Plumbing | Splice 09/11/20 | A | 9/11/2020 | SHANEN | SHANEN | Delta 9 revisions: One sheet provided with this splice - P-3 adjusted plumbing maintenance plan. | | Plumbing | 1381675 |
Electronic Plan | Splice 09/11/20 | / | 9/11/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1381654 |
Construction | Splice 08/14/20 - Trusses | A | 8/17/2020 | DANM | DANM | Deferred Trusses | | Construction | 1367673 |
Electronic Plan | Splice 08/14/20 - Trusses | / | 8/17/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1367660 |
Resubmittal 1 | Splice 08/14/20 - Trusses | / | 8/17/2020 | DANM | DANM | Resubmittal #1 | | Resubmittal 1 | 1367654 |
Construction | Splice 08/14/20 - Trusses | D | 8/14/2020 | DANM | DANM | Show all necessary truss connection hardware including hangers, uplift connectors and truss bearing enhancers on truss layout
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1366765 |
Electronic Plan | Splice 08/14/20 - Trusses | / | 8/14/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1366719 |
Construction | Splice 12/05/19 | A | 12/5/2019 | DANM | DANM | Revise door width to two doors | | Construction | 1263956 |
Out to Review | Splice 12/05/19 | / | 12/5/2019 | BECKYA | BECKYA | | | Out to Review | 1263929 |
Out to Review | Original | / | 5/3/2018 | MATTHEWM | MATTHEWM | Contractor Picked up Finished | | Out to Review | 1064623 |
To Be Scanned Bin | Original | / | 5/3/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1064158 |
Water Division | Original | A | 5/2/2018 | CSUREVIEW | CSUREVIEW | MLW | mlwilliams | Water Division | 1064130 |
Waste Water Div | Original | A | 5/2/2018 | CSUREVIEW | CSUREVIEW | MLW | mlwilliams | Waste Water Div | 1064129 |
Gas/Elec. Utils | Original | A | 5/2/2018 | CSUREVIEW | CSUREVIEW | MLW | mlwilliams | Gas/Elec. Utils | 1064128 |
CSU Contract Admin. | Original | A | 12/18/2017 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved and applicable development fees and charges paid MKL | mkluke | CSU Contract Admin. | 1022070 |
Electrical | Original | A | 11/16/2017 | SHELBY | SHELBY | | | Electrical | 1013786 |
Out to Review | Original | / | 10/16/2017 | JANE | JANE | teri | | Out to Review | 1004521 |
Finished Bin | Original | / | 10/13/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1003878 |
Plan Coordinator | Original | / | 10/13/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1003850 |
Electrical | Original | D | 10/13/2017 | BERTHA | BERTHA | 1. Provide compliance with 240.87 NEC 2. Provide drawings notes for sheet E-29 (one-line) 3. Show all panels on one-lines (HC, unit panels) 4. Provide fault current calculations for all new service equipment and sub panels. 5. Provide overcurrent protection for all panels (unit panels) 6. Provide keyplan/overall site plan indicating location of all service equipment (MC, disconnects, MCB) 7. All metering configurations must comply with CSPU line extension and service standards 8. Comply 250.32(A) NEC 9. Provide service load summary. 10. Provide 2009 IECC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1003848 |
Electrical | Original | / | 10/12/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1003538 |
Electrical | Original | / | 10/10/2017 | | GITA | Location = Electrical by GITA | | Electrical | 1002742 |
Resubmittal 1 | Original | / | 10/10/2017 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1002741 |
Out to Review | Original | / | 10/3/2017 | RITA | RITA | Teri | | Out to Review | 1000931 |
Finished Bin | Original | / | 9/28/2017 | | SCANNING | Location = Finished Bin by SCANNING large shelf | | Finished Bin | 999510 |
CSU Contract Admin. | Original | D | 9/28/2017 | CSUAPPSPRM | CSUAPPSPRM | Comments: Requires Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. Taken to finish bin bml | bmludiker | CSU Contract Admin. | 999475 |
CSU Contract Admin. | Original | / | 9/28/2017 | | KCARLEO | Location = CSU Contract Admin. by KCARLEO | | CSU Contract Admin. | 999355 |
CO Springs DRE | Original | A | 9/28/2017 | KCARLEO | KCARLEO | All must maintain consistent with approved CPC PUD 16-00095 and any approved amendments. Final irrigation and landscape due within 90 days of this building permit for the whole development. No signage approved with this permit. (see full review) | | CO Springs DRE | 999354 |
City Engr | Original | A | 9/27/2017 | CSENGINEER | CSENGINEER | | csengineer | City Engr | 999005 |
Hazmat | Original | N | 9/22/2017 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 997837 |
CO Springs Fire | Original | A | 9/22/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 997836 |
Enumeration | Original | A | 9/21/2017 | BRENT | BRENT | code study form still incorrect. corrected by Enumerations. | | Enumeration | 997626 |
Water Division | Original | D | 9/18/2017 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Water Division | 996464 |
Waste Water Div | Original | D | 9/18/2017 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Waste Water Div | 996463 |
Waste Water Div | Original | A | 9/18/2017 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Waste Water Div | 996462 |
