To Be Scanned Bin | Splice 4/5/18 | / | 4/5/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1054631 |
Mechanical | Splice 4/5/18 | A | 4/5/2018 | TCRIPPEN | TCRIPPEN | new splice R3 relocate refrigeration piping R4 revise detail 3 to include drain pan R7 added entire sheet for reference | | Mechanical | 1054583 |
Out to Review | Splice 4/5/18 | / | 4/5/2018 | BECKYA | BECKYA | | | Out to Review | 1054564 |
To Be Scanned Bin | Splice 1/23/18 | / | 1/25/2018 | | GITA | Location = To Be Scanned Bin by GITA | | To Be Scanned Bin | 1031943 |
Construction | Splice 1/23/18 | N | 1/25/2018 | MICHAELA | MICHAELA | | | Construction | 1031924 |
Mechanical | Splice 1/23/18 | A | 1/23/2018 | DALEH | DALEH | | | Mechanical | 1031134 |
Electrical | Splice 1/23/18 | A | 1/23/2018 | SHELBY | SHELBY | | | Electrical | 1031114 |
Plumbing | Splice 1/23/18 | A | 1/23/2018 | TCRIPPEN | TCRIPPEN | new splice pages revised equipment tags, revised filter diagram | | Plumbing | 1031097 |
Out to Review | Splice 1/23/18 | / | 1/23/2018 | BECKYA | BECKYA | | | Out to Review | 1031070 |
Electrical | Splice 11/27/17 | A | 11/27/2017 | SHELBY | SHELBY | | | Electrical | 1015743 |
Mechanical | Splice 11/27/17 | A | 11/27/2017 | JUSTINC | JUSTINC | | | Mechanical | 1015732 |
Out to Review | Splice 11/27/17 | / | 11/27/2017 | DANM | DANM | | | Out to Review | 1015723 |
Construction | Splice 11/27/17 | A | 11/27/2017 | DANM | DANM | Remove and replace equipment on floor plan | | Construction | 1015722 |
Plumbing | Splice 11/27/17 | A | 11/27/2017 | TCRIPPEN | TCRIPPEN | revise filter diagram for coffee equipment per owner direction. | | Plumbing | 1015694 |
Mechanical | 10/16/17 | A | 10/16/2017 | JUSTINC | JUSTINC | Revised sheet notes | | Mechanical | 1004509 |
Construction | 10/16/17 | A | 10/16/2017 | MICHAELA | MICHAELA | Minor revisions | | Construction | 1004499 |
Plumbing | 10/16/17 | A | 10/16/2017 | TCRIPPEN | TCRIPPEN | new splice pagesnew splice pages: P0 revise lav model type per proto updates, add df for clarification, remove detail 6 from sheet per proto updates P1 remove growler station plumbing stub up and associated plumbing lines per proto update, remove co2 line and plan note per proto updates, relocate restroom floor drains per owner direction. P2 remove growler station plumbing stub up and associated plumbing lines per proto update,P4 remove dimension and stub ups for growler station for clarity. revise dimension for stub up as shown on sheet for clarity. relocate restroom floor drain per owner direction.P5 revise sanitary piping per owners direction, add df for clarification.P6 revise water piping per owner direction add df for clarification | | Plumbing | 1004463 |
Electrical | 10/16/17 | A | 10/16/2017 | BERTHA | BERTHA | Multiple lighting and power revision. Updated panel schedules. | | Electrical | 1004416 |
Out to Review | 10/16/17 | / | 10/16/2017 | NELIDA | NELIDA | Teri walking | | Out to Review | 1004391 |
Scanned/Finished Bin | Original | / | 9/5/2017 | | JESSICAM | Location = Scanned/Finished Bin by JESSICAM | | Scanned/Finished Bin | 992873 |
To Be Scanned Bin | Original | / | 9/5/2017 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 992808 |
City Engr | Original | A | 9/5/2017 | CSENGINEER | CSENGINEER | Plan given to consultant. pvm | csengineer | City Engr | 992787 |
City Engr | Original | / | 8/31/2017 | | MINDY | Location = City Engr by MINDY | | City Engr | 991819 |
Hazmat | Original | A | 8/30/2017 | CSFIRE | CSFIRE | Plans approved. Please read approved comments. Plans forwarded to RBD. Additional fee applies for 3rd review. (see full review) | smanning | Hazmat | 991758 |
CSU Contract Admin. | Original | A | 8/30/2017 | CSUAPPSPRM | CSUAPPSPRM | Utility Charges and Fees paid 8/30/17. BML | bmludiker | CSU Contract Admin. | 991612 |
Enumeration | Original | A | 8/23/2017 | BRENT | BRENT | | | Enumeration | 989416 |
Mechanical | Original | A | 8/23/2017 | JUSTINC | JUSTINC | Restamped for revisions to CO2 | | Mechanical | 989375 |
Out to Review | Original | / | 8/23/2017 | NELIDA | NELIDA | Teri 491-5711 | | Out to Review | 989256 |
Finished Bin | Original | / | 8/22/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 989016 |
CSU Contract Admin. | Original | D | 8/22/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires payment of Development Charges and Fees. Call Utilities Development Services at 719-668-8111 to inquire. ZJS | zshearer | CSU Contract Admin. | 988920 |
Water Division | Original | A | 8/22/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Water Division | 988858 |
Waste Water Div | Original | A | 8/22/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Waste Water Div | 988857 |
CSU Contract Admin. | Original | / | 8/21/2017 | | MSCHULTZ | Location = CSU Contract Admin. by MSCHULTZ | | CSU Contract Admin. | 988347 |
