Out to Review | Splice 04/18/18 | / | 5/7/2018 | NELIDA | NELIDA | picked up by Eli Morris | | Out to Review | 1065472 |
Scanned/Finished Bin | Splice 04/18/18 | / | 4/19/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1059390 |
Plan Coordinator | Splice 04/18/18 | / | 4/19/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1059229 |
Mechanical | Splice 04/18/18 | A | 4/19/2018 | JUSTINC | JUSTINC | Revised gas layout and RTU schedule | | Mechanical | 1059227 |
Mechanical | Splice 04/18/18 | / | 4/19/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1059197 |
Mechanical | Splice 04/18/18 | / | 4/18/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1058751 |
Out to Review | 4/11/18 | / | 4/18/2018 | RITA | RITA | ELli 704-654-7399 | | Out to Review | 1058744 |
Scanned/Finished Bin | Splice Elect 4/9/18 | / | 4/16/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1057649 |
To Be Scanned Bin | Splice Elect 4/9/18 | / | 4/16/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1057543 |
Plan Coordinator | Splice Elect 4/9/18 | / | 4/13/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1057529 |
Electrical | Splice Elect 4/9/18 | A | 4/13/2018 | BERTHA | BERTHA | Splice to provide new AIC and SCA information. | | Electrical | 1057528 |
To Be Scanned Bin | 4/11/18 | / | 4/11/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1056584 |
Plan Coordinator | 4/11/18 | / | 4/11/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1056582 |
Mechanical | 4/11/18 | A | 4/11/2018 | TCRIPPEN | TCRIPPEN | new splice relocated gas meter | | Mechanical | 1056581 |
Mechanical | 4/11/18 | / | 4/11/2018 | | NELIDA | Location = Mechanical by NELIDA | | Mechanical | 1056317 |
Electrical | Splice Elect 4/9/18 | / | 4/10/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1055871 |
Electrical | Splice Elect 4/9/18 | / | 4/9/2018 | | MATTHEWM | Location = Electrical by MATTHEWM | | Electrical | 1055387 |
Scanned/Finished Bin | 2/9/18 | / | 2/12/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1036627 |
To Be Scanned Bin | 2/9/18 | / | 2/12/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1036623 |
Plan Coordinator | 2/9/18 | / | 2/12/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1036609 |
Mechanical | 2/9/18 | A | 2/12/2018 | JUSTINC | JUSTINC | Revised sheet M001 for revised RTU schedule and wall heater schedule | | Mechanical | 1036608 |
Scanned/Finished Bin | Splice 01/16/18 | / | 1/30/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1032976 |
To Be Scanned Bin | Splice 01/16/18 | / | 1/30/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1032969 |
Plan Coordinator | Splice 01/16/18 | / | 1/30/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1032954 |
Electrical | Splice 01/16/18 | A | 1/30/2018 | SHELBY | SHELBY | | | Electrical | 1032952 |
Electrical | Splice 01/16/18 | / | 1/30/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1032862 |
Electrical | Splice 01/16/18 | / | 1/24/2018 | | GITA | Location = Electrical by GITA | | Electrical | 1031261 |
Resubmittal 1 | Splice 01/16/18 | / | 1/24/2018 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1031260 |
Finished Bin | Splice 01/16/18 | / | 1/19/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1029970 |
Plan Coordinator | Splice 01/16/18 | / | 1/19/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1029969 |
Mechanical | Splice 01/16/18 | A | 1/19/2018 | TCRIPPEN | TCRIPPEN | new splice page moved gas meter, rerouted gas lines. | | Mechanical | 1029968 |
Mechanical | Splice 01/16/18 | / | 1/18/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1029837 |
Plan Coordinator | Splice 01/16/18 | / | 1/18/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1029814 |
Electrical | Splice 01/16/18 | D | 1/18/2018 | SHELBY | SHELBY | Please cloud specific changes only ( Panel C is being added.Cloud should not include panels A and B on one line. Cloud should not include panels A and B panel schedules etc). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1029810 |
Electrical | Splice 01/16/18 | / | 1/18/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1029779 |
