| CO Springs DRE | Original | D | 8/14/2026 | CVANAPPLEDORN | CVANAPPLEDORN | Please provide a site plan with accurate property lines included and the distance from the utility boxes to the nearest property line. | | CO Springs DRE | 2348134 |
| Zoning/Planning | Original | / | 8/14/2026 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2348133 |
| CO Springs Hazmat | Original | D | 8/4/2026 | CSFIRE | CSFIRE | DFM-C-ES-26-00021 Need a detailed floor plan of the garage showing the location of the batteries, all walls, windows, and doors, including the roll-up garage door and the door to the interior of the house. A hard-wired smoke and/or heat detector shall be installed, and the location shall be shown on the plans. | mark.stanwood@colora | CO Springs Hazmat | 2342729 |
| Mechanical | Original | N | 7/31/2026 | TREVORH | TREVORH | Not Applicable; No Mechanical scope. | | Mechanical | 2341562 |
| Electrical | Original | D | 7/31/2026 | CONNERM | CONNERM | See one-line * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2341460 |
| Electronic Plan | Original | / | 7/31/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2341439 |
| Construction | Original | D | 7/31/2026 | DOUGC | DOUGC | Design Loads for Roof // Layout page with door location to dwelling and distance * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2341437 |
| Submittal 2 | Original | / | 7/30/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2341319 |
| CO Springs Hazmat | Original | D | 3/26/2026 | CSFIRE | CSFIRE | DFM-C-ES-26-00021 Need a detailed Interior Floor Plan showing the location, type of room, and locations of interior and exterior doors and windows. Please show the location of the smoke or heat alarms. Batteries must be spaced 3 FT apart or have a UL 9540A testing documentation showing the acceptable reduced spacing. A copy of the UL 9540 Listing is required. | mark.stanwood@colora | CO Springs Hazmat | 2285300 |
| CO Springs Fire | Original | N | 3/26/2026 | CSFIRE | CSFIRE | No FCS Review this is HAZMAT Only - NA FDMUS | mark.stanwood@colora | CO Springs Fire | 2285291 |
| Mechanical | Original | D | 3/10/2026 | TREVORH | TREVORH | Disapproved; Need to see construction review comments addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2278173 |
| Electrical | Original | D | 3/10/2026 | CONNERM | CONNERM | Provide letter of certification form NRTL verifying UL listing 9540 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2278166 |
| Electronic Plan | Original | / | 3/10/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2278161 |
| Construction | Original | D | 3/10/2026 | DOUGC | DOUGC | Floor plan // Elevation // Design Criteria * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2278139 |
| Electronic Plan | Original | / | 3/10/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2278116 |
| | Original | / | 2/20/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/20/2026 for plan submitted 02/18/2026. Submit Date updated to now. Plan now open for review. | | | 2269127 |
| Energy | Original | N | 2/18/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2267707 |
| Floodplain | Original | N | 2/18/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6315112031) | | Floodplain | 2267706 |