Out to Review | Splice 2/2/18 | / | 2/6/2018 | TCRIPPEN | TCRIPPEN | | | Out to Review | 1035073 |
Plumbing | Splice 2/2/18 | N | 2/6/2018 | TCRIPPEN | TCRIPPEN | not using this splice page. | | Plumbing | 1035072 |
Finished Bin | Splice 2/2/18 | / | 2/5/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1034836 |
Plan Coordinator | Splice 2/2/18 | / | 2/5/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1034738 |
Mechanical | Splice 2/2/18 | A | 2/5/2018 | JUSTINC | JUSTINC | Revised combustion air louver sizes | | Mechanical | 1034737 |
Mechanical | Splice 2/2/18 | / | 2/5/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1034621 |
Mechanical | Splice 2/2/18 | / | 2/2/2018 | | BECKYA | Location = Mechanical by BECKYA | | Mechanical | 1034566 |
Plumbing | Splice 2/2/18 | D | 2/2/2018 | TCRIPPEN | TCRIPPEN | need one vent to outside, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1034552 |
Out to Review | Splice 2/2/18 | / | 2/2/2018 | BECKYA | BECKYA | | | Out to Review | 1034534 |
Scanned/Finished Bin | Original | / | 12/26/2017 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1023767 |
To Be Scanned Bin | 12/20/17 | / | 12/22/2017 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1023709 |
Plan Coordinator | 12/20/17 | / | 12/22/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1023705 |
Plumbing | 12/20/17 | A | 12/22/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1023704 |
Plumbing | 12/20/17 | / | 12/22/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1023694 |
Plan Coordinator | 12/20/17 | / | 12/22/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1023676 |
Mechanical | 12/20/17 | A | 12/22/2017 | DALEH | DALEH | | | Mechanical | 1023675 |
Mechanical | 12/20/17 | / | 12/22/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1023611 |
Mechanical | 12/20/17 | / | 12/21/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1023367 |
Plan Coordinator | 12/20/17 | / | 12/21/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1023347 |
Electrical | 12/20/17 | A | 12/21/2017 | SHELBY | SHELBY | | | Electrical | 1023343 |
Electrical | 12/20/17 | / | 12/21/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1023317 |
Electrical | 12/20/17 | / | 12/21/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1023285 |
Plan Coordinator | 12/20/17 | / | 12/21/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1023257 |
Construction | 12/20/17 | A | 12/21/2017 | DANM | DANM | Add Makeup Air Unit and increase egress width with double entry door | | Construction | 1023256 |
Construction | 12/20/17 | / | 12/20/2017 | DANM | DANM | In Current Review by DANM | | Construction | 1023191 |
Construction | 12/20/17 | / | 12/20/2017 | | NELIDA | Location = Construction by NELIDA | | Construction | 1023142 |
Out to Review | Original | / | 10/18/2017 | RITA | RITA | Rick 303-596-9799 | | Out to Review | 1005090 |
Scanned/Finished Bin | Original | / | 8/30/2017 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 991593 |
To Be Scanned Bin | Original | / | 8/30/2017 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 991530 |
Electrical | Original | A | 8/30/2017 | RITA | RITA | per SLE 08/30/17 | | Electrical | 991529 |
Electrical | Original | A | 8/30/2017 | SHELBY | SHELBY | Set as pending in Electrical to ensure new MEP sheets added after scanning are scanned before permit is issued. | | Electrical | 991522 |
Plumbing | Original | A | 8/30/2017 | TCRIPPEN | TCRIPPEN | new page change p-trap from cast iron to pvc | | Plumbing | 991493 |
Mechanical | Original | A | 8/30/2017 | DALEH | DALEH | re-approved changes to boiler and combustion air | | Mechanical | 991472 |
Out to Review | Original | / | 8/30/2017 | NELIDA | NELIDA | Micah 719-306*-3131 | | Out to Review | 991426 |
Scanned/Finished Bin | Original | / | 8/16/2017 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 987211 |
To Be Scanned Bin | Original | / | 8/15/2017 | | JANE | Location = To Be Scanned Bin by JANE | | To Be Scanned Bin | 986618 |
County Fire | Original | A | 8/15/2017 | JANE | JANE | | | County Fire | 986617 |
Palmer Lake Zoning | Original | N | 8/15/2017 | JANE | JANE | | | Palmer Lake Zoning | 986616 |
Out to Review | Original | / | 8/8/2017 | RITA | RITA | Wyatt 303-304-8616 | | Out to Review | 984684 |
Finished Bin | Original | / | 8/2/2017 | | JANE | Location = Finished Bin by JANE | | Finished Bin | 983205 |
Electrical | Original | A | 8/2/2017 | BERTHA | BERTHA | | | Electrical | 983202 |
Mechanical | Original | A | 8/1/2017 | DALEH | DALEH | | | Mechanical | 983072 |
Plumbing | Original | A | 8/1/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 983055 |
