Plumbing | Splice 4/25/18 | A | 4/25/2018 | JOEL | JOEL | | | Plumbing | 1061443 |
Mechanical | 3/23/18` | A | 3/29/2018 | TCRIPPEN | TCRIPPEN | okay reinstall gas pipe removed by mistake | | Mechanical | 1051899 |
Resubmittal 1 | 3/23/18` | / | 3/29/2018 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1051867 |
Mechanical | 3/23/18` | D | 3/23/2018 | TCRIPPEN | TCRIPPEN | need mor information on gas piping you have changed sizes to smaller pipe (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1049900 |
Out to Review | 3/23/18` | / | 3/23/2018 | NELIDA | NELIDA | Rick 303-770-8884 | | Out to Review | 1049890 |
Out to Review | 3/1/2018 | / | 3/2/2018 | SCANNING | SCANNING | | | Out to Review | 1042577 |
Construction | 3/1/2018 | A | 3/1/2018 | MICHAELA | MICHAELA | Revise assembly to include metal roof truss | | Construction | 1042196 |
Construction | 3/1/2018 | / | 3/1/2018 | | JANE | Location = Construction by JANE | | Construction | 1042174 |
Construction | 2/15/2018 | A | 2/15/2018 | LBENNETT | LBENNETT | Added ramp and details; minor floor plan revisions; labelled rated wall | | Construction | 1038326 |
Electrical | 2/15/2018 | A | 2/15/2018 | BERTHA | BERTHA | See summary of changes. | | Electrical | 1038102 |
Mechanical | 2/15/2018 | A | 2/15/2018 | JUSTINC | JUSTINC | Revised exhaust to remove EF-9 | | Mechanical | 1038072 |
Out to Review | 2/15/2018 | / | 2/15/2018 | LBENNETT | LBENNETT | walking | | Out to Review | 1038050 |
Construction | 2/15/2018 | A | 2/15/2018 | LBENNETT | LBENNETT | Added ramp and details; minor floor plan revisions; labelled rated wall | | Construction | 1038049 |
Plumbing | 2/15/2018 | A | 2/15/2018 | TCRIPPEN | TCRIPPEN | New splice changed over head drains to underground, added 2 hose bibs, updated EWC- 1 & WB- 1 | | Plumbing | 1038024 |
Construction | 1/30/18 | A | 2/6/2018 | MICHAELA | MICHAELA | Revised exterior framed walls to CMU | | Construction | 1035009 |
Resubmittal 1 | 1/30/18 | / | 2/5/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1034855 |
Out to Review | 1/30/18 | / | 2/5/2018 | NELIDA | NELIDA | Kyle 720-323-1493 | | Out to Review | 1034848 |
Finished Bin | 1/30/18 | / | 1/30/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1033107 |
Plan Coordinator | 1/30/18 | / | 1/30/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1033076 |
Mechanical | 1/30/18 | A | 1/30/2018 | JUSTINC | JUSTINC | Revised gas,bathroom location, RTU schedule | | Mechanical | 1033074 |
Mechanical | 1/30/18 | / | 1/30/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1033038 |
Mechanical | 1/30/18 | / | 1/30/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1032967 |
Plan Coordinator | 1/30/18 | / | 1/30/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1032955 |
Construction | 1/30/18 | D | 1/30/2018 | MICHAELA | MICHAELA | III-B construction requires 2-hr exterior bearing walls - provide listing for wall types W-1, W-2 and verify infills are rated or non-bearing Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1032953 |
Construction | 1/30/18 | / | 1/30/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1032911 |
Construction | 1/30/18 | / | 1/30/2018 | MATTHEW | MATTHEW | In Current Review by MATTHEW | | Construction | 1032910 |
Construction | 1/30/18 | / | 1/30/2018 | | NELIDA | Location = Construction by NELIDA | | Construction | 1032875 |
Plumbing | 1/30/18 | A | 1/30/2018 | TCRIPPEN | TCRIPPEN | new splice pages relocated bathroom to locker room added washer box, increased roof drain line to 12" updated fixture schedule, showing new vent locations for bathroom and washer box. | | Plumbing | 1032853 |
Electrical | 1/30/18 | A | 1/30/2018 | BERTHA | BERTHA | Revised lighting E101. Revised power E201 – background changes, deleted receptacles. Revised Mechanical Equipment Schedule E501. Revised panels E502. | | Electrical | 1032831 |
