| CO Springs DRE | Original | D | 9/28/2026 | SSADLER | SSADLER | Upload the required hillside site plan | | CO Springs DRE | 2364075 |
| City Engr | Original | D | 9/25/2026 | JDAGNILLO | JDAGNILLO | Geological hazard report has been submitted in Project Dox (#STM-REV26-1024) and is currently being reviewed by CGS and the City. CGS comments are due back 9-30-26 and will be communicated directly in Project Dox. Once all comments are addressed and City approves report, upload City-signed report with this building permit plan set. | | City Engr | 2363713 |
| Energy | Original | D | 9/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2363381 |
| Mechanical | Original | D | 9/24/2026 | QUINTONW | QUINTONW | Disapproved: AM&M required for use of 2024 IECC. See equipment cert and Heat loss calcs for all disapproval comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2363380 |
| Stormwater | Original | N | 9/24/2026 | JDUNCAN | JDUNCAN | Activity does not disturb an acre or more and is not part of a larger common plan of development. No stormwater scope of work. | | Stormwater | 2363330 |
| Plumbing | Original | D | 9/24/2026 | SHANEN | SHANEN | Show the water meter location. Show or note compliance with 2021 IECC section R403.5.2. Provide shower pan dimensions. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2363123 |
| Zoning/Planning | Original | / | 9/24/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2363119 |
| Electrical | Original | D | 9/24/2026 | CONNERM | CONNERM | Specify and show potential PV pathway from attic to electric panel. If vertical pathway then specify so . Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
Show compliance with R404.2 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2363113 |
| Electronic Plan | Original | / | 9/24/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2363105 |
| Construction | Original | D | 9/24/2026 | BPHILLIPS | BPHILLIPS | IECC, roof loading criteria, solar ready roof plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2363100 |
| Electronic Plan | Original | / | 9/24/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2363079 |
| Enumeration | Original | A | 9/17/2026 | AMY | AMY | | | Enumeration | 2360701 |
| Electronic Plan | Original | / | 9/17/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2360699 |
| | Original | / | 9/17/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/17/2026 for plan submitted 09/17/2026. Submit Date updated to now. Plan now open for review. | | | 2360670 |
| Energy | Original | / | 9/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2360589 |
| Fire | Original | / | 9/17/2026 | RBD GIS | RBD GIS | Parcel 7423408053 is within the Wildland Urban Interface (WUI). Fire Department Review is required. | | Fire | 2360586 |
| Floodplain | Original | N | 9/17/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7423408053) | | Floodplain | 2360587 |