Plan #
  
Type
 
Plan
Owner
Address
497 WHISTLER CREEK CT, MONUMENT, CO 80132
Parcel Info
7125415036
Truss P/SF
30 (Elevation: 6,928 Feet)
Project
RESIDENTIAL ESS (
434
)
Type Of Plan
Normal
Review Type
Electronic
Fire District
MONUMENT FIRE DIST
Submit Date
Approval Date
Location
Plan Image
View Plan Image
Download Plan Image
Map
Google Map
Yahoo Maps
Bing Maps
MapQuest
GIS Map
County Map & Data
PPRBD Directions
Required Departments: 6
By checking this box, you agree to the following:
Overtime reviews are billed at $100/hour of review time.
Requesting overtime is optional. If I don’t request it, my plan will still be reviewed in the order submitted.
Overtime reviews are dependent on staff availability, so there is no guarantee that the review will be expedited. You will only be charged overtime fees if we are able to perform those reviews. If no one is available to take that review on an overtime basis, your plan may end up being reviewed in the regular sequence.
Required Departments and Log Entries
Department
Status
Approve Overtime
Overtime
Overtime_2
BoundColumn_2
Department
Construction
D
0
C
Construction
Electrical
D
0
E
Electrical
Energy
N
G
Energy
Monument Fire
A
F
Monument Fire
Floodplain
N
W
Floodplain
Mechanical
D
0
M
Mechanical
Log Entries: 8
Log Details
View Log
Log
Time Summary
Department
Splice
Status
Date
Reviewer
Reviewer
Comment
username
Department
tid
Mechanical
Original
D
5/27/2026
TCRIPPEN
TCRIPPEN
Disapproved
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Mechanical
2312229
Monument Fire
Original
A
5/26/2026
MONUMENTFIRE
MONUMENTFIRE
“Battery system is reported as 6.2 kWh aggregate capacity. No PV array is proposed. Based on the 2021 IFC Section 1207.1.1 threshold for electrochemical ESS, the system is below the capacity requiring compliance with Section 1207. No fire permit/review is required by the IFC, subject to verification of aggregate capacity, listing, manufacturer installation instructions, electrical permit requirements, and any local amendments.”
SBenson9
Monument Fire
2312007
Electrical
Original
D
5/26/2026
CONNERM
CONNERM
Provide conductor size, type, and quantity
Provide over current protection sizes
Label equipment as new or existing
Portable batteries not allowed under NEC 400.12
Batteries must have UL 9540 listing.
Provide specs for inverter/home panel
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Electrical
2311890
Electronic Plan
Original
/
5/26/2026
CONNERM
CONNERM
In Current Review by CONNERM
Electronic Plan
2311883
Construction
Original
D
5/26/2026
SHELLEY
SHELLEY
Demonstrate compliance with UL 9540A
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Construction
2311815
Original
/
5/22/2026
SYSTEM
SYSTEM
Plan Review fees paid 05/22/2026 for plan submitted 05/22/2026. Submit Date updated to now. Plan now open for review.
2311446
Energy
Original
N
5/22/2026
SYSTEM
SYSTEM
Energy Department review not required under 2023 PPRBC when IECC is N/A
Energy
2311439
Floodplain
Original
N
5/22/2026
RBD GIS
RBD GIS
Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7125415036)
Floodplain