Out to Review | Splice 4/4/18 | / | 4/9/2018 | RITA | RITA | MIke 659-8057 | | Out to Review | 1055432 |
Scanned/Finished Bin | Splice 4/4/18 | / | 4/4/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1053837 |
To Be Scanned Bin | Splice 4/4/18 | / | 4/4/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1053832 |
Electrical | Splice 4/4/18 | A | 4/4/2018 | SHELBY | SHELBY | | | Electrical | 1053804 |
Mechanical | Splice 4/4/18 | A | 4/4/2018 | TCRIPPEN | TCRIPPEN | okay new splice one green wall and one solid purple wall one dotted purple wall note added to plan, added 4 fire dampers adjusted air schedule, add fire damper detail. | | Mechanical | 1053792 |
Construction | Splice 4/4/18 | A | 4/4/2018 | SHELLEY | SHELLEY | Revised floor plan | | Construction | 1053770 |
Out to Review | Splice 4/4/18 | / | 4/4/2018 | MATTHEWM | MATTHEWM | Walk | | Out to Review | 1053763 |
Hazmat | Original | A | 10/5/2017 | CSFIRE | CSFIRE | Plans approved. Please read approval comments. Inspection required for med gas system modifications (see full review) | smanning | Hazmat | 1001452 |
Electrical | Original | A | 10/2/2017 | SHELBY | SHELBY | | | Electrical | 1000490 |
Mechanical | Original | A | 10/2/2017 | JUSTINC | JUSTINC | | | Mechanical | 1000389 |
Plumbing | Original | A | 10/2/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1000113 |
Electronic Plan | Original | / | 10/2/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1000110 |
Electronic Plan | Original | / | 9/27/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 998962 |
Construction | Original | A | 9/27/2017 | BPHILLIPS | BPHILLIPS | | | Construction | 998904 |
Electronic Plan | Original | / | 9/26/2017 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 998871 |
Resubmittal 1 | Original | / | 9/26/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 998545 |
Mechanical | Original | D | 8/8/2017 | JUSTINC | JUSTINC | Please clarify will CT machines be installed with this permit? If so provide manufacture drawings, indicate routing of quench vent. Indicate termination and how protecting. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 984939 |
Electronic Plan | Original | / | 8/8/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 984633 |
Hazmat | Original | D | 8/3/2017 | CSFIRE | CSFIRE | Plans disapproved. Please provide information describing how scope of work impacts existing medical gas systems and/or other hazmat storage. (see full review) | smanning | Hazmat | 983686 |
CO Springs Fire | Original | A | 8/2/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 983313 |
Electrical | Original | D | 7/31/2017 | SHELBY | SHELBY | 1. Show supply conductors and over current for relocated and new CT machines (One line shows a C/T in room 1318 only; scope of work for this project is rooms 1203 and 1207 ). 2. Include C/T loads in load summaries. 3. For panels to be metered ( EEQBSDP-1--EEQBSDP-3---NBMSB-1---NBMSB-3 ) identify responsible party in the event metering should necessitate upgrade or replacement. 4. Provide load calculation for NPSDP-1. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 982408 |
CO Springs DRE | Original | N | 7/25/2017 | GSANDERS | GSANDERS | all work interior (see full review) | | CO Springs DRE | 980651 |
Zoning/Planning | Original | / | 7/25/2017 | GSANDERS | GSANDERS | In Current Review by GSANDERS | | Zoning/Planning | 980616 |
Water Division | Original | N | 7/24/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. JPN | jnoble | Water Division | 980484 |
Waste Water Div | Original | N | 7/24/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. JPN | jnoble | Waste Water Div | 980483 |
Plumbing | Original | D | 7/24/2017 | TCRIPPEN | TCRIPPEN | Unable to read water loss calculations (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 980403 |
Electronic Plan | Original | / | 7/24/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 980324 |
Construction | Original | A | 7/24/2017 | BPHILLIPS | BPHILLIPS | | | Construction | 980313 |
Electronic Plan | Original | / | 7/20/2017 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 979766 |
Enumeration | Original | A | 7/18/2017 | BRENT | BRENT | | | Enumeration | 978913 |
Floodplain | Original | N | 6/16/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 970097 |
Floodplain | Original | N | 6/16/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 970098 |