Construction | Splice 07/19/22 | A | 8/12/2022 | BPHILLIPS | BPHILLIPS | Provided engineering for modified framing for dumbwaiter. | | Construction | 1727326 |
Construction | Splice 07/19/22 | D | 7/19/2022 | CHRISTAW | CHRISTAW | Registrant must be the same designer (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1715781 |
Out to Review | Splice 07/19/22 | / | 7/19/2022 | AMYP | AMYP | fred 719-201-3865 | | Out to Review | 1715333 |
Mechanical | Splice 09/15/20 | A | 9/16/2020 | JUSTINC | JUSTINC | Revised manual J,S,D for revised IECC | | Mechanical | 1383619 |
Electronic Plan | Splice 09/15/20 | / | 9/16/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1383552 |
Construction | Splice 09/15/20 | A | 9/16/2020 | DANM | DANM | Revised IECC from prescriptive method to perforrmace with supporting documentation | | Construction | 1383437 |
Electronic Plan | Splice 09/15/20 | / | 9/15/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1383318 |
Out to Review | Original | / | 9/6/2019 | NELIDA | NELIDA | Bridger 720-227-7944 | | Out to Review | 1232255 |
Scanned/Finished Bin | Original | / | 8/21/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1226584 |
To Be Scanned Bin | Original | / | 8/20/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1226098 |
CO Springs DRE | Original | A | 8/20/2019 | KHYLLESTED | KHYLLESTED | New SFA approved per AR R 19-00049. EDR okay with plans, written permission is required to grade on adjacent private property. (see full review) | | CO Springs DRE | 1226077 |
Zoning/Planning | Original | / | 8/20/2019 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1226038 |
Finished Bin | Original | / | 7/12/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1212104 |
Plan Coordinator | Original | / | 7/11/2019 | | KHYLLESTED | Location = Plan Coordinator by KHYLLESTED | | Plan Coordinator | 1212076 |
CO Springs DRE | Original | D | 7/11/2019 | KHYLLESTED | KHYLLESTED | 1. A geohazard disclosure statement is required on the site plan. State the site specific geohazards along with the proposed mitigation. 2. Site specific soils and foundation reports are required for ALL lots. Reports must include mitigation recommendations for expansive soils. LOTS 4 &5 must discuss mitigation of any potential impacts on the stability of the retaining walls and address Entech's recommendations. 3. Global stability of the retaining walls must be evaluated by PE. Must include estimated impacts to the retaining walls from roads, driveways, and structures. Follow Entech's recommendations on surface and subsurface drainage, fill placement, must be part of construction plans.
Please contact Katelyn with questions at katelyn.hyllested@coloradosprings.gov (see full review) | | CO Springs DRE | 1212075 |
CO Springs Fire | Original | A | 6/19/2019 | CSFIRE | CSFIRE | | wtaylor | CO Springs Fire | 1204305 |
Out to Review | Original | / | 6/18/2019 | RITA | RITA | Bridger 720-227-7944 | | Out to Review | 1203871 |
Finished Bin | Original | / | 5/23/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1194311 |
CO Springs Fire | Original | D | 5/23/2019 | CSFIRE | CSFIRE | Previous review comments not addressed: Still need approved site/development plans and approved water plans. CSFD does not have record of reviewing either of these submittals. | dwithee | CO Springs Fire | 1194292 |
Electrical | Original | A | 1/15/2019 | BERTHA | BERTHA | | | Electrical | 1149881 |
Construction | Original | A | 1/15/2019 | DANM | DANM | | | Construction | 1149874 |
Out to Review | Original | / | 1/7/2019 | RITA | RITA | Lloyd 719-322-1022 | | Out to Review | 1147575 |
Finished Bin | Original | / | 1/7/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1147304 |
CO Springs Fire | Original | D | 1/4/2019 | CSFIRE | CSFIRE | See CSFD Plan Review Comments at: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp (see full review) | wtaylor | CO Springs Fire | 1147005 |
CO Springs DRE | Original | D | 12/28/2018 | KHYLLESTED | KHYLLESTED | 32'8" AR R 16-00508 expired 4/27/18 - admin relief must be renewed. (see full review) | | CO Springs DRE | 1145706 |
Fire | Original | / | 12/28/2018 | | KHYLLESTED | Location = Fire by KHYLLESTED | | Fire | 1145703 |
CO Springs DRE | Original | D | 12/28/2018 | KHYLLESTED | KHYLLESTED | 1. Recorded plat was included, geohazard report has been approved but a geohazard disclosure statement is required on the site plan. State the site specific geohazards along with the proposed mitigation. 2. An unapproved copy of the grading and erosion control plan was included in the plan set - the approved GECP must be included in resubmittal. 3. Site specific soils and foundation reports are required for ALL lots. Reports must include mitigation recommendations for expansive soils. LOTS 4 &5 must discuss mitigation of any potential impacts on the stability of the retaining walls and address Entech's recommendations. 4. Global stability of the retaining walls must be evaluated by PE. Must include estimated impacts to the retaining walls from roads, driveways, and structures. Follow Entech's recommendations on surface and subsurface drainage, fill placement, must be part of construction plans. (see full review) | | CO Springs DRE | 1145702 |
Zoning/Planning | Original | / | 12/18/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1142847 |
Plan Coordinator | Original | / | 12/18/2018 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1142742 |
Plumbing | Original | A | 12/18/2018 | SHANEN | SHANEN | See utility service plan. Note: two plans in this series - 112765, 112767 | | Plumbing | 1142741 |
Plumbing | Original | / | 12/18/2018 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1142663 |
Plumbing | Original | / | 12/17/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1142361 |
Plan Coordinator | Original | / | 12/17/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1142189 |
Mechanical | Original | A | 12/17/2018 | JUSTINC | JUSTINC | | | Mechanical | 1142187 |
Mechanical | Original | / | 12/17/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1142062 |
Mechanical | Original | / | 12/13/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1140995 |
Plan Coordinator | Original | / | 12/12/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1140963 |
Electrical | Original | D | 12/12/2018 | SHELBY | SHELBY | Show location of Electrical meters, service disconnects and panels on floor plan. Note two plans in this series 112765, 112767 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1140962 |
Electrical | Original | / | 12/7/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1139288 |
Plan Coordinator | Original | / | 12/7/2018 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1139247 |
Construction | Original | D | 12/7/2018 | SHELLEY | SHELLEY | Structural plans are over 2 years old, new stamp required;
See AMM approval under plan R91734 for unvented rafters. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1139246 |
Construction | Original | / | 12/7/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1139198 |
Construction | Original | / | 12/4/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1137274 |
Plan Coordinator | Original | / | 12/4/2018 | AMY | AMY | In Current Review by AMY | | Plan Coordinator | 1137266 |
Plan Coordinator | Original | / | 12/4/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1137265 |
Enumeration | Original | A | 12/4/2018 | AMY | AMY | 2224 & 2236 GLENN STREET. SITE PLAN A1.1 | | Enumeration | 1137264 |
Enumeration | Original | / | 12/4/2018 | AMY | AMY | In Current Review by AMY | | Enumeration | 1137261 |
Fire | Original | / | 11/29/2018 | RBD GIS | RBD GIS | Parcel 7411111019 is within the Wildland Urban Interface (WUI). Fire Department Review is required. | | Fire | 1136019 |
Floodplain | Original | N | 11/29/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7411111019) | | Floodplain | 1136020 |