Plan #
  
Type
 
Plan
Owner
Address
610 RED SPRING VALLEY PL, COLORADO SPRINGS, CO 80919
Parcel Info
7301001001
Truss P/SF
30 (Elevation: 6,485 Feet)
Project
PV SOLAR W/ESS WITH ESS ( 13530 WATTS ) (
434
)
Type Of Plan
Normal
Review Type
Electronic
Fire District
WOODMEN VALLEY FIRE PROTECTION DISTRICT
Submit Date
Approval Date
Location
Plan Image
View Plan Image
Download Plan Image
Map
Google Map
Yahoo Maps
Bing Maps
MapQuest
GIS Map
County Map & Data
PPRBD Directions
Required Departments: 6
By checking this box, you agree to the following:
Overtime reviews are billed at $100/hour of review time.
Requesting overtime is optional. If I don’t request it, my plan will still be reviewed in the order submitted.
Overtime reviews are dependent on staff availability, so there is no guarantee that the review will be expedited. You will only be charged overtime fees if we are able to perform those reviews. If no one is available to take that review on an overtime basis, your plan may end up being reviewed in the regular sequence.
Required Departments and Log Entries
Department
Status
Approve Overtime
Overtime
Overtime_2
BoundColumn_2
Department
Construction
D
Approved for Overtime
1
C
Construction
Electrical
A
0
E
Electrical
Energy
N
G
Energy
Woodmen Valley Fire
-
0
F
Woodmen Valley Fire
Floodplain
N
W
Floodplain
County Zoning
N
0
Z
County Zoning
Log Entries: 9
Log Details
View Log
Log
Time Summary
Department
Splice
Status
Date
Reviewer
Reviewer
Comment
username
Department
tid
Electrical
Original
A
1/5/2026
CONNERM
CONNERM
Electrical
2253271
Electronic Plan
Original
/
1/5/2026
CONNERM
CONNERM
In Current Review by CONNERM
Electronic Plan
2253265
Construction
Original
D
1/5/2026
SIERRAC
SIERRAC
DISAPPROVED
Basic Wind Speed should be 130 mph.
Minimum Ground Snow Load for properties under 7,000 ft in elevation require at least 43 psf.
Wind Exposure Category should be C.
Please provide the distances from the window/door to the Battery.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Construction
2253248
Construction
Original
/
12/31/2025
WEBSITE
WEBSITE
Overtime Authorized for Construction by MARK BAKER
SpringsElectrical1
Construction
2252459
Hazmat
Original
/
12/19/2025
SYSTEM
SYSTEM
You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically.
Hazmat
2250269
Fire
Original
/
12/19/2025
SYSTEM
SYSTEM
You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically.
Fire
2250270
Energy
Original
N
12/19/2025
SYSTEM
SYSTEM
Energy Department review not required under 2023 PPRBC when IECC is N/A
Energy
2250268
Zoning
Original
N
12/19/2025
SYSTEM
SYSTEM
Zoning review is not required for roof-mounted PV solar projects in El Paso County.
Zoning
2250267
Floodplain
Original
N
12/19/2025
RBD GIS
RBD GIS
Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7301001001)
Floodplain
2250266