Elevators | Splice 10/05/21 | A | 10/6/2021 | ERIC | ERIC | Removed elevators from scope | | Elevators | 1574496 |
Construction | Splice 10/05/21 | A | 10/6/2021 | MICHAELA | MICHAELA | Deleted elevators | | Construction | 1574485 |
Construction | Splice 07/02/21 | A | 7/7/2021 | MICHAELA | MICHAELA | Add structural changes | | Construction | 1526870 |
Electrical | Original | A | 5/28/2021 | DANIELG | DANIELG | | | Electrical | 1508417 |
Mechanical | Original | A | 5/25/2021 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 1505977 |
Electrical | Original | D | 5/24/2021 | DANIELG | DANIELG | Specify method to keep electrical panel in unit 1758 off the rated wall.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1505142 |
Electronic Plan | Original | / | 5/21/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1504324 |
Construction | Original | A | 5/20/2021 | MICHAELA | MICHAELA | | | Construction | 1503942 |
Electronic Plan | Original | / | 5/20/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1503529 |
Enumeration | Original | A | 5/19/2021 | BECKYA | BECKYA | | | Enumeration | 1503195 |
Electronic Plan | Original | / | 5/19/2021 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1503170 |
Resubmittal 2 | Original | / | 5/18/2021 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1502764 |
Health Dept. | Original | N | 5/17/2021 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT0043404 is valid from 1/1/21-7/1/21. AB | abrannon | Health Dept. | 1501943 |
Electrical | Original | D | 5/14/2021 | DANIELG | DANIELG | Comply with previous review comments.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1501276 |
Mechanical | Original | D | 5/14/2021 | TCRIPPEN | TCRIPPEN | I have 3 sets of equipment certificates and calculations for only one unit F-1 missing the other two packets ? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1501196 |
Electronic Plan | Original | / | 5/14/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1501178 |
Construction | Original | D | 5/14/2021 | MICHAELA | MICHAELA | 2009 ANSI 117.1 does not permit shower doors in Type B units. An AM&M to use the 2017 ANSI would be required to allow doors removable without damage to the walls. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1501156 |
Enumeration | Original | A | 5/13/2021 | BECKYA | BECKYA | | | Enumeration | 1500209 |
Electronic Plan | Original | / | 5/13/2021 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1500193 |
Resubmittal 1 | Original | / | 5/12/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1500054 |
CO Springs Fire | Original | A | 5/5/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | dwithee | CO Springs Fire | 1496380 |
Health Dept. | Original | D | 4/29/2021 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application For questions, contact Environmental Health at 719-578-3199 option 3. KM | kmaldonado | Health Dept. | 1493619 |
Electrical | Original | D | 4/29/2021 | DANIELG | DANIELG | 1) Show all electrical service equipment and disconnects serving each structure. Must be able to verify location of meter disconnect and each unit panel.
2) Provide clarification that panels are not in rated walls.
3) Pending construction approval of accessibility plan.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1493406 |
Electronic Plan | Original | / | 4/29/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1493084 |
Plumbing | Original | A | 4/28/2021 | SHANEN | SHANEN | Living areas not reviewed.Must comply with current adopted codes. | | Plumbing | 1492553 |
City Engr | Original | A | 4/28/2021 | PMORRIS | PMORRIS | | | City Engr | 1492273 |
Mechanical | Original | D | 4/26/2021 | TCRIPPEN | TCRIPPEN | Missing heat calculations (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1491386 |
Electronic Plan | Original | / | 4/26/2021 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1491376 |
CSU Contract Admin. | Original | N | 4/26/2021 | CSUAPPSPRM | CSUAPPSPRM | All applicable development fees/charges will be collected at time of individual townhome applications. AG | aguerin | CSU Contract Admin. | 1491272 |
CO Springs DRE | Original | A | 4/26/2021 | MPFITZSIMMONS | MPFITZSIMMONS | Stamped plans included for the Ivywild townhomes. (see full review) | | CO Springs DRE | 1491221 |
Zoning/Planning | Original | / | 4/26/2021 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MPFITZSIMMONS | | Zoning/Planning | 1491161 |
CSU Waste Water | Original | A | 4/26/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. DMM | dmakings | CSU Waste Water | 1491042 |
CSU Water | Original | A | 4/26/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. DMM | dmakings | CSU Water | 1491040 |
Gas/Elec. Utils | Original | A | 4/26/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. DMM | dmakings | Gas/Elec. Utils | 1491039 |
Construction | Original | D | 4/26/2021 | MICHAELA | MICHAELA | Accessibility plan - This should be for the entire site and although this structure is only 3 units the are many 4 unit structures. Indicate compliance with IRC sec. 320 and IBC sec 1107.6.3 Provide a 2-hr separation wall assembly or submit an Alternate Materials and Methods request to use the 2018 IRC for compliance. Locate smoke and CO alarms, bath fans, attic access. Add notes for required garage/dwelling separation. Rated assembly must extend to the underside of the roof sheathing of the lower roof. 1-hr protection at the property line must occur above the lower roof. Structural - Correct wind load. H2.5 has been discontinued for years. Indicate a hanger with a value that can be currently evaluated. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1490929 |
Electronic Plan | Original | / | 4/26/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1490835 |
Enumeration | Original | A | 4/22/2021 | BRENT | BRENT | | | Enumeration | 1489790 |
Electronic Plan | Original | / | 4/22/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1489725 |
Floodplain | Original | A | 4/20/2021 | KEITH | KEITH | see fp 21028 for more fp docs | | Floodplain | 1488487 |
Floodplain | Original | / | 4/20/2021 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6430209048) | | Floodplain | 1488135 |