| Energy | Original | A | 8/13/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2347372 |
| Electrical | Original | A | 8/13/2026 | CONNERM | CONNERM | | | Electrical | 2347371 |
| Elevators | Original | A | 8/13/2026 | ROBERTV | ROBERTV | RBD Note: Shop Drawings provided for (1) Symmetry Hydraulic Elevator w/ Machine Room. A17.1 - 2019, 2023 RBC | | Elevators | 2347319 |
| CO Springs DRE | Original | A | 8/13/2026 | SSADLER | SSADLER | All code requirements are met and the new single-family permit is approved. This approval does not allow the addition of a second dwelling unit to be rented or function separately from the primary unit or approve any easement encroachments. Architectural features encroaching into setback shall adhere to Chapter 7.4.203 of the Unified Development Code
Contact Trebor at trebor.brown@coloradosprings.gov to schedule the limit of disturbance inspection prior to work starting. | | CO Springs DRE | 2347253 |
| Zoning/Planning | Original | / | 8/12/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2346410 |
| City Engr | Original | A | 8/11/2026 | JDAGNILLO | JDAGNILLO | | | City Engr | 2346341 |
| Construction | Original | A | 8/11/2026 | MATTHEWA | MATTHEWA | | | Construction | 2346333 |
| Energy | Original | / | 8/11/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2346277 |
| Submittal 2 | Original | / | 8/11/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2346276 |
| CO Springs Fire | Original | D | 7/29/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2340465 |
| Energy | Original | A | 7/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2338650 |
| Mechanical | Original | A | 7/24/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2338649 |
| Plumbing | Original | A | 7/23/2026 | SHANEN | SHANEN | | | Plumbing | 2338102 |
| Electrical | Original | A | 7/21/2026 | CONNERM | CONNERM | | | Electrical | 2336648 |
| Electronic Plan | Original | / | 7/21/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2336647 |
| Elevators | Original | D | 7/20/2026 | ROBERTV | ROBERTV | Need site specific shop drawings, power data and controller short circuit current rating (SCCR) for all elevators being installed. All elevator shop drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved
Need to provide location of elevator controller and specify all required separate circuits for specific locations identified in NEC 620.22, 620.23, 620.24, 620.25. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2336626 |
| CO Springs DRE | Original | D | 7/16/2026 | SSADLER | SSADLER | On the hillside site plan we will need to see the vegetation identified. Here is the hillside checklist link. Look under the "Vegetation" and show what is required. https://coloradosprings.gov/system/files/2023-03/Hillside%20Plan%20Submittal%20Checklist.pdf | | CO Springs DRE | 2335070 |
| City Engr | Original | D | 7/15/2026 | DSOSA | DSOSA | The uploaded geohazard report has not been signed by EDRD. Please submit the geohazard report through the City’s electronic review system (ProjectDox). A link to ProjectDox and the user manual is provided below. https://coloradosprings.gov/stormwater/planreview.
Once the report has been approved by EDRD, upload a copy to the building permit plan set for City Engineering signoff on the permit. | | City Engr | 2334460 |
| Stormwater | Original | A | 7/14/2026 | JLANDON | JLANDON | | | Stormwater | 2334181 |
| Zoning/Planning | Original | / | 7/14/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2334023 |
| Construction | Original | A | 7/14/2026 | MATTHEWA | MATTHEWA | | | Construction | 2333994 |
| Electronic Plan | Original | / | 7/10/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2333253 |
| Enumeration | Original | A | 6/29/2026 | AMY | AMY | | | Enumeration | 2327852 |
| Electronic Plan | Original | / | 6/29/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2327834 |
| | Original | / | 6/26/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/26/2026 for plan submitted 06/26/2026. Submit Date updated to now. Plan now open for review. | | | 2327724 |
| Energy | Original | / | 6/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2327628 |
| Fire | Original | / | 6/26/2026 | RBD GIS | RBD GIS | Parcel 7512205024 is within the Wildland Urban Interface (WUI). Fire Department Review is required. | | Fire | 2327626 |
| Floodplain | Original | N | 6/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7512205024) | | Floodplain | 2327627 |