Out to Review | 1/30/18 | / | 1/30/2018 | NELIDA | NELIDA | Rick Sander walking 303-770-8884 | | Out to Review | 1032796 |
Hazmat | Original | A | 11/3/2017 | CSFIRE | CSFIRE | Hazmat approved. Please read approval comments. As per second review comment, additional fees applied of $630 + 50% ($315) = 945. (see full review) | smanning | Hazmat | 1009720 |
Resubmittal 5 | Original | / | 11/2/2017 | BECKYA | BECKYA | Resubmittal #5 | | Resubmittal 5 | 1009450 |
Resubmittal 4 | Original | / | 11/2/2017 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1009448 |
Hazmat | Original | D | 10/31/2017 | CSFIRE | CSFIRE | Plans disapproved. Previous review comments not addressed; please provide comment response letter addressing hazmat comments. (see full review) | smanning | Hazmat | 1008414 |
CO Springs Fire | Original | A | 10/25/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1006841 |
Mechanical | Original | A | 10/20/2017 | JUSTINC | JUSTINC | | | Mechanical | 1005760 |
Resubmittal 3 | Original | / | 10/18/2017 | DANM | DANM | Resubmittal #3 | | Resubmittal 3 | 1005175 |
CO Springs DRE | Original | A | 10/17/2017 | MMCCONNELL | MMCCONNELL | PD DP 72-92-A6MJ17 (see full review) | | CO Springs DRE | 1004944 |
Zoning/Planning | Original | / | 10/12/2017 | MMCCONNELL | MMCCONNELL | In Current Review by MMCCONNELL | | Zoning/Planning | 1003726 |
Hazmat | Original | D | 10/12/2017 | CSFIRE | CSFIRE | Plans disapproved. Please read disapproved comments. (see full review) | smanning | Hazmat | 1003407 |
CO Springs Fire | Original | D | 10/11/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1003287 |
Water Division | Original | A | 10/10/2017 | CSUREVIEW | CSUREVIEW | Items have been addressed. mjg | mgackle | Water Division | 1002512 |
Waste Water Div | Original | A | 10/10/2017 | CSUREVIEW | CSUREVIEW | Items have been addressed. mjg | mgackle | Waste Water Div | 1002511 |
Mechanical | Original | D | 10/10/2017 | JUSTINC | JUSTINC | Ducts indicated as penetrating rated fire barrier without protection per the legend indicated on sheet M800. Indicate damper brand and model # for each penetration. Indicate all damper locations on plan with legend. TYP.
Sheet legends do not match legend schedule indicated on sheet M800? (TYP.)
Clarify what LV-1 is interlocked with
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1002380 |
CO Springs DRE | Original | D | 10/6/2017 | GSANDERS | GSANDERS | Include stamped approved minor amendment plans from City Planning (see full review) | | CO Springs DRE | 1001897 |
Construction | Original | A | 10/6/2017 | MICHAELA | MICHAELA | | | Construction | 1001857 |
Resubmittal 2 | Original | / | 10/5/2017 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1001654 |
Hazmat | Original | D | 9/14/2017 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 995357 |
CO Springs Fire | Original | D | 9/13/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 995180 |
Electrical | Original | A | 9/11/2017 | SHELBY | SHELBY | | | Electrical | 994296 |
CO Springs DRE | Original | D | 9/11/2017 | GSANDERS | GSANDERS | Include approved minor amendment (see full review) | | CO Springs DRE | 994248 |
Zoning/Planning | Original | / | 9/7/2017 | GSANDERS | GSANDERS | In Current Review by GSANDERS | | Zoning/Planning | 993370 |
Plumbing | Original | A | 9/7/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 993360 |
Mechanical | Original | D | 9/7/2017 | JUSTINC | JUSTINC | Per the 1st review comments will need to provide a complete pool boiler schedule to review. The schedule is to indicate BTU, PSI, HP Model and brand, Type of boiler (steam) or (hydronic). etc..
