Electrical | Original | D | 10/26/2023 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1919344 |
Construction | Original | A | 10/26/2023 | CHRISTINEH | CHRISTINEH | | | Construction | 1919214 |
Submittal 5 | Original | / | 10/26/2023 | BRIANNAM | BRIANNAM | Submittal #5 | | Submittal 5 | 1919117 |
Electrical | Original | D | 3/29/2023 | DANIELG | DANIELG | 1. Remove GEC from the PV service conductors. Please see note on the one-line.
2. Plan is missing a detailed floor plan.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1822492 |
Electronic Plan | Original | / | 3/29/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1822486 |
Construction | Original | A | 3/29/2023 | CHRISTINEH | CHRISTINEH | | | Construction | 1822381 |
Submittal 4 | Original | / | 3/29/2023 | SIERRAC | SIERRAC | Submittal #4 | | Submittal 4 | 1822218 |
Electrical | Original | D | 2/27/2023 | DANIELG | DANIELG | 1. Remove the GEC from the PV service conductors.
2. Site-plan, floor-plan, and one-line diagram still do not match.
Call 719-327-2980 for consultation.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1807403 |
Electronic Plan | Original | / | 2/27/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1807352 |
Construction | Original | A | 2/27/2023 | CHRISTINEH | CHRISTINEH | | | Construction | 1807226 |
Submittal 3 | Original | / | 2/24/2023 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 1807130 |
Electrical | Original | D | 2/16/2023 | DANIELG | DANIELG | 1. Comply with previous review comments #2 and #3.
2. Site-plan, floor-plan, and one-line diagram must match.
3. Comply 250.122 NEC. Provide EGC from the array to the enphase combiner.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1803617 |
Electronic Plan | Original | / | 2/16/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1803612 |
Construction | Original | A | 2/15/2023 | CHRISTINEH | CHRISTINEH | | | Construction | 1803501 |
Submittal 2 | Original | / | 2/15/2023 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1803247 |
Electrical | Original | D | 1/24/2023 | DANIELG | DANIELG | 1. Labeling of each device must match on the site-plan, one-line, and floor plan.
2. Remove GEC from PV service conductor's.
3. List conductors from PV service disconnect to the IQ system controller.
4. List conductor size, type, and quantity from IQ system controller to new back-up loads panel.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1794831 |
Electronic Plan | Original | / | 1/24/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1794823 |
Construction | Original | A | 1/23/2023 | CHRISTINEH | CHRISTINEH | | | Construction | 1793838 |
Electronic Plan | Original | / | 1/23/2023 | CHRISTINEH | CHRISTINEH | In Current Review by CHRISTINEH | | Electronic Plan | 1793833 |
Floodplain | Original | N | 1/20/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6421425001) | | Floodplain | 1793412 |