Health Dept. | Original | A | 9/25/2017 | MINDY | MINDY | requested to add Health, per Jodi Zimmerman with EPCO Health. | | Health Dept. | 998305 |
Health Dept. | Original | A | 9/18/2017 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Jodi Zimmerman 719-433-3685 | Jzimmerman | Health Dept. | 999484 |
Plumbing | Splice 7/13/17 | A | 7/13/2017 | TCRIPPEN | TCRIPPEN | okay, added water heater platform, adjusted cals,removed sanitary waste lines, showing new sanitary waste lines on new page | | Plumbing | 977461 |
Out to Review | Splice 7/13/17 | / | 7/13/2017 | BECKYA | BECKYA | | | Out to Review | 977435 |
Waste Water Div | Original | A | 6/19/2017 | CSUREVIEW | CSUREVIEW | Grease interceptor model Watts GI-75-K (150 lb.) proposed on plumbing plans. Comment addressed. HSF | hfranson | Waste Water Div | 970427 |
Hazmat | Original | N | 6/19/2017 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 970411 |
CO Springs Fire | Original | A | 6/19/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 970409 |
Resubmittal 1 | Original | / | 6/14/2017 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 969014 |
Electrical | Original | A | 6/13/2017 | SHELBY | SHELBY | | | Electrical | 968766 |
Out to Review | Original | / | 6/13/2017 | TCRIPPEN | TCRIPPEN | with Jim 719-232-3339 | | Out to Review | 968753 |
Plumbing | Original | A | 6/13/2017 | TCRIPPEN | TCRIPPEN | approved as noted on plans | | Plumbing | 968751 |
Water Division | Original | A | 6/13/2017 | CSUREVIEW | CSUREVIEW | Backflow form approved by Holly Link per email dated 6/12/17. HSF | hfranson | Water Division | 968601 |
Waste Water Div | Original | D | 6/12/2017 | CSUREVIEW | CSUREVIEW | Variance to have a 150 pound grease trap instead of a grease interceptor was approved on 4/25/17. Ensure that the proposed grease trap conforms to this size. If you propose a different size, please contact Kim Caltrider (719-668-4506). HSF | hfranson | Waste Water Div | 968010 |
Finished Bin | Original | / | 6/12/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 968013 |
Water Division | Original | D | 6/12/2017 | CSUREVIEW | CSUREVIEW | Need to submit a Backflow Assembly Plan Review Form to determine if a backflow assembly exists. It can be found at https://www.csu.org/CSUDocuments/backflowdomesticform.pdf. Contact Tara McGowan at 719-668-8253 or Holly Link at 719-668-4733 with any questions. HSF | hfranson | Water Division | 968009 |
Hazmat | Original | D | 6/9/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 967769 |
CO Springs Fire | Original | D | 6/9/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 967767 |
Fire | Original | / | 6/2/2017 | | MBINGMAN | Location = Fire by MBINGMAN | | Fire | 965628 |
CO Springs DRE | Original | N | 6/2/2017 | MBINGMAN | MBINGMAN | Interior remodel in FBZ. MRB per MPF (see full review) | | CO Springs DRE | 965627 |
Zoning/Planning | Original | / | 5/30/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 964353 |
Plan Coordinator | Original | / | 5/30/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 964318 |
Plumbing | Original | D | 5/30/2017 | TCRIPPEN | TCRIPPEN | need variance letter for grease trap it controls the size and fixtures to go to the grease trap. hot water source shall not be over 50 feet without pump. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 964317 |
Plumbing | Original | / | 5/30/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 964280 |
Plumbing | Original | / | 5/25/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 963447 |
Plan Coordinator | Original | / | 5/25/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 963436 |
Mechanical | Original | A | 5/25/2017 | JUSTINC | JUSTINC | | | Mechanical | 963434 |
Mechanical | Original | / | 5/25/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 963379 |
Mechanical | Original | / | 5/25/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 963314 |
Plan Coordinator | Original | / | 5/25/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 963265 |
Electrical | Original | D | 5/25/2017 | SHELBY | SHELBY | 1. New 112.5 KVA transformer encroaches on required clearance for existing panel LP1. 2. label all new and relocated electrical equipment/devices with panel and circuit number ( see note 3 E 1.1 etc). 3. Provide complete one line. 4. Supply side bonding jumper for panel A is incorrect. 5. See http://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf for detailed requirements. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 963264 |
Electrical | Original | / | 5/25/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 963253 |
Electrical | Original | / | 5/24/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 963143 |
Plan Coordinator | Original | / | 5/24/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 963107 |
Construction | Original | A | 5/24/2017 | MICHAELA | MICHAELA | | | Construction | 963106 |
Construction | Original | / | 5/24/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 962809 |
Construction | Original | / | 5/23/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 962622 |
Plan Coordinator | Original | / | 5/23/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 962599 |
Enumeration | Original | A | 5/23/2017 | BRENT | BRENT | Permit history for this business is at 119 E Pikes Peak, yet the awning outside the entrance says 123 E. Pikes Peak.This should change to reflect the permitted address. | | Enumeration | 962598 |
Floodplain | Original | N | 5/17/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 960831 |