| City Engr | Original | A | 8/12/2026 | HVO | HVO | A geo-hazard report has been approved and is on file with the development plan application. | | City Engr | 2346956 |
| City Engr | Original | / | 8/10/2026 | | SCANNING | Location = City Engr by SCANNING | | City Engr | 2345146 |
| CO Springs Fire | Original | A | 8/7/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | phil.valdez | CO Springs Fire | 2345087 |
| Fire | Original | / | 7/30/2026 | | SSADLER | Location = Fire by SSADLER | | Fire | 2341251 |
| CO Springs DRE | Original | D | 7/30/2026 | SSADLER | SSADLER | On the site plan, show the building setbacks. City wide impact fees are due prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov | | CO Springs DRE | 2341250 |
| Zoning/Planning | Original | / | 7/24/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2338905 |
| Zoning/Planning | Original | / | 7/24/2026 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 2338747 |
| Plan Coordinator (Main) | Original | / | 7/24/2026 | | SHANEN | Location = Plan Coordinator (Main) by SHANEN | | Plan Coordinator (Main) | 2338730 |
| Plumbing | Original | A | 7/24/2026 | SHANEN | SHANEN | State of CO DOH approved plumbing plans. | | Plumbing | 2338729 |
| Plumbing (Main) | Original | / | 7/23/2026 | | QUINTONW | Location = Plumbing (Main) by QUINTONW | | Plumbing (Main) | 2338565 |
| Mechanical | Original | D | 7/23/2026 | QUINTONW | QUINTONW | Disapproved: Provide page 2 of Equipment Certificate for Whole house ventilation. Show on the basement plan the location of the whole house ventilation fan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2338560 |
| Mechanical (Main) | Original | / | 7/23/2026 | | SCANNING | Location = Mechanical (Main) by SCANNING | | Mechanical (Main) | 2338277 |
| Plan Coordinator (Main) | Original | / | 7/23/2026 | | CONNERM | Location = Plan Coordinator (Main) by CONNERM | | Plan Coordinator (Main) | 2338230 |
| Electrical | Original | A | 7/23/2026 | CONNERM | CONNERM | | | Electrical | 2338229 |
| Electrical (Main) | Original | / | 7/23/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electrical (Main) | 2338218 |
| Electrical (Main) | Original | / | 7/23/2026 | | SCANNING | Location = Electrical (Main) by SCANNING | | Electrical (Main) | 2338098 |
| Construction | Original | D | 7/23/2026 | BRIANB | BRIANB | - Missing site plan – unable to verify fire separation distances - Missing architectural plan for basement and will need to indicate if basement will be conditioned space. If conditioned space, then a IECC certificate will be required. - 2024 IECC certificate provided requires an approved Alternate Means and Method Application completed and approved prior to plan submittal. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2338081 |
| Construction (Main) | Original | / | 7/20/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Construction (Main) | 2336373 |
| Construction (Main) | Original | / | 6/30/2026 | | SCANNING | Location = Construction (Main) by SCANNING | | Construction (Main) | 2329119 |
| Plan Coordinator (Main) | Original | / | 6/30/2026 | | BECKYA | Location = Plan Coordinator (Main) by BECKYA | | Plan Coordinator (Main) | 2329009 |
| Enumeration | Original | D | 6/30/2026 | BECKYA | BECKYA | Provide a proper plot/site plan. Enumerations should not be approving Utility Plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2329005 |
| Enumeration (Main) | Original | / | 6/30/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Enumeration (Main) | 2328971 |
| Enumeration (Main) | Original | / | 6/30/2026 | | SCANNING | Location = Enumeration (Main) by SCANNING | | Enumeration (Main) | 2328957 |
| Plan Coordinator (Main) | Original | / | 6/30/2026 | | MELISSAF | Location = Plan Coordinator (Main) by MELISSAF | | Plan Coordinator (Main) | 2328948 |
| Out to Review | Original | / | 6/30/2026 | | MELISSAF | Location = Out to Review by MELISSAF | | Out to Review | 2328935 |
| | Original | / | 6/30/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/30/2026 for plan submitted 06/30/2026 | | | 2328934 |
| Energy | Original | N | 6/30/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2328932 |
| Fire | Original | / | 6/30/2026 | RBD GIS | RBD GIS | Parcel 7415114016 is within the Wildland Urban Interface (WUI). Fire Department Review is required. | | Fire | 2328930 |
| Floodplain | Original | N | 6/30/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7415114016) | | Floodplain | 2328931 |