CO Springs Fire | Original | D | 6/13/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2171484 |
City Engr | Original | A | 6/5/2025 | HVO | HVO | A geo-hazard report has been approved and is on the building permit submission set. | | City Engr | 2167416 |
CO Springs DRE | Original | D | 6/4/2025 | SSADLER | SSADLER | This parcel is in the hillside overlay and requires a hillside site plan. Upload the correct site plan showing all required site dimensional standards and hillside requirements. | | CO Springs DRE | 2166502 |
Zoning/Planning | Original | / | 6/3/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2166431 |
Energy | Original | D | 6/3/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2166064 |
Mechanical | Original | D | 6/3/2025 | TREVORH | TREVORH | Disapproved; need to show efficiency on the equipment certificate * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2166063 |
Electrical | Original | A | 6/3/2025 | DANIELG | DANIELG | | | Electrical | 2166024 |
Electronic Plan | Original | / | 6/3/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2166018 |
Construction | Original | D | 6/3/2025 | CHRISTINEH | CHRISTINEH | Provide front door size / Label trusses on roof framing page / See IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2165960 |
Plumbing | Original | D | 5/30/2025 | SHANEN | SHANEN | Provide a plumbing floor plan to show all plumbing fixtures. All hydronic heating related items must be on the mechanical plans. Remove all references to this system from the plumbing plans. Provide code path that supports daylighting floor drains. Water meter location must comply with utility department requirements. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2164684 |
Electronic Plan | Original | / | 5/29/2025 | CHRISTINEH | CHRISTINEH | In Current Review by CHRISTINEH | | Electronic Plan | 2164599 |
Floodplain | Original | N | 5/23/2025 | KEITH | KEITH | | | Floodplain | 2162381 |
Enumeration | Original | D | 5/22/2025 | BRENT | BRENT | The tax schedule number shown on the site plan is incorrect for the address shown. Update to show the correct tax schedule number. The legal description must appear on the site plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2162337 |
Electronic Plan | Original | / | 5/22/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2162334 |
Energy | Original | / | 5/22/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2162207 |
Floodplain | Original | / | 5/22/2025 | RBD GIS | RBD GIS | Autogenerated Review: Floodplain status unknown. (Parcel: 7327103061) | | Floodplain | 2162206 |
Fire | Original | / | 5/22/2025 | RBD GIS | RBD GIS | 2589 LYONS VIEW PT is on a private road within Colorado Springs. Fire Department Review is required. | | Fire | 2162205 |