Gas/Elec. Utils | Original | D | 9/18/2017 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 996461 |
Construction | Original | A | 9/14/2017 | DANM | DANM | | | Construction | 995541 |
Plumbing | Original | A | 9/14/2017 | DALEH | DALEH | | | Plumbing | 995528 |
Mechanical | Original | A | 9/14/2017 | DALEH | DALEH | | | Mechanical | 995523 |
Electrical | Original | D | 9/11/2017 | SHELBY | SHELBY | Please provide one line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 994470 |
Out to Review | Original | / | 8/3/2017 | RITA | RITA | Teri | | Out to Review | 983709 |
Finished Bin | Original | / | 7/17/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 978516 |
Health Dept. | Original | N | 7/17/2017 | HEALTHDEPT | HEALTHDEPT | Not applicable. RNielsen 575-8965 | rnielsen | Health Dept. | 978445 |
Health Dept. | Original | / | 7/13/2017 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 977642 |
Waste Water Div | Original | D | 7/13/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg 7/13/2017 | mgackle | Waste Water Div | 977615 |
Water Division | Original | D | 7/13/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg 7/13/2017 | mgackle | Water Division | 977618 |
Gas/Elec. Utils | Original | D | 7/13/2017 | CSUREVIEW | CSUREVIEW | Show proposed gas and electric meter location on building elevation plans. mjg 7/13/2017 | mgackle | Gas/Elec. Utils | 977614 |
City Engr | Original | D | 7/11/2017 | CSENGINEER | CSENGINEER | Include a copy of the approved Development Plan in the building permit set. Plan set route to CSU Utilities. pvm | csengineer | City Engr | 976836 |
CSU Utilities | Original | / | 7/11/2017 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 976827 |
Hazmat | Original | D | 7/11/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 976826 |
CO Springs Fire | Original | D | 7/11/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 976825 |
Fire | Original | / | 7/6/2017 | | RLOZANO | Location = Fire by RLOZANO | | Fire | 975578 |
CO Springs DRE | Original | D | 7/6/2017 | RLOZANO | RLOZANO | Please provide approved copy of development plan. RTL per KAC (see full review) | | CO Springs DRE | 975577 |
Zoning/Planning | Original | / | 7/3/2017 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | mkluke | Zoning/Planning | 974966 |
CSU Contract Admin. | Original | D | 7/3/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. MKL | mkluke | CSU Contract Admin. | 974965 |
CSU Contract Admin. | Original | / | 6/30/2017 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 974582 |
Plan Coordinator | Original | / | 6/30/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 974475 |
Mechanical | Original | D | 6/30/2017 | DALEH | DALEH | provide a floor plan only provide information that pertains to maint. build. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 974473 |
Mechanical | Original | / | 6/30/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 974462 |
Mechanical | Original | / | 6/29/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 973954 |
Plan Coordinator | Original | / | 6/28/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 973948 |
Electrical | Original | D | 6/28/2017 | SHELBY | SHELBY | 1. Provide one line. 2. Comply 210.8 (B)(8) NEC. 3. Provide panel schedules for this chain of supply ( panel M etc). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 973947 |
Plumbing | Original | D | 6/21/2017 | TCRIPPEN | TCRIPPEN | back flow required for water service, remove unused items on this page. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 971110 |
Electrical | Original | / | 6/20/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 970718 |
Plan Coordinator | Original | / | 6/20/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 970686 |
Construction | Original | D | 6/20/2017 | SHELLEY | SHELLEY | 2009 Comcheck required; Verify ramp or zero entry for accessible garage door; provide enlarged restroom plans and elevations; remove all UL sheets; see plans; walk ok TRUSSES PENDING (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 970685 |
Construction | Original | / | 6/20/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 970670 |
Construction | Original | / | 6/14/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 969104 |
Plan Coordinator | Original | / | 6/14/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 969091 |
Enumeration | Original | D | 6/14/2017 | BRENT | BRENT | The address, tax schedule number and legal description shown on code study form are all incorrect. The code study form states that a legal description is attached. No correct legal description is attached. The description of work shown on the code study form does not match the principal use of building description on the code study form. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 969090 |
Floodplain | Original | N | 6/14/2017 | BRENT | BRENT | | | Floodplain | 969082 |
Enumeration | Original | / | 6/14/2017 | BRENT | BRENT | In Current Review by BRENT | | Enumeration | 969080 |