| Electrical | Original | D | 2/25/2026 | CONNERM | CONNERM | Provide conductor/Conduit size, type, and quantity
Please submit revisions under their specific plan image (One-line, ESS Floor Plan), not "Other" * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2271101 |
| Construction | Original | D | 2/25/2026 | JUSTINL | JUSTINL | See floor plan for ESS location for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2271021 |
| Electronic Plan | Original | / | 2/25/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2271018 |
| Submittal 2 | Original | / | 2/25/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2270665 |
| CO Springs Hazmat | Original | A | 2/23/2026 | CSFIRE | CSFIRE | DFM-C-ES-26-00005 CSFD DFM You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources. If you do not have an ACA account at the time of CSFD review, you will need to reach out to the CSFD DFM staff to link the review to your account. DFM Plan Review Fee: $296.00 ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | CO Springs Hazmat | 2269576 |
| CO Springs Fire | Original | A | 2/23/2026 | CSFIRE | CSFIRE | DFM-C-Es-26-00005 RES ESS
CSFD DFM You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources. If you do not have an ACA account at the time of CSFD review, you will need to reach out to the CSFD DFM staff to link the review to your account. DFM Plan Review Fee: $296.00 ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | CO Springs Fire | 2269573 |
| Mechanical | Original | N | 2/18/2026 | TREVORH | TREVORH | Not Applicable; | | Mechanical | 2267892 |
| Electrical | Original | D | 2/18/2026 | CONNERM | CONNERM | Provide conductor size, type, and quantity
Provide spec sheets for Tesla Gateway 3 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2267630 |
| Electronic Plan | Original | / | 2/18/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2267626 |
| Construction | Original | D | 2/18/2026 | JUSTINL | JUSTINL | See ESS floor plan and manufacture specifications for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2267622 |
| Electronic Plan | Original | / | 2/6/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2264138 |
| | Original | / | 2/4/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/04/2026 for plan submitted 02/04/2026. Submit Date updated to now. Plan now open for review. | | | 2263287 |
| Energy | Original | N | 2/4/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2263198 |
| Floodplain | Original | N | 2/4/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6402201051) | | Floodplain | 2263197 |