Canceled Plans | Original | / | 2/19/2019 | | MATTHEWM | Location = Canceled Plans by MATTHEWM | | Canceled Plans | 1160466 |
CO Springs Fire | Original | A | 10/25/2017 | CSFIRE | CSFIRE | Approved per Engineer Taylor's. RTP | rpeterson | CO Springs Fire | 1006973 |
Electrical | Original | A | 10/23/2017 | BERTHA | BERTHA | | | Electrical | 1006193 |
Resubmittal 3 | Original | / | 10/17/2017 | SHELLEY | SHELLEY | Resubmittal #3 | | Resubmittal 3 | 1004661 |
Hazmat | Original | A | 10/13/2017 | CSFIRE | CSFIRE | Per comment response, contractor has requested a deferred submittal on the CO2 system. See hazmat comment responses submitted with plans. RBD plans shall currently be approved; however, Certificate of Occupancy shall not be granted before CO2 system/Hazmat approval. (see full review) | smanning | Hazmat | 1003896 |
CO Springs Fire | Original | A | 10/12/2017 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1003329 |
Electrical | Original | D | 10/4/2017 | BERTHA | BERTHA | Spoke with Chris Anderson at G2 Consulting Engineers. He will provide a "load summary" indicating a reduction in load.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1001299 |
Construction | Original | A | 10/3/2017 | SHELLEY | SHELLEY | | | Construction | 1000712 |
Resubmittal 2 | Original | / | 10/3/2017 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1000677 |
Hazmat | Original | D | 8/10/2017 | CSFIRE | CSFIRE | Hazmat still disapproved. It appears no additional information has been provided to address the previous comments. (see full review) | smanning | Hazmat | 985546 |
Electrical | Original | D | 8/8/2017 | SHELBY | SHELBY | Please provide load summary for building service. Call for consultation 719 327 2974 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 984619 |
CO Springs Fire | Original | A | 8/7/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 984165 |
Enumeration | Original | A | 8/2/2017 | BRENT | BRENT | | | Enumeration | 983417 |
Enumeration | Original | D | 8/2/2017 | BRENT | BRENT | see comments from 06/19/17 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 983395 |
Resubmittal 1 | Original | / | 8/2/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 983240 |
Hazmat | Original | D | 7/3/2017 | CSFIRE | CSFIRE | Plans disapproved. Please read full review comments. (see full review) | smanning | Hazmat | 974950 |
CO Springs Fire | Original | D | 6/30/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 974499 |
CO Springs DRE | Original | N | 6/27/2017 | SDALSING | SDALSING | Interior remodel. No exterior work to be done. (see full review) | | CO Springs DRE | 973256 |
Zoning/Planning | Original | / | 6/27/2017 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 972906 |
Electrical | Original | D | 6/26/2017 | SHELBY | SHELBY | 1. Please provide complete electrical ( panel schedules, panel and circuit on floor plan, one line etc---See http://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf ). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 972897 |
Mechanical | Original | N | 6/26/2017 | DALEH | DALEH | | | Mechanical | 972509 |
Water Division | Original | A | 6/23/2017 | CSUREVIEW | CSUREVIEW | No concerns. RDS | cquinn_ds | Water Division | 972285 |
Waste Water Div | Original | A | 6/23/2017 | CSUREVIEW | CSUREVIEW | No concerns. RDS | cquinn_ds | Waste Water Div | 972284 |
Plumbing | Original | A | 6/23/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 972166 |
Electronic Plan | Original | / | 6/23/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 972154 |
Construction | Original | A | 6/23/2017 | SHELLEY | SHELLEY | | | Construction | 972116 |
Electronic Plan | Original | / | 6/23/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 972018 |
Enumeration | Original | D | 6/19/2017 | BRENT | BRENT | Tax schedule number is missing from the code study form. Legal description shown on code study form is incorrect. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 970498 |
Floodplain | Original | N | 6/19/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 970484 |
Floodplain | Original | N | 6/19/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 970485 |