Construction | Splice 3/7/18 | A | 3/7/2018 | SHELLEY | SHELLEY | revised ramp | | Construction | 1044389 |
Out to Review | Splice 3/7/18 | / | 3/7/2018 | GITA | GITA | | | Out to Review | 1044313 |
CO Springs DRE | Original | A | 1/24/2018 | SDALSING | SDALSING | Use allowed - parking calculation is met. All other development standards are met. Signage not approved with this permit (see full review) | | CO Springs DRE | 1031184 |
CO Springs Fire | Original | A | 1/19/2018 | CSFIRE | CSFIRE | reference review report online for important information: BE ADVISED: 2009 IFC 903.2.1 requires the basement and 1st floor to be fire sprinkled: "the automatic fire sprinkler system shall be provided throughout the floor area where the Group ... A3 occupancy is located, and in all floors from the Group A occupancy to, and including, the nearest level of exit discharge serving the Group A occupancy." (see full review) | csfdit | CO Springs Fire | 1030433 |
Zoning/Planning | Original | / | 1/19/2018 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1029999 |
Construction | Original | A | 1/18/2018 | SHELLEY | SHELLEY | | | Construction | 1029872 |
Enumeration | Original | A | 1/18/2018 | BRENT | BRENT | | | Enumeration | 1029506 |
Resubmittal 3 | Original | / | 1/16/2018 | SHELLEY | SHELLEY | Resubmittal #3 | | Resubmittal 3 | 1028883 |
CO Springs Fire | Original | D | 12/29/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1024822 |
CO Springs DRE | Original | A | 12/20/2017 | SDALSING | SDALSING | Change of Occ - parking calculations met - use allowed (see full review) | | CO Springs DRE | 1022844 |
Electrical | Original | A | 12/18/2017 | SHELBY | SHELBY | | | Electrical | 1022364 |
Zoning/Planning | Original | / | 12/14/2017 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1021490 |
Construction | Original | D | 12/14/2017 | SHELLEY | SHELLEY | Clarify rating at jog of fire wall - see A1.0; still need verification of entire lower roof meeting 706.6.1; fire wall continuity not being met - see A1.2 for solution; (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1021305 |
Enumeration | Original | D | 12/13/2017 | BRENT | BRENT | see comments from 8/2/17 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1020928 |
Resubmittal 2 | Original | / | 12/13/2017 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1020880 |
CO Springs Fire | Original | D | 11/3/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1010115 |
CO Springs DRE | Original | D | 11/2/2017 | SDALSING | SDALSING | Please update parking calculation on CPC CU 11-00033. Please see email for further information (see full review) | | CO Springs DRE | 1009654 |
Electrical | Original | D | 11/2/2017 | SHELBY | SHELBY | Include all electrical components listed in 1109.12 2009 IBC in letter of compliance. Indicate heights to top of control, operating mechanism or hardware being referenced. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1009615 |
Plumbing | Original | N | 11/2/2017 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit | | Plumbing | 1009280 |
Electronic Plan | Original | / | 11/2/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1009266 |
Water Division | Original | N | 11/1/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. RDS | rsolberg | Water Division | 1009005 |
Waste Water Div | Original | N | 11/1/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. RDS | rsolberg | Waste Water Div | 1009004 |
Mechanical | Original | N | 10/31/2017 | JUSTINC | JUSTINC | Mechanical shown for reference of ventilation with new occupancy. | | Mechanical | 1008563 |
Zoning/Planning | Original | / | 10/31/2017 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1008336 |
Construction | Original | D | 10/31/2017 | SHELLEY | SHELLEY | Address entire lower roof ceiling at fire wall location; verify locations of fire wall(s); show horizontal continuity and termination; double fire walls are required to have opening protection in both walls; provide detail for compliant horizontal continuity; clarify reason for rated ceiling at beams; beam cannot be between fire walls - all supporting construction must be on the interior side of the wall for the building it is supporting; Alternate materials and methods request required to use the 2015 IBC which references NFPA 221; Clarify fire barrier where there isn't one; See plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1008332 |
Enumeration | Original | D | 10/30/2017 | BRENT | BRENT | See comments from 08/02/17. Tax schedule number shown on code study form is incorrect. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1007987 |
Resubmittal 1 | Original | / | 10/27/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1007827 |
Hazmat | Original | N | 8/14/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 986343 |
CO Springs Fire | Original | D | 8/14/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 986342 |
CO Springs DRE | Original | D | 8/14/2017 | SDALSING | SDALSING | Please calculate number of seats. Susanna Dalsing 719-385-5080 (see full review) | | CO Springs DRE | 986252 |
Zoning/Planning | Original | / | 8/9/2017 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 985275 |
Water Division | Original | D | 8/9/2017 | CSUREVIEW | CSUREVIEW | Pending submittal of Plumbing Plans. Requires submittal of a Backflow Assembly Plan Review Form to determine if the service backflow prevention meets Standards. Form can be found at: https://www.csu.org/CSUDocuments/backflowdomesticform.pdf. Contact Chelsa Shull at 719-668-8755 or Holly Link at 719-668-4733 with any questions. JPN | jnoble | Water Division | 985204 |
Waste Water Div | Original | D | 8/9/2017 | CSUREVIEW | CSUREVIEW | Pending submittal of Plumbing Plans. JPN | jnoble | Waste Water Div | 985201 |
Plumbing | Original | D | 8/8/2017 | TCRIPPEN | TCRIPPEN | your occupant load of 344 will require 4 women`s and 4 men`s toilets see calculations on plumbing page increased occupant load per construction (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 984893 |
Electronic Plan | Original | / | 8/8/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 984858 |
Mechanical | Original | D | 8/8/2017 | JUSTINC | JUSTINC | When intent is to change occupancy, a full set of mechanical plans are required to verify code compliance with new occupancy. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 984828 |
Electronic Plan | Original | / | 8/8/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 984826 |
Electrical | Original | D | 8/8/2017 | BERTHA | BERTHA | Provide electrical plans - Specify heights of all existing and new electrical devices. Indicate compliance with 210.8 NEC and ANSI 117.1.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 984796 |
Electronic Plan | Original | / | 8/8/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 984792 |
Construction | Original | D | 8/8/2017 | SHELLEY | SHELLEY | Revise code study form as indicated; provide complete allowable area calculations to include sum of the ratios; provide listed assembly and continuity details for fire barrier; verify opening protection at fire barrier and atrium; revise occupant loads for gross OLF; provide plumbing fixture count to ensure the proper amount of fixtures are provided; verify F1 vs. S1 occupancy; see plans; for all comments. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 984773 |
Electronic Plan | Original | / | 8/8/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 984548 |
Enumeration | Original | D | 8/2/2017 | BRENT | BRENT | This plan was submitted as Suite 100. Suite 100 would be a ground level floor. The plan pages call the suite as "basement". This suite should use 10 as the suite number. plan pages and code study form should be updated to show this suite number. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 983420 |
Floodplain | Original | N | 7/27/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 981524 |
Floodplain | Original | N | 7/27/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 981525 |