Electrical | Original | D | 2/10/2023 | RICHG | RICHG | 1. Comply with 706.31 (F)
2. Provide specification sheets for micro inverters being used.
3. Provide specification sheets for inverter.
4. Update site, floor, and one line to match once changes are made.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1801740 | Electronic Plan | Original | / | 2/10/2023 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1801729 | Construction | Original | A | 2/3/2023 | ANDREAL | ANDREAL | Approved | | Construction | 1798924 | Electronic Plan | Original | / | 2/3/2023 | ANDREAL | ANDREAL | In Current Review by ANDREAL | | Electronic Plan | 1798919 | Zoning | Original | N | 2/2/2023 | SYSTEM | SYSTEM | Zoning review is not required for roof-mounted PV solar projects in El Paso County. | | Zoning | 1798386 | Floodplain | Original | N | 2/2/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 2308001008) | | Floodplain | 1798385 |
|
| |
|