Mechanical | 9/20/17 | A | 9/26/2017 | DALEH | DALEH | | | Mechanical | 998819 |
Resubmittal 1 | 9/20/17 | / | 9/26/2017 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 998808 |
Out to Review | 9/20/17 | / | 9/25/2017 | GITA | GITA | 3033590276 by Eric | | Out to Review | 998180 |
Finished Bin | 9/20/17 | / | 9/22/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 997912 |
Plan Coordinator | 9/20/17 | / | 9/22/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 997831 |
Mechanical | 9/20/17 | D | 9/22/2017 | JUSTINC | JUSTINC | Mechanical review incomplete
New dishwasher exhaust has been indicated Verify amount of CFM to be exhausted? Clarify how providing additional makeup air for new dish exhaust Update air balance schedule Clarify if a new EF will be installed for dishwasher exhaust system, If so update equipment schedules All revisions for splices are to be clouded. Verify with ACCUREX sheets. Only provide sheets that are to be revised.
NO WALK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 997830 |
Mechanical | 9/20/17 | / | 9/22/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 997710 |
Mechanical | 9/20/17 | / | 9/21/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 997431 |
Plan Coordinator | Original | / | 9/21/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 997328 |
Plan Coordinator | 9/20/17 | / | 9/21/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 997326 |
Construction | 9/20/17 | A | 9/21/2017 | SHELLEY | SHELLEY | revised chase | | Construction | 997324 |
Construction | Original | / | 9/20/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 996947 |
Health Dept. | Original | A | 7/14/2017 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Rebecca Nielsen 575-8965 | rnielsen | Health Dept. | 977987 |
Cimarron Hills Fire | Original | A | 7/13/2017 | JANE | JANE | | | Cimarron Hills Fire | 977421 |
Out to Review | Original | / | 7/5/2017 | MINDY | MINDY | Kory 970 443 7291 | | Out to Review | 975365 |
Finished Bin | Original | / | 7/5/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 975260 |
Plan Coordinator | Original | / | 7/5/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 975199 |
Mechanical | Original | A | 7/5/2017 | JUSTINC | JUSTINC | | | Mechanical | 975198 |
Mechanical | Original | / | 6/30/2017 | | GITA | Location = Mechanical by GITA | | Mechanical | 974508 |
Resubmittal 1 | Original | / | 6/30/2017 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 974507 |
Construction | Original | A | 6/30/2017 | MICHAELA | MICHAELA | | | Construction | 974506 |
Out to Review | Original | / | 6/23/2017 | GITA | GITA | Grechen picked up | | Out to Review | 971908 |
Finished Bin | Original | / | 6/20/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 970651 |
Plan Coordinator | Original | / | 6/20/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 970618 |
Mechanical | Original | D | 6/20/2017 | JUSTINC | JUSTINC | Provide full size manaf. sheets for ACCUREX equipment. Provide ventilation schedule per 15" IMC 403.3 Provide complete interlock schedule for makeup air and shutdowns, Indicate all associated interlocks ie., MUA, KEF-1, VAV, gas solenoid valve, ect. Clarify locations of walk-in cooler/freezers. Indicate condensate routing, pipe size pipe material, and termination location for walk-in cooler/freezers Provide refrig. calculations for walk-in cooler/freezers per 15' IMC 1103.1. Indicate if within allowable limits. If over allowable limits indicate on plan how protecting. Verify water supply and drain for makeup air unit located on roof. Freeze protection? New MUA-1 indicates weight load exceeding 300#'s. Provide stamped letter or sheet from structural engineer. Verify wall behind TYPE I hood is constructed of NON-COMBUSTIBLE materials. Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection.
REVIEW INCOMPLETE RETURN ALL COMMENT SHEETS WITH NEXT REVIEW NO WALK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 970617 |
Mechanical | Original | / | 6/20/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 970538 |
Mechanical | Original | / | 6/19/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 970381 |
Plan Coordinator | Original | / | 6/19/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 970350 |
Construction | Original | D | 6/19/2017 | SHELLEY | SHELLEY | Restroom work appears to be on previous submittal - remove if NA to this scope. walk ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 970349 |
Construction | Original | / | 6/19/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 970246 |
Construction | Original | / | 6/13/2017 | | GITA | Location = Construction by GITA | | Construction | 968847 |
Floodplain | Original | N | 6/13/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 968796 |