Relocate all associated gas work to (M) sheets for review. 10% + or - is all that is allowed for air balance schedule. Provide refrig. calculations for walk-in cooler/freezers per 09' IMC 1103.1. Indicate if within allowable limits. If over allowable limits indicate on plan how protecting. Vented roof curbs are only permitted when duct is to be installed within a 1HR shaft. Indicate duct size of duct serving oven hood, Indicate type of duct to be used on oven hood. Will there be any insulation installed on duct serving oven?
RETURN ALL COMMENT SHEETS WITH NEXT REVIEW
NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 944100 |
Electrical | Original | / | 3/16/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electrical | 944034 |
Electrical | Original | / | 3/14/2017 | | TCRIPPEN | Location = Electrical by TCRIPPEN | | Electrical | 943653 |
Plumbing | Original | D | 3/14/2017 | TCRIPPEN | TCRIPPEN | review not complete need approved occupant type and load for fixture count, gas pipe and related items to be on the M-pages per our web site.F-1 and M one rest room and drinking fountain okay 3-21-17 TCC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 943651 |
Plumbing | Original | / | 3/14/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 943624 |
Plumbing | Original | / | 3/14/2017 | | JESSICAM | Location = Plumbing by JESSICAM | | Plumbing | 943623 |
Electrical | Original | / | 3/9/2017 | | JLANE | Location = Electrical by JLANE | | Electrical | 942626 |
Plan Coordinator | Original | / | 3/9/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 942569 |
Construction | Original | D | 3/9/2017 | MICHAELA | MICHAELA | Bakery is an F-1 occupancy - provide height and area calculations - not in projected occupancy for shell Missing 18" vertical grab bars at toilet rooms Toilet room must be on an accessible route from the M occupancy - may not require travel through kitchen No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 942568 |
Construction | Original | / | 3/8/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 942402 |
Construction | Original | / | 3/8/2017 | | MINDY | Location = Construction by MINDY | | Construction | 942271 |
Plan Coordinator | Original | / | 3/8/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 942188 |
Enumeration | Original | D | 3/8/2017 | BRENT | BRENT | The suite numbering shown on the location plan is incorrect. Suite 500 would indicate a 5th floor suite. This is a single story structure. It appears that this tenant will occupy both suites 160 and 170. Confirm that this is correct. If this is correct, then tenant needs to pick which suite it will use as the business address and update all plan pages and code study form to reflect this address. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 942187 |
Floodplain | Original | N | 3/6/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 941617 |
Floodplain | Original | N | 3/6/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 941616 |