Plumbing | Splice 02/13/20 | A | 2/13/2020 | SHANEN | SHANEN | Delta 3 revisions to remove plumbing scope of work. Note: Pool shall not/will not drain to storm. | | Plumbing | 1286251 |
Plumbing | Splice 02/13/20 | D | 2/13/2020 | SHANEN | SHANEN | Pool run-off cannot go to storm. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1286197 |
Out to Review | Splice 02/13/20 | / | 2/13/2020 | BECKYA | BECKYA | | | Out to Review | 1286174 |
Mechanical | Splice 07/09/19 | A | 7/9/2019 | TCRIPPEN | TCRIPPEN | new mechanical splice for gas pipe | | Mechanical | 1211008 |
Out to Review | Splice 07/09/19 | / | 7/9/2019 | NELIDA | NELIDA | Jim walking 719-232-3339 | | Out to Review | 1210921 |
Scanned/Finished Bin | Original | / | 7/21/2017 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 980081 |
To Be Scanned Bin | Original | / | 7/21/2017 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 980077 |
Plan Coordinator | Original | / | 7/21/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 980075 |
Plumbing | Original | A | 7/21/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 980074 |
Plumbing | Original | / | 7/21/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 980073 |
Plumbing | Original | / | 7/21/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 980072 |
To Be Scanned Bin | Original | / | 7/21/2017 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 980066 |
Enumeration | Original | A | 7/21/2017 | AMY | AMY | | | Enumeration | 980062 |
Out to Review | Original | / | 7/21/2017 | | NELIDA | Location = Out to Review by NELIDA | | Out to Review | 980050 |
Hazmat | Original | N | 7/20/2017 | CSFIRE | CSFIRE | Plans N/A, below permit amounts. No inspection required. (see full review) | smanning | Hazmat | 979939 |
CO Springs Fire | Original | A | 7/17/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 978506 |
Electrical | Original | A | 7/17/2017 | SHELBY | SHELBY | | | Electrical | 978482 |
Out to Review | Original | / | 7/6/2017 | JANE | JANE | 719 232 3339 | | Out to Review | 975739 |
Finished Bin | Original | / | 6/20/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 970944 |
Enumeration | Original | D | 6/20/2017 | SCANNING | SCANNING | Per RTP 06/20/17 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 970943 |
CO Springs Fire | Original | D | 6/20/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 970896 |
Fire | Original | / | 6/14/2017 | | SCANNING | Location = Fire by SCANNING | | Fire | 969321 |
Plan Coordinator | Original | / | 6/14/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 969312 |
Electrical | Original | D | 6/14/2017 | BERTHA | BERTHA | Provide compliance with 240.85 NEC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 969310 |
Electrical | Original | / | 6/14/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 969034 |
Electrical | Original | / | 6/12/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 968409 |
Resubmittal 2 | Original | / | 6/12/2017 | JANE | JANE | Resubmittal #2 | | Resubmittal 2 | 968373 |
Out to Review | Original | / | 6/7/2017 | NELIDA | NELIDA | Jim 719-232-3339 | | Out to Review | 966794 |
Finished Bin | Original | / | 6/7/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 966789 |
Hazmat | Original | D | 6/7/2017 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 966765 |
Waste Water Div | Original | A | 6/7/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. Pool drain directed to existing pump room. HSF | hfranson | Waste Water Div | 966759 |
CO Springs Fire | Original | D | 6/2/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 965553 |
Fire | Original | / | 5/26/2017 | | RTEFERTILLER | Location = Fire by RTEFERTILLER | | Fire | 963746 |
CO Springs DRE | Original | A | 5/26/2017 | RTEFERTILLER | RTEFERTILLER | construction plans are consistent with the recently updated approved development plan for the site: CPC DP 87-204-A3(89)-MM01 (see full review) | | CO Springs DRE | 963745 |
Zoning/Planning | Original | / | 5/24/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 963243 |
Plan Coordinator | Original | / | 5/24/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 963208 |
Plumbing | Original | A | 5/24/2017 | TCRIPPEN | TCRIPPEN | approved as noted on plans | | Plumbing | 963207 |
Plumbing | Original | / | 5/24/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 963148 |
Plan Coordinator | Original | / | 5/24/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 962953 |
Mechanical | Original | A | 5/24/2017 | JUSTINC | JUSTINC | | | Mechanical | 962952 |
Mechanical | Original | / | 5/24/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 962850 |
Mechanical | Original | / | 5/23/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 962614 |
Plan Coordinator | Original | / | 5/23/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 962592 |
Electrical | Original | D | 5/23/2017 | BERTHA | BERTHA | 1. Provide compliance with 240.85 NEC 2. Provide compliance with 408.3(E)(1) NEC 3. Provide compliance with 408.3(F)(1) NEC 4. Provide compliance with 110.15 NEC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 962591 |
Electrical | Original | / | 5/22/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 962050 |
Electrical | Original | / | 5/22/2017 | | BERTHA | Location = Electrical by BERTHA | | Electrical | 962049 |
Plan Coordinator | Original | / | 5/17/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 961175 |
