CO Springs DRE | Original | A | 3/6/2025 | CVANAPPLEDORN | CVANAPPLEDORN | Flush mount roof solar panels and/or PV solar panels do not exceed maximum residential height requirements. | | CO Springs DRE | 2128302 |
Zoning/Planning | Original | / | 3/6/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2128300 |
Electrical | Original | D | 3/6/2025 | DANIELG | DANIELG | Service conductors are undersized for a 200A service.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2128202 |
Construction | Original | D | 3/6/2025 | SIERRAC | SIERRAC | DISAPPROVED-
1. Please provide dimensions for fire setbacks and pathways along the panels perimeters.
2. Provide the Array Coverage vs. Total Roof Area: Total Roof Area=? Total Array Area=? % of Roof Coverage=?
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2128105 |
Electronic Plan | Original | / | 3/6/2025 | SIERRAC | SIERRAC | In Current Review by SIERRAC | | Electronic Plan | 2128096 |
Submittal 2 | Original | / | 3/6/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2128085 |
Electrical | Original | D | 2/18/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2121743 |
Electronic Plan | Original | / | 2/18/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2121738 |
CO Springs DRE | Original | A | 2/7/2025 | CVANAPPLEDORN | CVANAPPLEDORN | Flush mount roof solar panels and/or PV solar panels do not exceed maximum residential height requirements. | | CO Springs DRE | 2118637 |
Zoning/Planning | Original | / | 2/6/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2118283 |
Construction | Original | D | 2/6/2025 | SIERRAC | SIERRAC | DISAPPROVED- 1. Please provide dimensions for fire setbacks and pathways along the panels perimeters. 2. Provide the Array Coverage vs. Total Roof Area: Total Roof Area=? Total Array Area=? % of Roof Coverage=? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2118101 |
Energy | Original | N | 2/5/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2117722 |
Zoning | Original | / | 2/5/2025 | SYSTEM | SYSTEM | Colorado Springs requires a zoning review for roof-mounted PV solar projects. | | Zoning | 2117721 |
Floodplain | Original | N | 2/5/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6426111005) | | Floodplain | 2117720 |