Out to Review | Original | / | 7/24/2017 | AMY | AMY | EERICK 231-2573 | | Out to Review | 980357 |
Finished Bin | Original | / | 7/20/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 979650 |
Plan Coordinator | Original | / | 7/20/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 979614 |
Plumbing | Original | D | 7/20/2017 | TCRIPPEN | TCRIPPEN | need details on pit their is none on the A - pages how and what to build out of, how are you complying with the required restroom`s (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 979613 |
Plumbing | Original | / | 7/19/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 979349 |
Plan Coordinator | Original | / | 7/19/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 979289 |
Mechanical | Original | D | 7/19/2017 | DALEH | DALEH | need operating pressure and horsepower of boiler provide site plan on mechanical sheet to show exact routing of gas piping back to meter location see plans for complete green lines return green lines with next review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 979287 |
Mechanical | Original | / | 7/19/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 979149 |
Mechanical | Original | / | 7/18/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 978786 |
Plan Coordinator | Original | / | 7/17/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 978219 |
Electrical | Original | D | 7/17/2017 | SHELBY | SHELBY | 1. Please clarify new VS existing ( see labeling on Electrical sheets VS labeling on AS101 ). 2. Comply 225.30 NEC. 3. Comply 250.32 NEC (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 978218 |
Electrical | Original | / | 7/14/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 977904 |
Electrical | Original | / | 7/3/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 974852 |
Plan Coordinator | Original | / | 7/3/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 974798 |
Construction | Original | A | 7/3/2017 | DANM | DANM | | | Construction | 974797 |
Construction | Original | / | 6/30/2017 | DANM | DANM | In Current Review by DANM | | Construction | 974791 |
Construction | Original | / | 6/30/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 974790 |
Resubmittal 1 | Original | / | 6/30/2017 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 974451 |
Finished Bin | Original | / | 6/15/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 969398 |
Plumbing | Original | D | 6/15/2017 | DANM | DANM | Per TimC - provide plumbing sheets (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 969376 |
Construction | Original | / | 6/14/2017 | DANM | DANM | In Current Review by DANM | | Construction | 969367 |
Construction | Original | / | 6/14/2017 | | BERTHA | Location = Construction by BERTHA | | Construction | 969366 |
Electrical | Original | D | 6/14/2017 | BERTHA | BERTHA | Provide Electrical
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 969365 |
Plan Coordinator | Original | / | 6/14/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 969361 |
Mechanical | Original | D | 6/14/2017 | JUSTINC | JUSTINC | Provide full mechanical scope with this permit (M) sheet.
NO WALK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 969360 |
Mechanical | Original | / | 6/14/2017 | | DANM | Location = Mechanical by DANM | | Mechanical | 969330 |
Finished Bin | Original | / | 6/12/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 968436 |
Plan Coordinator | Original | / | 6/12/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 968407 |
Electrical | Original | N | 6/12/2017 | SHELBY | SHELBY | | | Electrical | 968406 |
Electrical | Original | / | 6/12/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 968215 |
Electrical | Original | / | 6/12/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 968134 |
Plan Coordinator | Original | / | 6/12/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 968052 |
Construction | Original | D | 6/12/2017 | DANM | DANM | Clarify if membrane meets IBC 3102.3.1, if so, then Construction Type is II-B - Storage structure out of wood not allowed in Type II-B construction Provide engineer stamp / signature / date on pool sheets (AQ1.0, AQ3.0) Clarify Sheet S1.0 which appears to be from an apartment project No walk-through review allowed
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 968051 |
Construction | Original | / | 6/9/2017 | DANM | DANM | In Current Review by DANM | | Construction | 967922 |
Construction | Original | / | 6/9/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 967592 |
Plan Coordinator | Original | / | 6/8/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 967581 |
Floodplain | Original | N | 3/16/2017 | BRENT | BRENT | | | Floodplain | 944191 |