| CO Springs DRE | Original | A | 9/15/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2359795 |
| Energy | Original | D | 9/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2359359 |
| Mechanical | Original | D | 9/15/2026 | QUINTONW | QUINTONW | Disapproved:Heat loss calcs do not match IECC R20 for walls R49 for ceiling and R30 for floors. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2359358 |
| Zoning/Planning | Original | / | 9/14/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2358958 |
| CSU Water | Original | D | 9/14/2026 | CSUREVIEW | CSUREVIEW | Currently proposed configuration appears to be per the current Colorado Springs Utilities WaterLESS details B2-9 ADU service detail (with exterior wastewater connection). Add note on the site plan and include the detail on the plumbing plan. Revise to show water connection after the existing meter inside existing building. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. PSD | PDosch | CSU Water | 2358953 |
| CSU Waste Water | Original | D | 9/14/2026 | CSUREVIEW | CSUREVIEW | Currently proposed configuration appears to be per the current Colorado Springs Utilities WaterLESS details B2-9 ADU service detail (with exterior wastewater connection). Add note on the site plan and include the detail on the plumbing plan. Revise to show water connection after the existing meter inside existing building. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. PSD | PDosch | CSU Waste Water | 2358952 |
| Electrical | Original | A | 9/14/2026 | CONNERM | CONNERM | | | Electrical | 2358911 |
| Construction | Original | A | 9/14/2026 | DOUGC | DOUGC | | | Construction | 2358900 |
| Enumeration | Original | A | 9/11/2026 | AMY | AMY | | | Enumeration | 2358537 |
| Electronic Plan | Original | / | 9/11/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2358512 |
| | Original | / | 9/11/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2358471 |
| | Original | / | 9/11/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2358432 |
| Submittal 3 | Original | / | 9/11/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2358431 |
| CSU Contract Admin. | Original | N | 8/18/2026 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees required for this plan set.
AMS | ASweet | CSU Contract Admin. | 2349011 |
| CSU Water | Original | D | 8/17/2026 | CSUREVIEW | CSUREVIEW | Please show the proposed water and wastewater service connections to the ADU on the site plans. Refer to the current Colorado Springs Utilities WaterLESS details B2-8 and B2-9 and select the correct ADU service detail to include on the plans.
CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. SSH | SHillman | CSU Water | 2348341 |
| CSU Waste Water | Original | D | 8/17/2026 | CSUREVIEW | CSUREVIEW | Please show the proposed water and wastewater service connections to the ADU on the site plans. Refer to the current Colorado Springs Utilities WaterLESS details B2-8 and B2-9 and select the correct ADU service detail to include on the plans.
CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. SSH | SHillman | CSU Waste Water | 2348340 |
| CO Springs DRE | Original | A | 8/17/2026 | SSADLER | SSADLER | Approved for a detached ADU and garage. All site dimensional standards have been met. All entitlements are on file. All fees have been paid and poster has been picked up. | | CO Springs DRE | 2348235 |
| Waste Water Div | Original | / | 8/17/2026 | SYSTEM | SYSTEM | CSU Waste Water reviews are required for Single Family plans identified as Additional Dwelling Units (ADU). | | Waste Water Div | 2348233 |
| CSU Contract Admin | Original | / | 8/17/2026 | SYSTEM | SYSTEM | CSU Contract Admin reviews are required for Single Family plans identified as Additional Dwelling Units (ADU). | | CSU Contract Admin | 2348234 |
| Water Division | Original | / | 8/17/2026 | SYSTEM | SYSTEM | CSU Water reviews are required for Single Family plans identified as Additional Dwelling Units (ADU). | | Water Division | 2348232 |
| Energy | Original | D | 7/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2334924 |
| Plumbing | Original | A | 7/16/2026 | TCRIPPEN | TCRIPPEN | Approved | | Plumbing | 2334923 |
| Mechanical | Original | D | 7/7/2026 | QUINTONW | QUINTONW | Disapproved: Per Architectural section views it appears ducts will be below floor ceiling assembly insulation. Duct loss on calculations? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2331058 |
| CO Springs DRE | Original | D | 7/2/2026 | SSADLER | SSADLER | Contact Charla at charla.hudspeth@coloradosprings.gov to discuss possible fees that are owed prior to building permit issuance.
Plans are consistent with the approved non use variances NVAR-24-0006 and NVAR-24-0010. Reduced setback and height are approved. | | CO Springs DRE | 2329874 |
| Zoning/Planning | Original | / | 6/29/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2328487 |
| Electrical | Original | D | 6/29/2026 | CONNERM | CONNERM | Emergency disconnect must comply with 230.85
Show compliance with R404.2 and R404.3 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2328413 |
| Construction | Original | A | 6/29/2026 | DOUGC | DOUGC | | | Construction | 2328314 |
| Enumeration | Original | A | 6/29/2026 | AMY | AMY | 1722 Woodburn Street (B ) was added to the mechanical sheet, IECC, Heat Loss Calcs, and HVAC Equip. for you. Add each address to the top of each home on the site plan. Enumerations did this as well. The north arrow was made clear by Enumerations . | | Enumeration | 2327805 |
| Submittal 2 | Original | / | 6/29/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2327760 |
| City Engr | Original | A | 6/24/2026 | JDAGNILLO | JDAGNILLO | | | City Engr | 2326400 |
| CO Springs DRE | Original | D | 6/23/2026 | SSADLER | SSADLER | Contact Charla at charla.hudspeth@coloradosprings.gov to discuss possible fees that are owed prior to building permit issuance.
Plans are consistent with the approved non use variances NVAR-24-0006 and NVAR-24-0010. Reduced setback and height are approved. | | CO Springs DRE | 2325673 |
| Stormwater | Original | N | 6/22/2026 | JLANDON | JLANDON | | | Stormwater | 2325081 |
| Energy | Original | D | 6/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2324920 |
| Plumbing | Original | D | 6/22/2026 | SHANEN | SHANEN | Reduced energy use in service water-heating as the additional energy efficiency option selected. Indicate which of the three IECC R408.2.3 efficiencies is being met.Show water meter location. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2324919 |
| Electrical | Original | D | 6/22/2026 | CONNERM | CONNERM | Show location of electrical panel and emergency disconnect
Show compliance with R404.2 and R404.3 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2324439 |
| Zoning/Planning | Original | / | 6/22/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2324417 |
| Mechanical | Original | D | 6/20/2026 | QUINTONW | QUINTONW | Disapproved: Heat Calculations have not been provided for the ADU they have only been provided for the Garage heater. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2324381 |
| Construction | Original | D | 6/19/2026 | DOUGC | DOUGC | Fire Separation Distance * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2324332 |
| Electronic Plan | Original | / | 6/17/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2322918 |
| Enumeration | Original | D | 6/4/2026 | AMY | AMY | The address that was assigned to the additional home is 1722 Woodburn Street (B). Add this address to the pages that have the address. Add each address to the top of each home on the site plan. The north arrow is not clear. The legal description & tax schedule number is incorrect for this property. The above information needs to be corrected even if another department has an approval stamp. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2316175 |
| Electronic Plan | Original | / | 6/4/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2316164 |
| | Original | / | 6/3/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/03/2026 for plan submitted 06/03/2026. Submit Date updated to now. Plan now open for review. | | | 2316151 |
| Energy | Original | / | 6/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2316117 |
| Floodplain | Original | N | 6/3/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6430206027) | | Floodplain | 2316116 |