Construction | Original | A | 5/17/2017 | DANM | DANM | | | Construction | 961174 |
Construction | Original | / | 5/17/2017 | DANM | DANM | In Current Review by DANM | | Construction | 961065 |
Construction | Original | / | 5/17/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 960835 |
Resubmittal 1 | Original | / | 5/17/2017 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 960830 |
Out to Review | Original | / | 4/25/2017 | RITA | RITA | JIM 719-232-3339 | | Out to Review | 955027 |
Water Division | Original | A | 4/24/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. Backflow device is OK per Jessica Davis. HSF | hfranson | Water Division | 954776 |
Finished Bin | Original | / | 4/24/2017 | | JESSICAM | Location = Finished Bin by JESSICAM | | Finished Bin | 954758 |
Water Division | Original | D | 4/24/2017 | CSUREVIEW | CSUREVIEW | CSU checking to see if there is an acceptable backflow device. If not, you will need to provide a Backflow Assembly Plan Review Form. It can be found at https://www.csu.org/CSUDocuments/backflowdomesticform.pdf. Contact Tara McGowan at 719-668-8253 with any questions. HSF | hfranson | Water Division | 954717 |
Waste Water Div | Original | D | 4/24/2017 | CSUREVIEW | CSUREVIEW | Provide the approved Utility Service Plan(USP) if connections being made to existing wastewater service line or wastewater main outside of main building. Show on plans how discharge from pool drain is limited to 100 gpm. Contact Utilities Development Services at 668-8111 with questions. HSF | hfranson | Waste Water Div | 954716 |
CSU Utilities | Original | / | 4/24/2017 | | CSFIRE | Location = CSU Utilities by CSFIRE | dwithee | CSU Utilities | 954684 |
Hazmat | Original | D | 4/24/2017 | CSFIRE | CSFIRE | | dwithee | Hazmat | 954683 |
CO Springs Fire | Original | D | 4/24/2017 | CSFIRE | CSFIRE | Need HazMat Triage form (see full review) | csfdit | CO Springs Fire | 954681 |
Fire | Original | / | 4/13/2017 | | RTEFERTILLER | Location = Fire by RTEFERTILLER | | Fire | 951873 |
CO Springs DRE | Original | D | 4/13/2017 | RTEFERTILLER | RTEFERTILLER | While Planning Staff supports the proposed work, the existing development plan (CPC DP 87-204-A3(90)) for the property must be amended to reflect the activation of the roof-top space. Please contact Ryan Tefertiller at 385-5382 to discuss the required application and review process. (see full review) | | CO Springs DRE | 951872 |
Zoning/Planning | Original | / | 4/10/2017 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 951065 |
Electrical | Original | / | 4/5/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 949950 |
Electrical | Original | D | 4/5/2017 | SHELBY | SHELBY | 1. New transformer supply side bonding jumper is incorrect. 2. For note 4 sheet E1.1 detail methodology for contractor compliance. 3. Show required EPO location( 680.41 NEC). 4. Note required encapsulation inspection ( 680.23(B)(2)(b) NEC ). 5. Note compliance with 680.26 NEC. 6. Provide complete one line. 7. Provide load calculations for panels effected by this scope of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 949949 |
Electrical | Original | / | 4/4/2017 | | TCRIPPEN | Location = Electrical by TCRIPPEN | | Electrical | 949493 |
Plumbing | Original | D | 4/4/2017 | TCRIPPEN | TCRIPPEN | no drain lines can drain onto the ground, back flow device required on water line with drain to an approved location. remove duplicate pages. , (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 949492 |
Plumbing | Original | / | 4/4/2017 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 949490 |
Electrical | Original | / | 4/4/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electrical | 949489 |
Mechanical | Original | D | 4/4/2017 | JUSTINC | JUSTINC | Provide detail to show connection to (E) gas meter. Verify (E) gas meter can carry new loads. Verify 10' separation to roof edge per 09' IMC 304.11
WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 949485 |
Electrical | Original | / | 4/4/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electrical | 949434 |
Electrical | Original | / | 4/3/2017 | | JESSICAM | Location = Electrical by JESSICAM | | Electrical | 948959 |
Plan Coordinator | Original | / | 4/3/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 948943 |
Construction | Original | D | 4/3/2017 | DANM | DANM | Travel distance should be measured to an exit or a level of protection such as an exit enclosure - see Sheet A1.0 for correct exiting Provide listed assemblies for all new primary and secondary structural members per I-A type of construction Pool deck appears to be elevated - provide enlarged plan and section(s) showing how exiting through Door 201 and how exiting on to roof No walk-through review allowed
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 948941 |
Construction | Original | / | 4/3/2017 | DANM | DANM | In Current Review by DANM | | Construction | 948883 |
Construction | Original | / | 3/31/2017 | | JESSICAM | Location = Construction by JESSICAM | | Construction | 948657 |
Plan Coordinator | Original | / | 3/31/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 948645 |
Enumeration | Original | A | 3/31/2017 | BRENT | BRENT | | | Enumeration | 948644 |
Floodplain | Original | N | 3/30/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 948229 |