Construction | Splice 10/07/19 | A | 10/7/2019 | MICHAELA | MICHAELA | Modify structure. | | Construction | 1243077 |
Construction | Original | A | 1/18/2019 | MICHAELA | MICHAELA | | | Construction | 1151124 |
Resubmittal 5 | Original | / | 1/18/2019 | BECKYA | BECKYA | Resubmittal #5 | | Resubmittal 5 | 1150937 |
Mechanical | Original | A | 1/7/2019 | TCRIPPEN | TCRIPPEN | okay using a boiler | | Mechanical | 1147500 |
Construction | Original | D | 1/7/2019 | MICHAELA | MICHAELA | This submittal is missing the engineering pages for the SIP panels. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1147199 |
Resubmittal 4 | Original | / | 1/4/2019 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1147142 |
Mechanical | Original | D | 1/4/2019 | TCRIPPEN | TCRIPPEN | IECC reads R 54 for ceiling your calc, is at 49 need to redo, all so need an approved IECC first. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1146799 |
County Zoning | Original | A | 1/4/2019 | DSDRANGEL | DSDRANGEL | DRIVEWAY WAIVED WITH BFF | | County Zoning | 1146792 |
Construction | Original | D | 1/3/2019 | MICHAELA | MICHAELA | Missing structural pages. Current adopted code for this structure is the 2015 IRC. Please revise SIP panel engineering pages. Regional Building Department has not adopted chapter 1 of the IBC. Refer to the 2017 Regional Building Code. https://www.pprbd.org/Information/CodeChanges (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1146733 |
Resubmittal 3 | Original | / | 1/3/2019 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1146515 |
Mechanical | Original | D | 12/21/2018 | TCRIPPEN | TCRIPPEN | Need an approved IECC first see constructions notes. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1144226 |
Electronic Plan | Original | / | 12/21/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1144135 |
County Zoning | Original | D | 12/21/2018 | DSDRANGEL | DSDRANGEL | SUBMIT SITE PLAN WITH HOUSE | | County Zoning | 1144050 |
Construction | Original | D | 12/20/2018 | MICHAELA | MICHAELA | Provide ICC-ES report for SIP panels. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1143974 |
Electronic Plan | Original | / | 12/20/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1143962 |
Enumeration | Original | N | 12/20/2018 | AMY | AMY | REBUILD | | Enumeration | 1143944 |
Electronic Plan | Original | / | 12/20/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1143941 |
Resubmittal 2 | Original | / | 12/20/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1143839 |
Mechanical | Original | D | 12/12/2018 | TCRIPPEN | TCRIPPEN | page 2 of the equipment certificate needs to be completed (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1140486 |
Electronic Plan | Original | / | 12/12/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1140485 |
County Zoning | Original | D | 12/11/2018 | DSDRANGEL | DSDRANGEL | SHOW LEGAL DESCRIPTION, TAX SCHEDULE NUMBER, DRIVEWAY ACCESS TO HOME AND NORTH ARROW ON SITE PLAN | | County Zoning | 1140263 |
Construction | Original | D | 12/11/2018 | MICHAELA | MICHAELA | Structural pages have not been resubmitted (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1140096 |
Enumeration | Original | D | 12/11/2018 | AMY | AMY | same comments from 10-15-18 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1140005 |
Electronic Plan | Original | / | 12/11/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1140004 |
Resubmittal 1 | Original | / | 12/10/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1139892 |
Mechanical | Original | D | 10/25/2018 | TCRIPPEN | TCRIPPEN | The 2017 code requires whole house ventilation how are you complying house square footage requires 60 CFM continuous provide the correct equipment certificate, Your U and R values no match to the IECC, You have 2 different IECC ?, This must be in the IECC drop down box for review and approval this is no match to the IECC in the IECC drop down box ?, you do not have any ducts not use the duct design drop down box.your A page must show the boiler and floor drain is required, . (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1123690 |
Electronic Plan | Original | / | 10/25/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1123689 |
County Zoning | Original | D | 10/17/2018 | DSDRANGEL | DSDRANGEL | SHOW LEGAL DESCRIPTION, TAX SCHEDULE NUMBER AND NORTH ARROW ON SITE PLAN | | County Zoning | 1120987 |
Zoning/Planning | Original | / | 10/17/2018 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1120986 |
Construction | Original | D | 10/17/2018 | MICHAELA | MICHAELA | Show mechanical equipment and indicate 18" platform required at garage. Label all hangers indicate ledger connection requirements. Indicate how posts connect to beams Provide ICC-ES Report for SIP panels. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1120957 |
Electronic Plan | Original | / | 10/17/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1120876 |
Enumeration | Original | D | 10/15/2018 | AMY | AMY | Legal Description, Tax Schedule number, North arrow are all required to be on the plot plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1119853 |
Floodplain | Original | N | 10/10/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5209005001) | | Floodplain | 1118462 |