Electrical | Original | D | 4/25/2018 | BERTHA | BERTHA | 1. Provide service load summary. 2. Provide feeder schedule. 3. Provide 2009 IECC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1061515 |
Out to Review | Original | / | 4/25/2018 | JANE | JANE | bryan | | Out to Review | 1061495 |
Finished Bin | Original | / | 4/25/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1061274 |
CO Springs Fire | Original | D | 4/24/2018 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1061229 |
Fire | Original | / | 4/23/2018 | | SCANNING | Location = Fire by SCANNING | | Fire | 1060338 |
Plan Coordinator | Original | / | 4/20/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1060301 |
Plumbing | Original | D | 4/20/2018 | TCRIPPEN | TCRIPPEN | 2- men`s and 2 women`s toilets required provide an occupant load to fixture count on plans (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1060300 |
Plumbing | Original | / | 4/19/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1059445 |
Plan Coordinator | Original | / | 4/19/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1059310 |
Mechanical | Original | D | 4/19/2018 | JUSTINC | JUSTINC | See plan for mechanical comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1059309 |
Electrical | Original | D | 4/19/2018 | JUSTINC | JUSTINC | Pending mechanical comments per SLE (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1059241 |
Mechanical | Original | / | 4/19/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1059189 |
Mechanical | Original | / | 4/18/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1058580 |
Plan Coordinator | Original | / | 4/18/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1058564 |
Electrical | Original | A | 4/18/2018 | SHELBY | SHELBY | | | Electrical | 1058561 |
Electrical | Original | / | 4/18/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1058515 |
Electrical | Original | / | 4/17/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1058408 |
Plan Coordinator | Original | / | 4/17/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1058350 |
Construction | Original | D | 4/17/2018 | MICHAELA | MICHAELA | Revise occupant load based on correct load factor Corridors appear to serve more than 30 which would require a 1-hr. rating, 20 min. doors and glazing Sliding doors are not permitted in rooms with more than 10 occupants No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1058349 |
Construction | Original | / | 4/17/2018 | MICHAEL | MICHAEL | In Current Review by MICHAEL | | Construction | 1058275 |
Construction | Original | / | 4/17/2018 | | NELIDA | Location = Construction by NELIDA | | Construction | 1058268 |
Resubmittal 1 | Original | / | 4/17/2018 | NELIDA | NELIDA | Resubmittal #1 4/17/18 | | Resubmittal 1 | 1058233 |
Out to Review | Original | / | 7/5/2017 | BECKYA | BECKYA | Picked up by Brian 719-369-6521 | | Out to Review | 975208 |
Finished Bin | Original | / | 6/30/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 974707 |
Water Division | Original | N | 6/30/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. JPN | jnoble | Water Division | 974654 |
Waste Water Div | Original | N | 6/30/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. JPN | jnoble | Waste Water Div | 974653 |
Hazmat | Original | N | 6/30/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 974489 |
CO Springs Fire | Original | D | 6/30/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 974488 |
Fire | Original | / | 6/27/2017 | | SDALSING | Location = Fire by SDALSING | | Fire | 973298 |
CO Springs DRE | Original | N | 6/27/2017 | SDALSING | SDALSING | Interior remodel. No exterior work permitted at this time. (see full review) | | CO Springs DRE | 973297 |
Zoning/Planning | Original | / | 6/23/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 972042 |
Plan Coordinator | Original | / | 6/23/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 972002 |
Mechanical | Original | D | 6/23/2017 | JUSTINC | JUSTINC | Indicated that walls will not go to structure. Provide details. Indicate locations of existing HVAC diffuser locations on (A) sheet or provide reflected ceiling plan.Or (M) sheets.
RETURN ALL COMMENT SHEETS WITH NEXT REVIEW WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 972001 |
Mechanical | Original | / | 6/23/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 971979 |
Mechanical | Original | / | 6/23/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 971927 |
Plan Coordinator | Original | / | 6/22/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 971895 |
Electrical | Original | D | 6/22/2017 | SHELBY | SHELBY | 1. Provide complete one line. 2. Provide load calculation for the building service. See http://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 971894 |
Electrical | Original | / | 6/21/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 971241 |
Plumbing | Original | D | 6/20/2017 | TCRIPPEN | TCRIPPEN | need approved occupant classification, need an approved occupant load provide an occupant load to fixture count analysis on plans (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 970593 |
Electrical | Original | / | 6/15/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 969733 |
Plan Coordinator | Original | / | 6/15/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 969659 |
Construction | Original | D | 6/15/2017 | MICHAELA | MICHAELA | Provide code data - codes, design loads, etc. Revise occupant load as indicated Address basement occupancy Shower must be accessible - provide elevations showing accessible features Clarify purpose of beds - overnight sleeping? No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 969658 |
Construction | Original | / | 6/14/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 969189 |
Construction | Original | / | 6/12/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 968140 |
Plan Coordinator | Original | / | 6/12/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 968091 |
Enumeration | Original | A | 6/12/2017 | BRENT | BRENT | | | Enumeration | 968090 |
Floodplain | Original | N | 6/8/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 967238 |