Wall rating review is still pending mechanical review pending construction reviewer comments
MECHANICAL REVIEW INCOMPLETE (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 993350 |
Electronic Plan | Original | / | 9/7/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 993343 |
Water Division | Original | D | 9/6/2017 | CSUREVIEW | CSUREVIEW | The following comments have not been addressed: "Approved Development Plan and CSU Construction Plans must be attached to the permit set. Contact Utilities Development Services at 719-668-8111 with any questions." JPN | jnoble | Water Division | 993300 |
Waste Water Div | Original | D | 9/6/2017 | CSUREVIEW | CSUREVIEW | The following comments have not been addressed: "Approved Development Plan and CSU Construction Plans must be attached to the permit set. Contact Utilities Development Services at 719-668-8111 with any questions." JPN | jnoble | Waste Water Div | 993299 |
Construction | Original | D | 9/6/2017 | MICHAELA | MICHAELA | If the A-3 is not separated from the E then you must combine the square footage and use worse case A-3 for the sum of the ratios calculations Add the adjacent M occupancy to the calculation. The entire building must be included Why does the wall hatch separating the M occupancy end where it does? If the pool equipment room is incidental use add it to the code study form and add a note on the plan that the door and walls must resist the passage of smoke per 508.2.5.2 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 993209 |
Electronic Plan | Original | / | 9/6/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 993144 |
Resubmittal 1 | Original | / | 9/6/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 993138 |
Hazmat | Original | D | 8/9/2017 | CSFIRE | CSFIRE | | dwithee | Hazmat | 985125 |
CO Springs Fire | Original | D | 8/9/2017 | CSFIRE | CSFIRE | reference review report online for comments (see full review) | csfdit | CO Springs Fire | 985124 |
Mechanical | Original | D | 8/5/2017 | JUSTINC | JUSTINC | Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection. Verify with equipment schedules. "GAS LOAD SUMMARY" Current code adopted by PPRBD is 09' IMC. Verify values indicated with adopted code. Revise plan to reflect correct code year. (TYP.) Add note: Gas is an engineered system. How providing exhaust per 09' IMC 403.3 (g) Education "Art classroom." Provide pool equipment schedule. Provide on plan location of equipment, venting, gas. Gas fired water heaters indicated on (P) sheets. Indicate locations of equipment,venting, gas layout, how providing combustion air. Wall ratings have not been reviewed.Pending construction reviewer comments.
REVIEW INCOMPLETE
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 984131 |
Electrical | Original | D | 8/2/2017 | SHELBY | SHELBY | 1. Show compliance with 240.87 NEC for main disconnect. 2. Panel MSB requires a main disconnect ( comply 240.87 NEC). 3. Indicate height of pool area light fixtures above maximum pool water level. 4. Indicate horizontal distance of pool area light fixtures from inside wall of the pool. 5. MSB schedule shows a breaker feeding LP1 VS one line showing panel RCP ( review SCA and AIC).
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 983276 |
CO Springs DRE | Original | D | 8/1/2017 | GSANDERS | GSANDERS | please include approved amendment plans or request a pre-application meeting to begin the amendment process. https://coloradosprings.gov/planning/webform/pre-application-meeting-request (see full review) | | CO Springs DRE | 982911 |
Water Division | Original | D | 8/1/2017 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU Construction Plans must be attached to the permit set. Contact Utilities Development Services at 719-668-8111 with any questions. JPN | jnoble | Water Division | 982812 |
Waste Water Div | Original | D | 8/1/2017 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU Construction Plans must be attached to the permit set. Contact Utilities Development Services at 719-668-8111 with any questions. JPN | jnoble | Waste Water Div | 982810 |
Plumbing | Original | D | 7/31/2017 | TCRIPPEN | TCRIPPEN | Trench drain for pool and spa shall not tie directly into the sanitary waste it must be an indirect through a floor sink or sump. See 802.1.4 of the 2015 IPC. Can drain to basin in mechanical room. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 982542 |
Electronic Plan | Original | / | 7/31/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 982434 |
Construction | Original | D | 7/31/2017 | MICHAELA | MICHAELA | E occupancy must be separated from B AND A-3 If pool equipment exceeds limits of table 508.2.5 the room will need to be 1-hr. rated. Current plumbing code is 2015 IBC Provide a listed "top of wall" detail for rated walls
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 982428 |
Electronic Plan | Original | / | 7/27/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 981555 |
Enumeration | Original | A | 7/25/2017 | BRENT | BRENT | | | Enumeration | 980629 |
Floodplain | Original | N | 7/18/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 978612 |