Electrical | Splice 01/16/18 | / | 1/16/2018 | | RITA | Location = Electrical by RITA | | Electrical | 1028632 |
CSU Contract Admin. | Original | A | 8/3/2017 | CSUAPPSPRM | CSUAPPSPRM | Utility Charges and Fees Paid 8/3/17. ZJS | zshearer | CSU Contract Admin. | 983484 |
City Engr | Original | A | 7/26/2017 | PMORRIS | PMORRIS | | | City Engr | 981212 |
Water Division | Original | A | 7/25/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Water Division | 981058 |
Waste Water Div | Original | A | 7/25/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Waste Water Div | 981057 |
Enumeration | Original | A | 7/25/2017 | AMY | AMY | | | Enumeration | 980993 |
Electronic Plan | Original | / | 7/25/2017 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 980989 |
Resubmittal 3 | Original | / | 7/25/2017 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 980910 |
CO Springs Fire | Original | A | 7/21/2017 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 980266 |
City Engr | Original | D | 7/18/2017 | PMORRIS | PMORRIS | Same comment from 6-16-2017: Include a copy of the Water Resources Engineering Division approved Grading & Erosion Control Plan in the electronic building permit set. | | City Engr | 978799 |
Health Dept. | Original | N | 7/18/2017 | HEALTHDEPT | HEALTHDEPT | Not applicable. RNielsen 575-8965 | rnielsen | Health Dept. | 978698 |
CO Springs DRE | Original | A | 7/18/2017 | DSEXTON | DSEXTON | Approved. DJS (see full review) | | CO Springs DRE | 978669 |
Enumeration | Original | D | 7/18/2017 | AMY | AMY | TRASH ENCLOSURE HEIGHT REDUCED TO 6'11'-PAGES NEED TO BE EDITED ONCE RESUBMITTED. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 978651 |
Plumbing | Original | A | 7/18/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 978615 |
Mechanical | Original | A | 7/18/2017 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 978614 |
Electronic Plan | Original | / | 7/18/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 978599 |
Enumeration | Original | A | 7/18/2017 | AMY | AMY | TRASH ENCLOSURE HEIGHT DEDUCED TO 6'11" | | Enumeration | 978537 |
Water Division | Original | D | 7/14/2017 | CSUREVIEW | CSUREVIEW | Requires approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg 7/14/2017 | mgackle | Water Division | 978044 |
Waste Water Div | Original | D | 7/14/2017 | CSUREVIEW | CSUREVIEW | Requires approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg 7/14/2017 | mgackle | Waste Water Div | 978042 |
Electrical | Original | A | 7/14/2017 | BERTHA | BERTHA | | | Electrical | 977913 |
Zoning/Planning | Original | / | 7/14/2017 | DSEXTON | DSEXTON | In Current Review by DSEXTON | | Zoning/Planning | 977798 |
CSU Contract Admin. | Original | D | 7/14/2017 | CSUAPPSPRM | CSUAPPSPRM | Same comment, Requires Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. ZJS | zshearer | CSU Contract Admin. | 977772 |
Construction | Original | A | 7/14/2017 | SHELLEY | SHELLEY | | | Construction | 977746 |
Enumeration | Original | A | 7/13/2017 | AMY | AMY | SINGLE TENANT BUILDING-9268 FOREST BLUFFS VIEW, TRASH ENCLOSURE 9262 FOREST BLUFFS VIEW.
PLAT RECEIVED. | | Enumeration | 977709 |
Electronic Plan | Original | / | 7/13/2017 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 977508 |
Resubmittal 2 | Original | / | 7/12/2017 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 977273 |
Plan Coordinator | Original | D | 7/11/2017 | JAY | JAY | Disapprove all remaining departments to allow plan to be resubmitted. Incorrect plans were uploaded. Provide Plans for correct building at this address. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 976846 |
Enumeration | Original | D | 7/11/2017 | AMY | AMY | PLANS HAVE NOW CHANGED TO ANOTHER BUILDING 9278 FOREST BLUFFS VIEW AND NOT 9268 FOREST BLUFFS VIEW. IF THIS IS NOT THE INTENT PLEASE CONTACT ENUMERATIONS 719-327-2930 OR AMY@PPRBD.ORG
ITEMS STILL NOT MET FROM LAST REVIEW:
PROPOSED LOT 6 ADDRESS IS 9268 FOREST BLUFFS VIEW NOT HIGHLANDS RIDGE HTS-EDIT CODE STUDY FORM TO REFLECT THE CORRECT ADDRESS. LEGAL DESCRIPTION SHOULD SHOW LOT 6.
TRASH ENCLOSURE ADDRESS-9262 FOREST BLUFFS VIEW
SINGLE TENANT BUILDING.
