| City Engr | Original | A | 7/28/2026 | HVO | HVO | EDRD has no additional comments. | | City Engr | 2339868 |
| City Engr | Original | / | 7/22/2026 | | SCANNING | Location = City Engr by SCANNING | | City Engr | 2337652 |
| Plan Coordinator | Original | / | 7/22/2026 | | SSADLER | Location = Plan Coordinator by SSADLER | | Plan Coordinator | 2337563 |
| CO Springs DRE | Original | D | 7/22/2026 | SSADLER | SSADLER | Site dimensional standards met. However, the only remaining comment is to collect police and fire fees. Plans are approved and once fees are collected, the building permit can be approved. Please contact DRE at charla.hudspeth@coloradosprings.gov
All required documents are on file. | | CO Springs DRE | 2337562 |
| Zoning/Planning | Original | / | 7/16/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2335059 |
| Zoning/Planning | Original | / | 7/16/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2334887 |
| Zoning/Planning | Original | / | 7/16/2026 | | NELIDA | Location = Zoning/Planning by NELIDA | | Zoning/Planning | 2334839 |
| Plan Coordinator (Main) | Original | / | 7/16/2026 | | CONNERM | Location = Plan Coordinator (Main) by CONNERM | | Plan Coordinator (Main) | 2334837 |
| Electrical | Original | A | 7/16/2026 | CONNERM | CONNERM | | | Electrical | 2334836 |
| Electrical (Main) | Original | / | 7/14/2026 | | NELIDA | Location = Electrical (Main) by NELIDA | | Electrical (Main) | 2334017 |
| Plan Coordinator (Main) | Original | / | 7/14/2026 | | TCRIPPEN | Location = Plan Coordinator (Main) by TCRIPPEN | | Plan Coordinator (Main) | 2333985 |
| Plumbing | Original | A | 7/14/2026 | TCRIPPEN | TCRIPPEN | Approved | | Plumbing | 2333983 |
| Mechanical | Original | A | 7/14/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2333971 |
| Mechanical (Main) | Original | / | 7/10/2026 | | SCANNING | Location = Mechanical (Main) by SCANNING | | Mechanical (Main) | 2333012 |
| Plan Coordinator (Main) | Original | / | 7/10/2026 | | BRIANB | Location = Plan Coordinator (Main) by BRIANB | | Plan Coordinator (Main) | 2333010 |
| Construction | Original | D | 7/10/2026 | BRIANB | BRIANB | Provide complete stamped set of plans / 11x17 plans submitted are incomplete * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2333007 |
| Construction (Main) | Original | / | 7/9/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Construction (Main) | 2332782 |
| Construction (Main) | Original | / | 6/23/2026 | | REESAA | Location = Construction (Main) by REESAA | | Construction (Main) | 2325204 |
| | Original | / | 6/23/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/23/2026 for plan submitted 06/23/2026 | | | 2325201 |
| | Original | / | 6/23/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2325200 |
| | Original | / | 6/23/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2325195 |
| Submittal 3 | Original | / | 6/23/2026 | REESAA | REESAA | Submittal #3 | | Submittal 3 | 2325194 |
| Out to Review | Original | / | 6/18/2026 | NELIDA | NELIDA | 719-459-1771 Rob | | Out to Review | 2323241 |
| City Engr | Original | D | 6/17/2026 | DSOSA | DSOSA | Please address previous comment | | City Engr | 2323041 |
| City Engr | Original | / | 6/11/2026 | | SCANNING | Location = City Engr by SCANNING | | City Engr | 2319620 |
| Zoning/Planning | Original | / | 6/9/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2318121 |
| Zoning/Planning | Original | / | 6/8/2026 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 2317935 |
| Plumbing | Original | D | 6/8/2026 | TCRIPPEN | TCRIPPEN | disapproved * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2317921 |
| Mechanical | Original | D | 6/8/2026 | TCRIPPEN | TCRIPPEN | Disapproved see plans * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2317914 |
| Mechanical (Main) | Original | / | 6/8/2026 | | SCANNING | Location = Mechanical (Main) by SCANNING | | Mechanical (Main) | 2317664 |
| Plan Coordinator (Main) | Original | / | 6/5/2026 | | CONNERM | Location = Plan Coordinator (Main) by CONNERM | | Plan Coordinator (Main) | 2317332 |
| Electrical | Original | D | 6/5/2026 | CONNERM | CONNERM | Address construction comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2317331 |
| Electrical (Main) | Original | / | 6/5/2026 | | SCANNING | Location = Electrical (Main) by SCANNING | | Electrical (Main) | 2317328 |