CO Springs DRE | Original | A | 8/21/2017 | MSCHULTZ | MSCHULTZ | At time of issuance of building permit the owner/applicant should initiate a request to vacation the 50 foot public utility easement within that portion of Pearl Drive. (see full review) | | CO Springs DRE | 988346 |
Electrical | Original | A | 8/17/2017 | SHELBY | SHELBY | | | Electrical | 987618 |
Out to Review | Original | / | 8/11/2017 | RITA | RITA | Teri | | Out to Review | 986189 |
Finished Bin | Original | / | 8/7/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 984203 |
Hazmat | Original | D | 8/4/2017 | CSFIRE | CSFIRE | Plans disapproved. Please read disapproval comments. LPG Cage and Underground Fuel tanks will be submitted through Division of Fire Marshal. As this is the second review, subsequent reviews shall incur an additional fee. (see full review) | smanning | Hazmat | 984116 |
CO Springs Fire | Original | A | 8/3/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 983633 |
CSU Contract Admin. | Original | D | 7/27/2017 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved. Plat must be recorded prior to payment of development charges/fees. LMP | lmpope | CSU Contract Admin. | 981796 |
Fire | Original | / | 7/25/2017 | | SDALSING | Location = Fire by SDALSING | | Fire | 981000 |
CO Springs DRE | Original | D | 7/25/2017 | SDALSING | SDALSING | No approved DP (see full review) | | CO Springs DRE | 980999 |
Zoning/Planning | Original | / | 7/19/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 979460 |
Water Division | Original | D | 7/19/2017 | CSUREVIEW | CSUREVIEW | The following comments has not been addressed: Requires approved CSU mainline Construction Plans and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. JPN | jnoble | Water Division | 979409 |
Waste Water Div | Original | D | 7/19/2017 | CSUREVIEW | CSUREVIEW | The following comments has not been addressed: Requires approved CSU mainline Construction Plans and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. JPN | jnoble | Waste Water Div | 979408 |
CSU Contract Admin. | Original | D | 7/19/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf) and payment of development charges/fees. Contact Utilities Development Services at 719-668-8111 for more information. ZJS | zshearer | CSU Contract Admin. | 979359 |
CSU Contract Admin. | Original | / | 7/19/2017 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 979046 |
Plan Coordinator | Original | / | 7/19/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 979040 |
Enumeration | Original | D | 7/19/2017 | AMY | AMY | ENUMERATIONS WILL REVIEW THE MYLAR PRIOR TO PLAT, ADDRESSING FEE DUE AT THE TIME OF THE REVIEW, A COPY OF THE FINAL RECORDED PLAT IS REQUIRED PRIOR TO APPROVAL IN THIS DEPT.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 979039 |
Enumeration | Original | / | 7/19/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 979038 |
Enumeration | Original | / | 7/17/2017 | | SCANNING | Location = Enumeration by SCANNING | | Enumeration | 978243 |
Plan Coordinator | Original | / | 7/17/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 978221 |
Mechanical | Original | A | 7/17/2017 | DALEH | DALEH | | | Mechanical | 978220 |
Mechanical | Original | / | 7/17/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 978174 |
Mechanical | Original | / | 7/17/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 978120 |
Plan Coordinator | Original | / | 7/14/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 977972 |
Electrical | Original | D | 7/14/2017 | SHELBY | SHELBY | Please comply with previous review comments 1,2,3,and 5. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 977971 |
Electrical | Original | / | 7/14/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 977902 |
Electrical | Original | / | 7/10/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 976327 |
Plan Coordinator | Original | / | 7/10/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 976319 |
Construction | Original | A | 7/10/2017 | MICHAELA | MICHAELA | | | Construction | 976317 |
Construction | Original | / | 7/10/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 976300 |
Construction | Original | / | 7/7/2017 | | RITA | Location = Construction by RITA | | Construction | 976115 |
Resubmittal 1 | Original | / | 7/7/2017 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 976103 |
Health Dept. | Original | A | 6/7/2017 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Jodi Zimmerman 719-433-3685 | Jzimmerman | Health Dept. | 966958 |
Finished Bin | Original | / | 6/6/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 966366 |
Health Dept. | Original | D | 6/6/2017 | HEALTHDEPT | HEALTHDEPT | Health Department plan review required. MYM 578-3199 Option #3 | Michelle Martinez | Health Dept. | 966361 |
Health Dept. | Original | / | 6/5/2017 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 966017 |
