| Energy | Original | D | 7/27/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2339528 |
| Mechanical | Original | A | 7/27/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2339527 |
| County Zoning | Original | D | 7/24/2026 | DSDYOUNGER | DSDYOUNGER | If the existing home is intended to be used as a "guest house" for occasional stays the Accessory Living Quarters Affidavit is required. The form must be filled out completely to include the address of the accessory living quarters (typically different than main address), legal description, and tax schedule number. The affidavit must be signed and notarized by all property owners on title. This information can be found on the El Paso County Assessor’s parcel search page. The affidavit must then be recorded with the Clerk and Recorder’s office. Once the recorded affidavit is received, upload or include the recorded document with your plan set to Pikes Peak Regional Building Department.
If the existing home will be used for permanent occupancy, please contact the Planner of the Day at 719-520-6944 for assistance. The affidavit would also be required as well.
Affidavit has been uploaded as an "other" document for your convenience. | | County Zoning | 2339142 |
| Zoning/Planning | Original | / | 7/24/2026 | DSDYOUNGER | DSDYOUNGER | In Current Review by DSDYOUNGER | | Zoning/Planning | 2339087 |
| Plumbing | Original | A | 7/24/2026 | SHANEN | SHANEN | | | Plumbing | 2339079 |
| Electrical | Original | D | 7/24/2026 | CONNERM | CONNERM | Verify locations of conduit and termination points serving the EV ready space.
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Show a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note requiring compliance with 2021 ECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
High efficacy lighting amendment for R404.2 does not apply to the unamended 2021 IECC. Plan will need to fully comply with original R.404.2 for lighting controls
Comply with R404.3 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2339071 |
| Electronic Plan | Original | / | 7/24/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2339068 |
| Construction | Original | D | 7/24/2026 | MATTHEWA | MATTHEWA | Code Reference // Provide manufacturer's specifications for wood stove for clearance to combustibles // Structural clarification // Need approved AM&M application to utilize 2024 IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2339064 |
| Electronic Plan | Original | / | 7/24/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2339010 |
| Enumeration | Original | D | 7/7/2026 | AMY | AMY | There is an existing home on site that is being labeled as a garage. Change the wording on the site plan. The new home proposed will need a separate address. The new home will be addressed as 12952 Herring Road. Change all pages of the plan to this address, even pages that have been approved by other departments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2331375 |
| Electronic Plan | Original | / | 7/7/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2331359 |
| | Original | / | 7/7/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/07/2026 for plan submitted 07/07/2026. Submit Date updated to now. Plan now open for review. | | | 2331114 |
| Stormwater | Original | / | 7/7/2026 | SYSTEM | SYSTEM | You will need to contact Stormwater department for approval prior to permit. This department will not review the plan electronically. | | Stormwater | 2331065 |
| Energy | Original | / | 7/7/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2331064 |
| Floodplain | Original | N | 7/7/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5208002005) | | Floodplain | 2331063 |