| Plan Coordinator (Main) | Original | / | 6/5/2026 | | BRIANB | Location = Plan Coordinator (Main) by BRIANB | | Plan Coordinator (Main) | 2317305 |
| Construction | Original | D | 6/5/2026 | BRIANB | BRIANB | Missing State of Colorado cover sheet for Building Specifications with expiration date and CDOH Approval Number / Need full size plan 11 x 17 or larger (8x10 plans are too small) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2317304 |
| Construction (Main) | Original | / | 6/4/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Construction (Main) | 2316765 |
| Construction (Main) | Original | / | 6/1/2026 | | REESAA | Location = Construction (Main) by REESAA | | Construction (Main) | 2314774 |
| Submittal 2 | Original | / | 6/1/2026 | REESAA | REESAA | Submittal #2: Rob 719-459-1771 | | Submittal 2 | 2314773 |
| Out to Review | Original | / | 5/18/2026 | NELIDA | NELIDA | Rob 719-459-1771 | | Out to Review | 2309060 |
| Finished Bin (Main) | Original | / | 5/15/2026 | | NELIDA | Location = Finished Bin (Main) by NELIDA | | Finished Bin (Main) | 2308312 |
| City Engr | Original | D | 5/15/2026 | HVO | HVO | Please include a copy of the approved Developement Plan, and a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2308295 |
| City Engr | Original | / | 5/15/2026 | | SCANNING | Location = City Engr by SCANNING | | City Engr | 2308002 |
| Plan Coordinator | Original | / | 5/15/2026 | | SSADLER | Location = Plan Coordinator by SSADLER | | Plan Coordinator | 2307774 |
| CO Springs DRE | Original | D | 5/15/2026 | SSADLER | SSADLER | Upload the approval letter and the approved stamped plans for record # SUBD-25-0075. Fees may be due prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov | | CO Springs DRE | 2307773 |
| Zoning/Planning | Original | / | 5/8/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2305208 |
| Zoning/Planning | Original | / | 5/8/2026 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 2305196 |
| Plan Coordinator (Main) | Original | / | 5/8/2026 | | TCRIPPEN | Location = Plan Coordinator (Main) by TCRIPPEN | | Plan Coordinator (Main) | 2305142 |
| Plumbing | Original | D | 5/8/2026 | TCRIPPEN | TCRIPPEN | Disapproved * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2305025 |
| Mechanical | Original | D | 5/8/2026 | TCRIPPEN | TCRIPPEN | Disapproved * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2305023 |
| Mechanical (Main) | Original | / | 5/7/2026 | | SCANNING | Location = Mechanical (Main) by SCANNING | | Mechanical (Main) | 2304222 |
| Plan Coordinator (Main) | Original | / | 5/7/2026 | | CONNERM | Location = Plan Coordinator (Main) by CONNERM | | Plan Coordinator (Main) | 2304195 |
| Electrical | Original | D | 5/7/2026 | CONNERM | CONNERM | See Construction comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2304194 |
| Electrical (Main) | Original | / | 5/5/2026 | | SCANNING | Location = Electrical (Main) by SCANNING | | Electrical (Main) | 2302904 |
| Plan Coordinator (Main) | Original | / | 5/4/2026 | | BRIANB | Location = Plan Coordinator (Main) by BRIANB | | Plan Coordinator (Main) | 2302712 |
| Construction | Original | D | 5/4/2026 | BRIANB | BRIANB | Colorado State spec sheet expired 1NOV23 - provide documentation that construction of the unit was started prior to the expiration date * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2302711 |
| Construction (Main) | Original | / | 5/4/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Construction (Main) | 2302694 |
| Construction (Main) | Original | / | 4/1/2026 | | SCANNING | Location = Construction (Main) by SCANNING | | Construction (Main) | 2287667 |
| Plan Coordinator (Main) | Original | / | 4/1/2026 | | BECKYA | Location = Plan Coordinator (Main) by BECKYA | | Plan Coordinator (Main) | 2287636 |
| Floodplain | Original | N | 4/1/2026 | BECKYA | BECKYA | | | Floodplain | 2287635 |
| Enumeration | Original | A | 4/1/2026 | BECKYA | BECKYA | | | Enumeration | 2287634 |
| Enumeration (Main) | Original | / | 4/1/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Enumeration (Main) | 2287514 |
| Enumeration (Main) | Original | / | 3/31/2026 | | SCANNING | Location = Enumeration (Main) by SCANNING | | Enumeration (Main) | 2287263 |
| Plan Coordinator (Main) | Original | / | 3/31/2026 | | NICOLASV | Location = Plan Coordinator (Main) by NICOLASV | | Plan Coordinator (Main) | 2287164 |
| Energy | Original | N | 3/31/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2287163 |