Finished Bin (Main) | Original | / | 11/1/2024 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 2080799 |
City Engr | Original | A | 11/1/2024 | JDAGNILLO | JDAGNILLO | No geological hazard report or waiver will be required.
plans routed to RBD | | City Engr | 2080784 |
City Engr (SERT) | Original | / | 10/31/2024 | | MAMBUUL | Location = City Engr (SERT) by MAMBUUL | | City Engr (SERT) | 2079885 |
CO Springs DRE | Original | D | 10/31/2024 | MAMBUUL | MAMBUUL | Please provide a site plan showing setback requirements and dimensions of proposed additions to residence, garage, and for new shed. (see full review) | | CO Springs DRE | 2079884 |
Zoning/Planning | Original | / | 10/30/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2079400 |
Zoning/Planning | Original | / | 10/30/2024 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 2079390 |
Energy | Original | D | 10/30/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2079149 |
Plan Coordinator (Main) | Original | / | 10/30/2024 | | DOUGC | Location = Plan Coordinator (Main) by DOUGC | | Plan Coordinator (Main) | 2079148 |
Energy | Original | D | 10/30/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2079147 |
Construction | Original | D | 10/30/2024 | DOUGC | DOUGC | • Clarify if shed is heated • Clarify insulation in shed per sheet S-4 • Provide fire separation distance from addition to property line • Clarify space between existing garage and shed, A1 says its 4’ • Provide missing elevation cuts A-E on S-2 • Provide manufacturers product details for polycarbonate roofing panels to show compliance with class A requirements • Provide ES report for spray foam insulation used 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2079146 |
Construction (Main) | Original | / | 10/28/2024 | DOUGC | DOUGC | In Current Review by DOUGC | | Construction (Main) | 2078085 |
Construction (Main) | Original | / | 10/24/2024 | | RITA | Location = Construction (Main) by RITA | | Construction (Main) | 2076896 |
Energy | Original | / | 10/24/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2076895 |
Floodplain | Original | N | 10/24/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6406420016) | | Floodplain | 2076894 |