Hazmat | Original | D | 6/5/2017 | CSFIRE | CSFIRE | Plans disapproved. Please read disapproval comments. Plans forwarded to RBD. (see full review) | smanning | Hazmat | 965971 |
High Pile | Original | N | 5/31/2017 | CSFIRE | CSFIRE | | dwithee | High Pile | 964888 |
Hazmat | Original | / | 5/31/2017 | | CSFIRE | Location = Hazmat by CSFIRE | dwithee | Hazmat | 964886 |
CO Springs Fire | Original | D | 5/31/2017 | CSFIRE | CSFIRE | WALK OK (see full review) | csfdit | CO Springs Fire | 964882 |
Fire | Original | / | 5/23/2017 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 962547 |
CO Springs DRE | Original | D | 5/23/2017 | RDCUSER | RDCUSER | No approved DP (see full review) | | CO Springs DRE | 962546 |
Zoning/Planning | Original | / | 5/17/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 961125 |
City Engr | Original | / | 5/10/2017 | | CSUAPPSPRM | Location = City Engr by CSUAPPSPRM | zshearer | City Engr | 959129 |
Zoning/Planning | Original | / | 5/10/2017 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | zshearer | Zoning/Planning | 959128 |
CSU Contract Admin. | Original | D | 5/10/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires annexation or agreement to annex, approved Commercial Water Meter Sizing Form, and Payment of Development Charges and Fees. ZJS | zshearer | CSU Contract Admin. | 959127 |
Water Division | Original | D | 5/9/2017 | CSUREVIEW | CSUREVIEW | Requires approved CSU mainline Construction Plans and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. HSF | hfranson | Water Division | 958827 |
Waste Water Div | Original | D | 5/9/2017 | CSUREVIEW | CSUREVIEW | Requires approved CSU mainline Construction Plans and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. HSF | hfranson | Waste Water Div | 958825 |
Gas/Elec. Utils | Original | A | 5/9/2017 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final meter/service line/transformer locations. Please contact JC Butterfield at 719-668-5618 with any gas/electric questions. HSF | hfranson | Gas/Elec. Utils | 958817 |
CSU Contract Admin. | Original | / | 5/9/2017 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 958705 |
Plan Coordinator | Original | / | 5/9/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 958685 |
Mechanical | Original | D | 5/9/2017 | DALEH | DALEH | provide a ventilation schedule (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 958683 |
Mechanical | Original | / | 5/9/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 958604 |
Mechanical | Original | / | 5/8/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 958160 |
Plan Coordinator | Original | / | 5/5/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 958153 |
Electrical | Original | D | 5/5/2017 | BERTHA | BERTHA | 1. Provide conductor size, type and quantity - service lateral. 2. Verify information prior to plan submittal - see Electrical Service Note sheet E3.0. 3. Comply 110.26(C)(2). 4. Comply 514.11(B) NEC 5. Comply 240.87
Plans in series - 87331, 96679, 96681
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 958109 |
Electrical | Original | / | 5/1/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 956423 |
Plumbing | Original | A | 4/28/2017 | TCRIPPEN | TCRIPPEN | okay. | | Plumbing | 956221 |
Electrical | Original | / | 4/27/2017 | | JLANE | Location = Electrical by JLANE | | Electrical | 955938 |
Plan Coordinator | Original | / | 4/27/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 955871 |
Construction | Original | D | 4/27/2017 | MICHAELA | MICHAELA | Revise envelope ComCheck to 2007 ASRAE IN LIEU OF ADDING A VESTIBULE PLEASE FILL OUT AN "ALTERNATE MATERIAL AND METHODS" FORM FOUND ON THE RBD WEBSITE TO USE AN AIR CURTAIN PER THE 2015 IBC. PLEASE STAMP THE COMPLETED FORM AND INCLUDE IT WITH THE RESUBMITTAL. Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 955870 |
Construction | Original | / | 4/27/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 955701 |
Construction | Original | / | 4/26/2017 | | MINDY | Location = Construction by MINDY | | Construction | 955450 |
Plan Coordinator | Original | / | 4/26/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 955428 |
Enumeration | Original | D | 4/26/2017 | AMY | AMY | TAX SCHEDULE NUMBER & LEGAL DESCRIPTION WILL CHANGE AFTER PLAT, ALL WRECKING PERMITS NEED TO BE IN PLACE AND COMPLETED PRIOR TO PERMITTING THIS PLAN, RETAIL STORE WAS ASSIGNED 4512 AUSTIN BLUFFS PKWY & FUEL CANOPY 4514 AUSTIN BLUFFS PKWY, EDIT THE END TABS TO SHOW THE CORRECT ADDRESSING FOR PAGES.
FENCING TO TRASH ENCLOSURE 6 FOOT NO PERMIT REQUIRED,
ENUMERATIONS WILL REVIEW THE MYLAR PRIOR TO PLAT, ADDRESSING FEE DUE AT THE TIME OF THE REVIEW, A COPY OF THE FINAL RECORDED PLAT IS REQUIRED PRIOR TO APPROVAL IN THIS DEPT.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 955427 |
Floodplain | Original | N | 4/17/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 952988 |