Mechanical | Splice 9/19/17 | A | 9/19/2017 | DALEH | DALEH | splice to remove AHU and associated duct | | Mechanical | 996670 |
Out to Review | Splice 9/19/17 | / | 9/19/2017 | BECKYA | BECKYA | | | Out to Review | 996641 |
Electrical | Splice 9/14/17 | A | 9/18/2017 | BERTHA | BERTHA | Revised feeder #5 to indicate AL, Panel L indicated as new. | | Electrical | 996265 |
Resubmittal 1 | Splice 9/14/17 | / | 9/18/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 996259 |
Electrical | Splice 9/14/17 | D | 9/14/2017 | BERTHA | BERTHA | Provide updated one-line to show revised feeders and show existing Panel L as new. Provide AIC rating for Panel L. Provide available fault current at Panel L.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 995471 |
Out to Review | Splice 9/14/17 | / | 9/14/2017 | BECKYA | BECKYA | | | Out to Review | 995433 |
Mechanical | Original | A | 8/11/2017 | DALEH | DALEH | | | Mechanical | 985865 |
Electronic Plan | Original | / | 8/11/2017 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 985855 |
Electrical | Original | A | 8/10/2017 | SHELBY | SHELBY | | | Electrical | 985396 |
Plumbing | Original | A | 8/10/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 985371 |
Construction | Original | A | 8/9/2017 | MICHAELA | MICHAELA | | | Construction | 985159 |
Resubmittal 2 | Original | / | 8/8/2017 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 984818 |
Mechanical | Original | D | 7/25/2017 | DALEH | DALEH | Need to include the RTU in the gas piping plan (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 980681 |
Electrical | Original | A | 7/24/2017 | BERTHA | BERTHA | | | Electrical | 980436 |
Plumbing | Original | D | 7/21/2017 | TCRIPPEN | TCRIPPEN | provide an water pipe size analysis data on plans,gas pipe and related items to be the M - pages per our web site, show the sinks in the bathroom`s (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 980263 |
Electronic Plan | Original | / | 7/21/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 980168 |
Construction | Original | A | 7/21/2017 | MICHAELA | MICHAELA | | | Construction | 980047 |
Resubmittal 1 | Original | / | 7/20/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 979900 |
CO Springs Fire | Original | A | 7/14/2017 | CSFIRE | CSFIRE | REFERENCE REVIEW REPORT ONLINE FOR COMMENTS AND DIRECTION FOR INSPECTIONS (see full review) | csfdit | CO Springs Fire | 978038 |
Water Division | Original | N | 7/13/2017 | CSUREVIEW | CSUREVIEW | No new service lines proposed CQ | cquinn_ds | Water Division | 977425 |
Waste Water Div | Original | N | 7/13/2017 | CSUREVIEW | CSUREVIEW | No new service lines proposed CQ | cquinn_ds | Waste Water Div | 977424 |
CO Springs DRE | Original | A | 7/11/2017 | MBINGMAN | MBINGMAN | Proposed barber shop / personal consumer services. Parked as commerical center per development plan. No drive up window on east side of building for bank/atm drivethru. Interior work only. No signage approved as part of this review. (see full review) | | CO Springs DRE | 976889 |
Electrical | Original | D | 7/11/2017 | SHELBY | SHELBY | 1. Over current protection for existing feeder to tenant space panel exceeds conductor ampacity. 2. Provide load calculation for building service. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 976829 |
Hazmat | Original | N | 7/11/2017 | CSFIRE | CSFIRE | No hazmat stored; review N/A. | smanning | Hazmat | 976774 |
Zoning/Planning | Original | / | 7/11/2017 | MBINGMAN | MBINGMAN | In Current Review by MBINGMAN | | Zoning/Planning | 976769 |
Mechanical | Original | D | 7/11/2017 | DALEH | DALEH | provide a gas piping plan provide a balance schedule see plan for complete red lines (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 976656 |
Plumbing | Original | D | 7/11/2017 | TCRIPPEN | TCRIPPEN | gas piping and related items to be on the M-pages per our web site. high - low drinking fountain required. your SS fixture not part of the bath group add vent. provide an water pipe size analysis data on plans. All so provide a copy of the instantaneous water heater detail on the M - pages for approval. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 976654 |
Electronic Plan | Original | / | 7/11/2017 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 976648 |
Electronic Plan | Original | / | 7/11/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 976640 |
Construction | Original | A | 7/10/2017 | MICHAELA | MICHAELA | | | Construction | 976535 |
Electronic Plan | Original | / | 7/10/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 976492 |
Enumeration | Original | A | 7/10/2017 | BRENT | BRENT | | | Enumeration | 976391 |
Floodplain | Original | N | 6/12/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 968258 |
Floodplain | Original | N | 6/12/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 968257 |