Out to Review | 4/27/2018 | / | 5/8/2018 | BECKYA | BECKYA | Dan 480-709-8289 | | Out to Review | 1066193 |
Plumbing | 4/27/2018 | / | 5/8/2018 | | BECKYA | Location = Plumbing by BECKYA | | Plumbing | 1066192 |
Plumbing | 4/27/2018 | A | 5/8/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1066169 |
Out to Review | 4/27/2018 | / | 5/4/2018 | NELIDA | NELIDA | Dan 480-709-8289 | | Out to Review | 1065250 |
Finished Bin | 4/27/2018 | / | 5/4/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1065190 |
Plan Coordinator | 4/27/2018 | / | 5/4/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1065173 |
Plumbing | 4/27/2018 | D | 5/4/2018 | TCRIPPEN | TCRIPPEN | missing comment letter for plumbing or narrative on plan set for plumbing. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1065172 |
Plumbing | 4/27/2018 | / | 5/3/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1064714 |
Plan Coordinator | 4/27/2018 | / | 5/3/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1064627 |
Mechanical | 4/27/2018 | A | 5/3/2018 | JUSTINC | JUSTINC | Revised gas system | | Mechanical | 1064625 |
Mechanical | 4/27/2018 | / | 5/2/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1063856 |
Mechanical | 4/27/2018 | / | 5/1/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1063610 |
Plan Coordinator | 4/27/2018 | / | 5/1/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1063585 |
Electrical | 4/27/2018 | A | 5/1/2018 | BERTHA | BERTHA | | | Electrical | 1063584 |
Electrical | 4/27/2018 | / | 5/1/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1063213 |
Electrical | 4/27/2018 | / | 4/27/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1062663 |
Plan Coordinator | 4/27/2018 | / | 4/27/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1062646 |
Construction | 4/27/2018 | A | 4/27/2018 | MICHAELA | MICHAELA | Move door - add platform on roof | | Construction | 1062645 |
Construction | 4/27/2018 | / | 4/27/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1062640 |
Construction | 4/27/2018 | / | 4/27/2018 | | JANE | Location = Construction by JANE | | Construction | 1062545 |
CO Springs Fire | Original | A | 10/31/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1008532 |
Plumbing | Original | A | 10/26/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1007333 |
Electronic Plan | Original | / | 10/26/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1007309 |
Electrical | Original | A | 10/25/2017 | SHELBY | SHELBY | | | Electrical | 1007003 |
Mechanical | Original | A | 10/25/2017 | JUSTINC | JUSTINC | | | Mechanical | 1006937 |
Construction | Original | A | 10/25/2017 | MICHAELA | MICHAELA | | | Construction | 1006810 |
Resubmittal 3 | Original | / | 10/25/2017 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1006789 |
Hazmat | Original | N | 10/18/2017 | CSFIRE | CSFIRE | Hazmat N/A. CO2 amounts below permit quantities. No inspection required. (see full review) | smanning | Hazmat | 1005416 |
Plumbing | Original | D | 10/16/2017 | TCRIPPEN | TCRIPPEN | Firer has disapproved plumbing sheet , need Fire approved first (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1004348 |
Electronic Plan | Original | / | 10/16/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1004346 |
CO Springs Fire | Original | D | 10/14/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1004162 |
Water Division | Original | A | 10/12/2017 | CSUREVIEW | CSUREVIEW | Backflow device OK per Holly Link. mjg | mgackle | Water Division | 1003421 |
Mechanical | Original | D | 10/12/2017 | JUSTINC | JUSTINC | Sheet M5 has been removed from plan set? Please re-upload sheet M5 for details associated with bagel oven. Also need to provide oven specifications on plan sheet See previous approvals for same type of restaurant Permit# I01374 also Permit # H02927
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1003388 |
Electronic Plan | Original | / | 10/12/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1003364 |
Electrical | Original | A | 10/11/2017 | SHELBY | SHELBY | | | Electrical | 1003261 |
Construction | Original | A | 10/11/2017 | MICHAELA | MICHAELA | | | Construction | 1002958 |
Resubmittal 2 | Original | / | 10/11/2017 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1002882 |
Health Dept. | Original | A | 8/26/2017 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Jodi Zimmerman 719-433-3685 | Jzimmerman | Health Dept. | 990474 |
Health Dept. | Original | / | 8/26/2017 | HEALTHDEPT | HEALTHDEPT | | Jzimmerman | Health Dept. | 990473 |
Health Dept. | Original | D | 8/25/2017 | HEALTHDEPT | HEALTHDEPT | Plan review required. Please contact the health department at (719) 578-3199 option 3. RNielsen 719-575-8965 | rnielsen | Health Dept. | 990234 |
Electrical | Original | D | 8/24/2017 | SHELBY | SHELBY | Provide complete electrical see http://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf (one line is incomplete, missing building load calculation etc). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 989765 |
Mechanical | Original | D | 8/22/2017 | JUSTINC | JUSTINC | Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection. Provide refrig. calculations for all walk-in coolers and freezers per 09' IMC 1103.1 Indicate if within allowable limits. If over allowable limits indicate on plan how protecting. Relocate all gas associated drawings, notes, details ,etc.. to (M) sheet for review Provide kitchen air balance schedule
Review incomplete (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 989107 |
Hazmat | Original | D | 8/22/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 988817 |
CO Springs Fire | Original | D | 8/22/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 988815 |
Water Division | Original | D | 8/21/2017 | CSUREVIEW | CSUREVIEW | Requires submittal of a Backflow Assembly Plan Review Form to determine if the service backflow prevention meets Standards. Form can be found at: https://www.csu.org/CSUDocuments/backflowdomesticform.pdf. Contact Chelsa Shull at 719-668-8755 or Holly Link at 719-668-4733 with any questions. RDS | rsolberg | Water Division | 988619 |
Waste Water Div | Original | A | 8/21/2017 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Waste Water Div | 988618 |
CO Springs DRE | Original | A | 8/17/2017 | MBINGMAN | MBINGMAN | Shall comply with approved development plan. Signage not approved with this review INCLUDING TEMPORARY BANNERS. Interior Finish. Use consistent with Development Plan. (see full review) | | CO Springs DRE | 987611 |
Plumbing | Original | D | 8/17/2017 | TCRIPPEN | TCRIPPEN | Gas piping and related items to be on the M-pages per our web site, separate drain lines required from each bowl. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 987484 |
Zoning/Planning | Original | / | 8/17/2017 | MBINGMAN | MBINGMAN | In Current Review by MBINGMAN | | Zoning/Planning | 987446 |
Construction | Original | A | 8/16/2017 | MICHAELA | MICHAELA | | | Construction | 987058 |
Electronic Plan | Original | / | 8/16/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 987009 |
Enumeration | Original | A | 8/16/2017 | BRENT | BRENT | Core and shell has been permitted. Final plat has been recorded. Tax schedule number and legal description shown on code study form to change when assessor records are updated. | | Enumeration | 987008 |
Resubmittal 1 | Original | / | 8/16/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 986990 |
Plan Coordinator | Original | D | 7/19/2017 | SHELLEY | SHELLEY | Disapprove all remaining departments to allow plan to be resubmitted - INTERIOR FINISH PLANS CANNOT BE SUBMITTED UNTIL THE SHELL PERMIT IS OBTAIN. RESUBMIT AFTER SHELL IS PERMITTED. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 979056 |
Electronic Plan | Original | / | 7/19/2017 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 979052 |
Floodplain | Original | N | 7/13/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 977503 |
Floodplain | Original | N | 7/13/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 977504 |