ENUMERATIONS HAS RECEIVED A COPY OF THE FINAL RECORDED PLAT.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 976798 |
Resubmittal 1 | Original | / | 7/7/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 975939 |
Hazmat | Original | N | 6/19/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 970374 |
CO Springs Fire | Original | D | 6/19/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 970373 |
City Engr | Original | D | 6/16/2017 | JDAGNILLO | JDAGNILLO | Include a copy of the City Engineering approved Grading and Erosion Control Plan in the electronic building plan set. | | City Engr | 969995 |
CO Springs DRE | Original | D | 6/14/2017 | DSEXTON | DSEXTON | Proof of final plat recordation not provided. DJS 6/14/2017 (see full review) | | CO Springs DRE | 968926 |
CSU Contract Admin. | Original | D | 6/13/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires approved commercial water meter sizing form and payment of development charges and fees. call 719-668-8111 to inquire. ZJS | zshearer | CSU Contract Admin. | 968680 |
Zoning/Planning | Original | / | 6/13/2017 | DSEXTON | DSEXTON | In Current Review by DSEXTON | | Zoning/Planning | 968654 |
Water Division | Original | D | 6/13/2017 | CSUREVIEW | CSUREVIEW | CORE/SHELL - Approved Utility Service Plan(USP) must be attached to the permit set prior to approval. Contact Utilities Development Services at 719-668-8111 with questions. HSF | hfranson | Water Division | 968567 |
Waste Water Div | Original | D | 6/13/2017 | CSUREVIEW | CSUREVIEW | CORE/SHELL - Approved Utility Service Plan(USP) must be attached to the permit set prior to approval. Contact Utilities Development Services at 719-668-8111 with questions. HSF | hfranson | Waste Water Div | 968564 |
Mechanical | Original | D | 6/12/2017 | TCRIPPEN | TCRIPPEN | provide the gas table that you are using and material you are using if high pressure show pressure regulator provide detail (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 968482 |
Health Dept. | Original | D | 6/12/2017 | HEALTHDEPT | HEALTHDEPT | Plan review required. Please contact the health department at (719) 578-3199 option 3. Rebecca Nielsen 575-8965 | rnielsen | Health Dept. | 968481 |
Electrical | Original | D | 6/12/2017 | SHELBY | SHELBY | Show SCA and AIC on one line. NOTE Three plans in this series 97982, 97983, 97984 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 968410 |
Plumbing | Original | D | 6/12/2017 | TCRIPPEN | TCRIPPEN | Provide an waster pipe size analysis. added scuppers to plumbing page for sizing and approval, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 968387 |
Gas/Elec. Utils | Original | A | 6/12/2017 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final meter/service/transformer locations. Please submit the Electric Load Data Form and the Application for Gas Service Line Approval. The forms can be found at: https://www.csu.org/Pages/development-files-forms.aspx Contact Todd Sturtevant at 719-668-3556 with any gas/electric questions. HSF | hfranson | Gas/Elec. Utils | 968379 |
Electronic Plan | Original | / | 6/12/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 968376 |
Construction | Original | D | 6/12/2017 | SHELLEY | SHELLEY | Discrepancy on sprinklers; provide canopy plans or indicate that a separate submittal required; foundation must reference soils report; allowable bearing must match between soils and design - soils does not have a bearing indicated for design chosen; see plans; (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 968311 |
Electronic Plan | Original | / | 6/12/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 968267 |
Enumeration | Original | D | 6/8/2017 | AMY | AMY | PROPOSED LOT 6 ADDRESS IS 9268 FOREST BLUFFS VIEW NOT HIGHLANDS RIDGE HTS-EDIT END TABS, PAGES & CODE STUDY FORM TO REFLECT THE CORRECT ADDRESS. LEGAL DESCRIPTION SHOULD SHOW LOT 6.
KEY SITE PLAN SHOWS LOCATION OF BUILDING-PAGE A100 Show location of trash enclosure for page A550 on an overall plan page to indicate location so that an address can be assigned.
PAGE A100 REFLECTS SUITE NUMBERING ASSIGNED BY ENUMERATIONS FOR ALL TENANT SPACES. ENUMERATIONS WILL REVIEW THE MYLAR PRIOR TO PLAT FOR ADDRESS PLACEMENT, STREET NAMES, TITLE BLOCK & FLOODPLAIN STATEMENT. A $10.00 PER LOT AND TRACT FEE WILL BE DUE AT THE TIME OF THE REVIEW OF THE MYLAR. A COPY OF THE FINAL RECORDED PLAT IS REQUIRED PRIOR TO APPROVAL IN THIS DEPARTMENT.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 967215 |
Floodplain | Original | N | 6/8/2017 | AMY | AMY | | | Floodplain | 967207 |
Electronic Plan | Original | / | 6/8/2017 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 967173 |