CO Springs Fire | Original | D | 10/9/2024 | CSFIRE | CSFIRE | Previous comments not addressed. | rpeterson | CO Springs Fire | 2070068 |
Energy | Original | D | 10/1/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2066528 |
Mechanical | Original | D | 10/1/2024 | TREVORH | TREVORH | Disapproved; 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2066527 |
CO Springs DRE | Original | D | 9/30/2024 | KSCHOTT | KSCHOTT | 1. Is this the most recent approved development plan? there are elevation drawings with original DP and any architectural drawings need to show the same elevations or a modification to the DP will be required 2. Upload the most recent replat from 2007 (the one you uploaded is older) 3. Need to provide additional/new private financial assurances for private improvements. contact DREPlanningInfo@coloradosprings.gov to pay 4. Need to pay school and park fees for each new unit. Contact DREPlanningInfo@coloradosprings.gov to pay 5. Per PRE-23-0994; provide written documentation/communication with City Stormwater regarding the initial Final Drainage Report done in 2014 and if suffices now or if additional information/review is needed. 6. Are there alterations to the original landscape plan found in the original DP? This may require additional review, contact patrick.dosch@coloradosprings.gov Current site has been vested and must be completed in accordance with approved development p (see full review) | | CO Springs DRE | 2066244 |
City Engr | Original | D | 9/27/2024 | JDAGNILLO | JDAGNILLO | Please address previou comments:
1. Include a copy of the approved Development Plan. | | City Engr | 2065809 |
Health Dept. | Original | D | 9/27/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | Health Dept. | 2065313 |
CSU Water | Original | D | 9/27/2024 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Water | 2065269 |
CSU Waste Water | Original | D | 9/27/2024 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2065268 |
Gas/Elec. Utils | Original | D | 9/27/2024 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 2065267 |
Plumbing | Original | D | 9/27/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2065233 |
Zoning/Planning | Original | / | 9/26/2024 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2065198 |
Electrical | Original | D | 9/26/2024 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2065091 |
Construction | Original | D | 9/26/2024 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2065060 |
Enumeration | Original | A | 9/26/2024 | BECKYA | BECKYA | | | Enumeration | 2064907 |
Submittal 2 | Original | / | 9/26/2024 | BRIANNAM | BRIANNAM | Submittal #2 | | Submittal 2 | 2064879 |
CO Springs Fire | Original | D | 5/15/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2004082 |
Energy | Original | D | 5/6/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1999218 |
Mechanical | Original | D | 5/6/2024 | TREVORH | TREVORH | Disapprove; When providing duct design you need to use a registered designer or can use an engineers stamp on all pages, whole house ventilation required. see progress set. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1999217 |
Electronic Plan | Original | / | 5/6/2024 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 1999175 |
Electronic Plan | Original | / | 5/6/2024 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 1999169 |
City Engr | Original | D | 5/2/2024 | PMORRIS | PMORRIS | 1. Upload a copy of the Approved Development Plan into the building permit review set.
2. Add the following note to the site & parking sheet C1 in the Civil Drawing: "GEOLOGIC HAZARD DISCLOSURE STATEMENT:
THIS PROPERTY IS SUBJECT TO THE FIINDINGS, SUMMARY AND CONCLUSIONS OF THE GEOLOGIC HAZARD REPORT PREPARED BY JOHN HIMMELREICH & ASSOCIATES, DATED 4/30/02. A COPY OF SAID REPORT HAS BEEN PLACED WITHIN FILE CPC DP 02-46 OF THE CITY OF COLORADO SPRINGS - LAND USE REVIEW DIVISION. CONTACT LAND USE REVIEW DIVISION, 30 S. NEVADA AVE., SUITE 701, COLORADO SPRINGS, CO. IF YOU WOULD LIKE TO REVIEW SAID REPORT." | | City Engr | 1997611 |
Health Dept. | Original | D | 5/1/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1997464 |
CO Springs DRE | Original | D | 5/1/2024 | MOBRIEN | MOBRIEN | Please upload approved development plan stamped by Land Use Review, as well as recorded plat. (see full review) | | CO Springs DRE | 1997127 |
Electrical | Original | D | 4/30/2024 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1996899 |
Electronic Plan | Original | / | 4/30/2024 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1996879 |
Plumbing | Original | D | 4/30/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1996153 |
Zoning/Planning | Original | / | 4/29/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1995861 |
CSU Contract Admin. | Original | N | 4/29/2024 | CSUAPPSPRM | CSUAPPSPRM | Applicable Development Charges and Fees prior to building permit issuance.
AMS | ASweet | CSU Contract Admin. | 1995778 |
CSU Water | Original | D | 4/29/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Water | 1995764 |
CSU Waste Water | Original | D | 4/29/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 1995763 |
Gas/Elec. Utils | Original | D | 4/29/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 1995761 |
Construction | Original | D | 4/29/2024 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1995728 |
Electronic Plan | Original | / | 4/29/2024 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 1995691 |
Enumeration | Original | A | 4/25/2024 | BECKYA | BECKYA | See plans for several Enumeration edits. Lot numbers, parcel numbers, etc. If any of these pages are to be resubmitted, please make these changes on your end prior to resubmitting the plans. | | Enumeration | 1994364 |
Electronic Plan | Original | / | 4/25/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1994308 |
Energy | Original | / | 4/24/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1993849 |
Floodplain | Original | N | 4/24/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7326105057) | | Floodplain | 1993848 |
Fire | Original | / | 4/24/2024 | RBD GIS | RBD GIS | Parcel 7326105057 is within the Wildland Urban Interface (WUI). Fire Department Review is required. | | Fire | 1993847 |